MITSUI OCEAN FUJI

MITSUI OCEAN FUJI is a 2009 passenger vessel (inspected). The Coast Guard has recorded 28 inspections since 2016, most recently in July 2026, along with 20 deficiencies and 1 operational control.

Records from 2016 to 2026. Most recent: inspection, 17 July 2026.

Built
2009
Last inspected
17 July 2026
Documentation
Not in the documentation file of 10 August 2026
Controls
None recorded without a removal date

Coast Guard record current through 23 August 2026, retrieved 5 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Passenger Ship class in Maury's sources begin in 2016.

Inspection record

Last inspected 17 July 2026
…with no type recorded1
Operational controls None recorded without a removal date
Years with a record 8 calendar years (2016–2026)
Every line above is a count of records the US Coast Guard wrote, or a date it recorded. A blank resolution means none was recorded in this data; it does not establish that a deficiency is outstanding. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Identity

9417086
940685
Flag
BAHAMAS, THE
Maury page id
psix-940685

Documentation record

Tonnage as PSIX records it18873 - Displacement, Ton
10657 - Convention (Subpart B), Net Ton
32477 - Convention (Subpart B), Gross Ton
3000 - Dead Weight, Ton
This hull's Official Number is not in the NVDC file dated 10 August 2026 as served by NOAA Fisheries, so no documentation record is shown. Absence from that file is a fact about the file, not about the hull.
Vessel history report
Every record for this hull, in one document — $299

Every recorded inspection, 2016 to 2026 for this class, in one chronology · every deficiency, with system, dates and resolution · operational controls imposed and removed · every name this hull has been recorded under · the vessels it was inspected alongside, and when · how its record compares with hulls of similar age and size, as a fact about the population and never a judgement about this vessel.

Read one first, in full: a forty-year chronology · a hull that changed operators four times · the sparse case, shown as an example, not for sale.

This report is in development and is not for sale yet. There is no date, and nothing is charged. Leave an email and we will tell you when it exists, once.

Inspection history · 28

17 July 2026 VRP Review
Administrative · U.S. COAST GUARD FORCES MICRONESIA/SECTOR GUAM · USCG Oceania District (CGD-O) · Activity 8443874
30 March 2025 PSC B · COC-CVE Annual
Physical examination · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 8098757
8 January 2025 VRP Review
Administrative · U.S. COAST GUARD FORCES MICRONESIA/SECTOR GUAM · USCG Oceania District (CGD-O) · Activity 8059835
9 May 2024 Deficiency Check
Physical examination · Sector Western Alaska and U.S. Arctic · USCG Arctic District (CGD-A) · Activity 7910189
5 May 2024 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7924159
2 May 2024 COC-CVE Annual · PSC A
Physical examination · Sector Western Alaska and U.S. Arctic · USCG Arctic District (CGD-A) · Activity 7903662
21 February 2024 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7878074
6 February 2024 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7877270
5 December 2023 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7842563
15 October 2023 COC-CVE Quarterly · PSC B
Physical examination · Sector Puget Sound · USCG Northwest District (CGD-NW) · Activity 7807728
7 July 2023 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7833433
14 June 2023 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7796043
19 May 2023 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7738843
15 May 2023 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7739605
30 April 2023 COC-CVE Annual · PSC A
Physical examination · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 7677108
28 February 2023 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7643550
4 January 2023 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7616444
30 November 2022 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7602172
13 October 2022 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7577056
24 August 2022 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7542940
9 August 2022 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7529430
29 April 2022 Deficiency Check · Administrative Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 7440676
25 April 2022 PSC B · COC-CVE Initial · COC-CVE Annual
Physical examination · Sector San Juan · USCG Southeast District (CGD-SE) · Activity 7436053
25 April 2022 Type not recorded
No type recorded · Sector San Juan · USCG Southeast District (CGD-SE) · Activity 7437356
8 April 2020 In-Service Inspection
Physical examination · USCG Southeast District (dp) · USCG Southeast District (CGD-SE) · Activity 6937090
30 October 2017 COC-CVE Annual · ISPS III Exam · Ballast Water Examination
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 6294739
19 December 2016 COC-CVE Annual · ISPS II Exam · Ballast Water Examination
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 6049284
5 January 2016 Deficiency Check · Administrative Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 5791066

