Records from 2016 to 2018. Most recent: inspection, 8 June 2018.
Inspection history · 4
8 June 2018
COC-MODU Annual
Type not classified · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6472702
5 June 2017
COC-MODU Renew
Type not classified · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 6113235
7 March 2017
In-Service Inspection
Physical examination · USCG Heartland District · USCG Heartland District (CGD-H) · Activity 6100431
16 March 2016
COC-MODU Annual
Type not classified · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 5835445
Engineering › Pressure Vessel › Maximum Allowable Working Pressure
Issued 5 June 2017
Resolved
ASME code pressure vessels must be tested and examined in accordance with the requirements in 46 CFR 61.10-5 every 5 years. PRessure vessels mustbe tested every 5 years. PV's have not been tested. NVIC 4-78 & 46 CFR 61.10-5
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 5 July 2017
Resolved 20 June 2017
Resolution: Recieved documentation from vessel rep showing that presseure vessels were tested in 2013 by ABS.
Lifesaving › Launching Appliances › Release Mechanism
Issued 5 June 2017
Resolved
Person's responsible for actual operations, including owners, operators, contactors, and subcontractors shall ensure that those operations subject to their control are conducted in compliance with workplace safety and health regulations and free from "recognized Hazards". The unit's lifeboars don ot have installed "white-lited" release hooks as per IMO MSC/CIR 1392.
Action required: 705 - Other - as specified
Due 8 August 2018
Resolved 9 July 2018
Fire Fighting › Fixed Fire Detection System › Control Panel
Issued 5 June 2017
Resolved
Each fire detection system and each smoke detection system on a unit must: have a chart or diagram next to the alarm that shows the location of the zones in the system and that contains the instructions for operating and testing the system.
Action required: 705 - Other - as specified
Due 14 July 2017
Resolved 20 June 2017
Resolution: Vessel rep provided photo documentation of installation of diagram and operating instructions.
Fire Fighting › Fixed Fire Detection System › Smoke Detectors
Issued 5 June 2017
Resolved
Each fire detection system must have a visual alarm and an audible alarm in the pilot house or at a normally manned control station. 2 tested smoke detectors failed to indicate.
Action required: 705 - Other - as specified
Due 14 July 2017
Resolved 20 June 2017
Resolution: Vessel Rep provided documentation from electrician on board unit that detectors were movedand tested sat.
Lifesaving › Line-Throwing Appliances › Lines
Issued 16 March 2016
Resolved
Quoit is not servicable.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 16 April 2016
Resolved 15 April 2016
Resolution: Quoits replaced.
Documentation › Logs/Records › Oil Record Book
Issued 16 March 2016
Resolved
Oil record book not filled in properly.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 16 April 2016
Resolved 15 April 2016
Resolution: Copy of record book indicates entries are being made properly.