Records from 2008 to 2025. Most recent: inspection, 15 May 2025.
Inspection history · 14
15 May 2025
COI Inspection · Administrative Inspection · Deficiency Check
Physical examination · Marine Safety Unit Duluth · USCG Great Lakes District (CGD-GL) · Activity 8133366
5 November 2024
Administrative Inspection
Administrative · Marine Safety Unit Duluth · USCG Great Lakes District (CGD-GL) · Activity 8029790
16 October 2023
Administrative Inspection
Administrative · Marine Safety Unit Duluth · USCG Great Lakes District (CGD-GL) · Activity 7809455
13 September 2023
Administrative Inspection · COI Inspection
Physical examination · Marine Safety Unit Duluth · USCG Great Lakes District (CGD-GL) · Activity 7790763
17 April 2023
Internal Structural Exam · Drydock Exam · Examination of Repairs
Physical examination · Marine Safety Unit Duluth · USCG Great Lakes District (CGD-GL) · Activity 7671489
10 June 2022
Annual Inspection
Physical examination · Sector Northern Great Lakes · USCG Great Lakes District (CGD-GL) · Activity 7473563
2 December 2021
Administrative Inspection
Administrative · Marine Safety Unit Duluth · USCG Great Lakes District (CGD-GL) · Activity 7360873
28 October 2020
Administrative Inspection · DAPI Audit · Annual Inspection
Physical examination · Marine Safety Unit Duluth · USCG Great Lakes District (CGD-GL) · Activity 7086429
7 November 2019
Annual Inspection · Deficiency Check · DAPI Audit
Physical examination · Marine Safety Unit Duluth · USCG Great Lakes District (CGD-GL) · Activity 6851515
22 May 2019
Administrative Inspection
Administrative · Marine Safety Unit Duluth · USCG Great Lakes District (CGD-GL) · Activity 6690880
6 April 2018
Initial Certification · Uninspected Other · Deficiency Check · Administrative Inspection · DAPI Audit
Physical examination · Marine Safety Unit Duluth · USCG Great Lakes District (CGD-GL) · Activity 6408981
29 April 2009
Deficiency Check
Physical examination · Marine Safety Unit Duluth · USCG Great Lakes District (CGD-GL) · Activity 3464717
12 December 2008
Type not recorded
No type recorded · Marine Safety Unit Duluth · USCG Great Lakes District (CGD-GL) · Activity 3402670
18 September 2008
Type not recorded
No type recorded · Marine Safety Unit Duluth · USCG Great Lakes District (CGD-GL) · Activity 3327257
11 - Life Saving Appliances › N/A - No Subsystem › Immersion suits
Issued 15 May 2025
Resolved
Towing vessel must carry at least one appropriate-size immersion suit for each person onboard; seams of one immersion suit were deteriorating, repair or replace. Limited to five total POB until rectified.
46 CFR 141.350
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 June 2025
Resolved 2 June 2025
Resolution: 2 new immersion suits placed on board
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 15 May 2025
Resolved
Each towing vessel must have a fire-detection system installed to detect engine room fires, ensuring that the design of the system and its installation on the towing vessel is certified and inspected by a registered professional engineer with experience in fire-detection system design, NICET level IV tech, or authorized class society; required certification was not available.
46 CFR 142.330(a)(7)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 June 2025
Resolved 20 June 2025
Resolution: PE Letter obtained
10 - Safety of Navigation › N/A - No Subsystem › Lights, shapes, sound-signals
Issued 15 May 2025
Resolved
Each towing vessel must be equipped with navigation lights, shapes, and sound signals in accordance with COLREGS; vessel did not have any dayshapes; acquire minimum of 3 ball and 1 diamond dayshape.
46 CFR 140.720
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 June 2025
Resolved 29 May 2025
Resolution: Dayshapes purchased
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 15 May 2025
Resolved
Electrical equipment must be marked with its respective current and voltage ratings; distrib panels not marked with rated load of each circuit. Label circuit directory with rated load, ensure no breaker exceeds rated load.