Deficiency record · 20

01 - Certificates & Documentation › 012 - Crew Certificates › Cert for personnel on survival craft & rescue boat
Issued 30 March 2025 Resolved
The level of knowledge of the subjects listed in column two of table A-VI/2-1 shall be sufficient to enable the candidate to launch and take charge of a survival craft or rescue boat in emergency situations. Port side life raft launching crew were unable to demonstrate adequate launching of liferaft without significant on-scene training and assistance of Safety Officer. STCW 2017 A-VI/2.2
Condition: Invalid
Action required: 17 - Rectify deficiencies prior to departure
Resolved 30 March 2025
Resolution: Crew demonstrated adequate launching after initial failure.
11 - Life Saving Appliances › N/A - No Subsystem › Launching arrangements for survival craft
Issued 30 March 2025 Resolved
Before the ship leaves port and at all times during the voyage, all lifesaving appliances shall be in working order and ready for immediate use. Port side life raft davit brake is not operational. 74 SOLAS 20 III/16.3
Condition: Invalid
Action required: 17 - Rectify deficiencies prior to departure
Due 12 April 2025
Resolved 15 April 2025
Resolution: Recieved class report with resolution. Added to documents.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 30 March 2025 Resolved
The fire integrity of the divisions shall be maintained at openings and penetrations. 02 Emergency escape hatches leading out of the engine room were locked in the open position. 74 SOLAS 04 II-2/9.1.3
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 30 March 2025
Resolution: Escape hatches closed.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 30 March 2025 Resolved
The fire integrity of the divisions shall be maintained at openings and penetrations. 06 Fire Screen doors throughout the vessel were not closing fully. 74 SOLAS 20 II-2/9.1.3
Condition: Design Flaw
Action required: 17 - Rectify deficiencies prior to departure
Resolved 30 March 2025
Resolution: All fire screen doors identified were fixed.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 30 March 2025 Resolved
The function of fixed fire detection and fire alarm systems shall be tested to the satisfaction of the administration by means of equipment producing hot air at the appropriate temperature. Ships crew ran out of cartridges to conduct heat detection tests in the galley for heat detectors. Deck 8 galley heat detection could not be tested. 74 SOLAS 04 II-2/7.2.4.2
Condition: Invalid
Action required: 16 - Rectify deficiencies w/in 14 days
Due 12 April 2025
Resolved 11 April 2025
Resolution: Vessel provided class report with more equipment for adequate testing.
15 - Safety Management Systems (ISM) › N/A - No Subsystem › Safety and environment policy
Issued 30 March 2025 Resolved
The company should ensure that the safety and environmental-protection policy is implemented and maintained at all levels of the organization, both ship-based and shore-based. Throughout the entirety of the exam, several ISM related concerns were identified. These issues are highlighted in deficiencies 01, 02, and 03. An ISM audit is required to resolve this deficiency. 74 SOLAS 20 IX/3.1 ISM Code A 2.2
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 28 April 2025
Resolved 17 April 2025
Resolution: ISM audit completed, reviewed and atached in documents.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 30 March 2025 Resolved
Sauna electrically heated ovens shall be provide with a timer. Sauna did not have a timer. 74 SOLAS 04 II-2/9.2.2.3.4.6
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 28 April 2025
Resolved 15 April 2025
Resolution: Recieved class report with resolution. Added to documents.
01 - Certificates & Documentation › 011 - Ships Certificates › Load Lines (including Exemption)
Issued 2 May 2024 Resolved
An International Load Line Certificate shall be issued to every ship which has been surveyed and marked in accordance with the present Convention. Vessel's deck line is painted the same color as the hull. Load Line Convention Article 16(1) 50a Code 01108
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 2 June 2024
Resolved 9 May 2024
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 2 May 2024 Resolved
Fire doors in main vertical zone bulkheads, galley boundaries and stairway enclosures shall be self-closing and be capable of closing with an angle of inclination of up to 3.5° opposing closure. Roller shutter 3.3.19 between crew galley and crew mess did not close via automatic or by manual means. 74 SOLAS 20 II-2/9.4.1.1.5.1 10c Code 07105
Condition: Improper Installation
Action required: 10 - Deficiency Rectified
Due 2 May 2024
Resolved 2 May 2024
11 - Life Saving Appliances › N/A - No Subsystem › Stowage and provision of liferafts
Issued 2 May 2024 Resolved
Each liferaft or group of liferafts shall be stowed with a float-free arrangement so that each floats free and, if inflatable, inflates automatically when the ship sinks. Starboard side life raft was found connected to the vessel and not to the float-free arrangement. 74 SOLAS 20 III/13.4.2 10c Code 11110
Condition: Improper Installation
Action required: 10 - Deficiency Rectified
Due 2 May 2024
Resolved 2 May 2024
04 - Emergency Systems › N/A - No Subsystem › Abandon ship drills
Issued 2 May 2024 Resolved
Every crew member with assigned emergency duties shall be familiar with these duties before the voyage begins. Starboard side life raft crew was not familiar with the life raft and which line was the painter line and which lines were the bowsing lines. 74 SOLAS 20 III/19.2.1 10c Code 04110
Condition: Invalid
Action required: 10 - Deficiency Rectified
Due 2 May 2024
Resolved 2 May 2024
07 - Fire Safety › N/A - No Subsystem › Operation of Fire protection systems
Issued 30 April 2023 Resolved
Fire protection systems and fire-fighting systems and appliances shall be maintained ready for use. Forward boiler section valve in the high pressure water mist system failed and was not working as designed. 74 SOLAS (20)II-2/14.1.1
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 30 April 2023
Resolution: PSCOs returned to vessel to clear prior to departure. The crew replaced a seal inside the valve that had gone bad, that was keeping the system from resetting.
07 - Fire Safety › N/A - No Subsystem › Fire patrol
Issued 30 April 2023 Resolved
Except for hatches between cargo, special category, store, and baggage space, and between such spaces and the weather decks, openings shall be provided with permanently attached means of closing which shall be at least as effective for resisting fires as the divisions in which they are fitted. Fire Screen Door number 4.3.38 is a double leaf door which overlaps after closing due to ineffective sequencing bar. 74 SOLAS 09 II-2/9.4.1.1.1
Condition: Improper/Lack of Maintenance
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 15 October 2023
Resolution: FD 4.3.38 tested and clased satisfactorily.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 30 April 2023 Resolved
Except for hatches between cargo, special category, store, and baggage space, and between such spaces and the weather decks, openings shall be provided with permanently attached means of closing which shall be at least as effective for resisting fires as the divisions in which they are fitted. Fire Screen Door numbers 1.2.2, 1.2.1, and 3.3.34 did not latch completely. 74 SOLAS 09 II-2/9.4.1.1.1
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Resolved 30 April 2023
Resolution: Ship carpenter corrected all listed doors. PSCO witnessed all doors latching properly.
04 - Emergency Systems › N/A - No Subsystem › Abandon ship drills
Issued 30 April 2023 Resolved
Every crew member with assigned emergency duties shall be familiar with these duties before the voyage begins. While testing the starboard side life raft davit, the raft onload release handle was caught under the raft cradle, causing the liferaft to release from the hook. 74 SOLAS 20 III/19.2.1
Action required: 10 - Deficiency Rectified
Resolved 30 April 2023
Resolution: Crew demonstrated for PSCOs another liferaft deployment with no issues witnessed.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 25 April 2022 Resolved
Main and auxiliary machinery essential for the propulsion and safety of the ship shall be provided with effective means for its operation an control. STBD Main propulsion engine does not operate at full capacity. 74 SOLAS (20)II-1/31
Condition: Improper/Lack of Maintenance
Action required: 15 - Rectify deficiencies by next port
Due 7 May 2022
Resolved 28 April 2022
Resolution: Received RO report that STBD engine has been repaired.
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 25 April 2022 Resolved
Means of escape from control stations, accommodation spaces and service spaces shall be maintained in a safe condition, clear of obstacles. Multiple stairway landings in way of muster stations had signs obstructing passage. 74 SOLAS (20) II-2/13.1.2
Action required: 10 - Deficiency Rectified
Resolved 25 April 2022
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 25 April 2022 Resolved
The following fire protection systems shall be kept in good order so as to ensure their required performance if a fire occurs: structural fire protection, including fire-resistant divisions, and protection of openings in these divisions. The following fire screen doors required adjustment. FSD 7.4.47, 7.5.34, and 9.5.44. 74 SOLAS (20) II-2/14.2.1.1
Action required: 10 - Deficiency Rectified
Resolved 25 April 2022
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 25 April 2022 Resolved
Waste receptacles shall be constructed of non-combustible materials with no openings in the sides or bottom. Combustible trash was not stowed in a non-combustible receptacle in the Main Laundry Space.
Action required: 10 - Deficiency Rectified
Due 7 May 2022
Resolved 25 April 2022
Fire Fighting › Combustible Materials › Paints/Varnishes/Other Finishes
Issued 19 December 2016 Resolved
The storage room in the spa (a. Cat. 7) on deck 9 has mnore than daily use amount of flammable material stored in space. There is approximately one month's amount of flammable material currently stored in the space, per information provided by the crew. - 74Solas(14) CH II-2/Reg 9.2.2.3.2.2
Due 19 December 2016
Resolved 19 December 2016

Ownership record

The Coast Guard's documentation record for this hull -- the Abstract of Title, with its owners and liens as filed -- is not in PSIX. Ask, and Maury buys it from the National Vessel Documentation Center, files it here with its date, and every reader of this page gets it.