46 CFR 143.400
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 June 2025
Resolved 5 June 2025
Resolution: Panel boards labeled with current rating of each circuit.
01 - Certificates & Documentation › 013 - Documents › Log-books/compulsory entries
Issued 15 May 2025
Resolved
The following list of items must be recorded in the TVR, official logbook:
(1) Personnel records, in accordance with § 140.400;
(2) Safety orientation, in accordance with § 140.410;
(3) Record of drills and instruction, in accordance with § 140.420;
(4) Examinations and tests, in accordance with § 140.61(5) Operative navigational safety equipment, in accordance with § 140.620;
(6) Navigation assessment, in accordance with § 140.635;
(7) Navigation safety training, in accordance with § 140.645;
(8) Oil residue discharges and disposals, in accordance with § 140.655;
(9) Record of inspection of towing gear, in accordance with § 140.820; and
(10) Fire-detection and fixed fire-extinguishing, in accordance with § 142.240.
Not all items were readily locatable during inspection; correct by next topside.
46 CFR 140.915
Action required: 705 - Other - as specified
Resolved 21 August 2026
Resolution: Required items logged.
08 - Alarms › N/A - No Subsystem › General alarm
Issued 15 May 2025
Resolved
Each towing vessel must be fitted with a general alarm; GA was not operational.
46 CFR 143.235(b)
Action required: 10 - Deficiency Rectified
Resolved 16 May 2025
Resolution: GA operational upon MI departure
01 - Certificates & Documentation › 011 - Ships Certificates › Certificate of Inspection (COI)
Issued 5 November 2024
Resolved
Vessel was unable to complete Annual Inspection, within 3 months of it's anniversary date, due to crew-availability shortfalls at end of the 2024 season. Vessel is laid-up in Duluth, MN for the winter. Vessel may not operate commercially until a Certificate of Inspection (COI) has been satisfactorily completed (anticipate Spring 2025).
Action required: 705 - Other - as specified
Due 15 April 2025
Resolved 15 May 2025
Resolution: COI inspection complete; COI reissued
11 - Life Saving Appliances › N/A - No Subsystem › Inflatable liferafts
Issued 10 June 2022
Resolved
Each liferaft must have a painter system providing a connection between the vessel and the liferaft. The painter for the liferaft is not connected to the vessel.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 June 2022
Resolved 24 June 2022
Resolution: Tied painter through D-ring.
11 - Life Saving Appliances › N/A - No Subsystem › Means of rescue
Issued 10 June 2022
Resolved
The owner or managing operator of a towing vessel must establish procedures to address fall overboard prevention and recovery of persons in the water, including, but not limited to use of retrieval equipment. The crew is unfamiliar with procedures for recovery of a person in the water and requires
additional equipment to accompany the installed davit.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 11 July 2022
Resolved 24 June 2022
Resolution: Operator purchased man overboard recovery cradle for vessel.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 10 June 2022
Resolved
Flexible connections between cylinders and distribution piping of semi-portable or fixed carbon dioxide fire extinguishing systems and discharge hoses in semi-portable carbon dioxide fire extinguishing systems must be replaced or tested at a pressure of 6.9 MPa (1,000 psig). Dry rot was identified on the flex loop of the semi-portable system in the Fidley. Test to the required pressure or replace in kind.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 11 July 2022
Resolved 24 June 2022
Resolution: Installed new flexible connections.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Operation of machinery
Issued 10 June 2022
Resolved
Machinery must be designed and maintained to provide for safe operation of the towing vessel and safety of persons onboard under normal and emergency conditions. One of the steering stop assists is non-operational and allows for overextension of the ram.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 11 July 2022
Resolved 24 June 2022
Resolution: Received pictures showing satisfactory repairs.
09 - Working and Living Conditions › 091 - Living Conditions › Sanitary Facilities
Issued 10 June 2022
Resolved
The vessel, including crew's quarters and the galley, must be kept in a sanitary condition. The vessel does not have a functioning head or accompanying sink. Re-install prior to overnight voyages.
Action required: 705 - Other - as specified
Resolved 19 October 2023
09 - Working and Living Conditions › 092 - Working Conditions › Safe means of access
Issued 10 June 2022
Resolved
Each escape hatch and emergency exit used as means of escape must be marked on both sides in clearly legible letters at least 50 millimeters (2 inches) high: “EMERGENCY EXIT, KEEP CLEAR”. The escape hatch in the engine room does not have proper markings.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 11 July 2022
Resolved 24 June 2022
Resolution: Received pictures showing new marking.
09 - Working and Living Conditions › 092 - Working Conditions › Machinery
Issued 7 November 2019
Resolved
Conduct hydro static test of air receivers in E/R in the presence of a CG Marine Inspector.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 7 December 2019
Resolved 15 November 2019
Resolution: witnessed hydro testing of air recievers
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 7 November 2019
Resolved
Electrical equipment and electrical cables must be suitable protected from wet and corrosive environments. Install junction box for spliced wiring on flying bridge.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 7 December 2019
Resolved 15 November 2019
Resolution: Owner provided evidence of non-power wiring, def revoked.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 7 November 2019
Resolved
Electrical equipment and electrical cables must be suitable protected from wet and corrosive environments. Renew wiring to port navigation light where sheathing had become wasted.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 7 December 2019
Resolved 15 November 2019
Resolution: Wiring renewed
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 7 November 2019
Resolved
Electrical systems and equipment must function properly and minimize system failures and fire and shock hazards. Remove dead ended cabling in overhead of upper stateroom.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 7 December 2019
Resolved 15 November 2019
Resolution: Wiring removed.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 7 November 2019
Resolved
Electrical conducters passing through watertight bulkheads must be installed so that the bulkhead remains water tight. 07 bulkhead penetrations in upper stateroom to be renewed or made water/fire tight.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 7 December 2019
Resolved 15 November 2019
Resolution: Bulkhead penetrations all filled with firestop.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Railing, gangway, walkway and means for safe passage
Issued 7 November 2019
Resolved
An exposed hazard such as gears and rotating machinery must be protected by a cover, guard or rail. Repair broken railing on upper engine room space aft by CO2 bottles.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 7 December 2019
Resolved 15 November 2019
Resolution: Railing repaired.
09 - Working and Living Conditions › 092 - Working Conditions › Lighting (Working spaces)
Issued 7 November 2019
Resolved
Sufficent lighting suitable for the marine environment must be provided within crew working areas. Renew broken light fixture globe on aft deck.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 7 December 2019
Resolved 15 November 2019
Resolution: Lighting globes renewed.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 3 May 2018
Resolved
Install oversized washers of 1/2" steel plate to seal the bolt openings through the main deck where the winches are mounted.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 3 June 2018
Resolved 21 May 2018
Resolution: Sealing washers installed under deck bolts.
09 - Working and Living Conditions › 092 - Working Conditions › Ropes and wires
Issued 3 May 2018
Resolved
Starboard side forward cleat shall either be removed or welded to the deck.
Condition: Damaged By Earlier Event
Action required: 705 - Other - as specified
Due 3 June 2018
Resolved 21 May 2018
Resolution: Cleat welded to deck.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 3 May 2018
Resolved
In the starboard deck locker (old CO2 space) an electrical cable is improperly spliced. The wiring connection shall be made inside of a junction box.
Action required: 705 - Other - as specified
Due 3 June 2018
Resolved 21 May 2018
Resolution: Wiring connection installed inside of j-box.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 3 May 2018
Resolved
Renew all air receiver pressure relief valves with appropriate valves with a relif setting not to exceed 250 psig.
Action required: 705 - Other - as specified
Due 3 June 2018
Resolved 21 May 2018
Resolution: New 200 psig relief valves were installed.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 3 May 2018
Resolved
The opening in the DC electrical panel is not gaurded to prevent inadvertent access. Install a cover or guard over the opening.
Action required: 705 - Other - as specified
Due 3 June 2018
Resolved 21 May 2018