ASPHALT SPRING

ASPHALT SPRING is a 2007 tank ship. The Coast Guard has recorded 14 inspections since 2016, most recently in March 2019, along with 21 deficiencies.

Records from 2016 to 2019. Most recent: inspection, 19 March 2019.

Built
2007
Last inspected
19 March 2019
Documentation
Not in the documentation file of 10 August 2026
Controls
None recorded without a removal date

This record may be incomplete: the most recent inspection recorded for this vessel was 7 years ago. Maury shows what the Coast Guard recorded, not whether the vessel has been inspected since, is still in service, or what condition it is in. Coast Guard record current through 23 August 2026, retrieved 5 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Tank Ship class in Maury's sources begin in 2016.

Inspection record

Last inspected 19 March 2019
…with no type recorded1
Operational controls None recorded without a removal date
Years with a record 4 calendar years (2016–2019)
Every line above is a count of records the US Coast Guard wrote, or a date it recorded. A blank resolution means none was recorded in this data; it does not establish that a deficiency is outstanding. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Identity

9394727
956872
Flag
MARSHALL ISLANDS
Maury page id
psix-956872

Documentation record

Tonnage as PSIX records it6457 - Convention (Subpart B), Gross Ton
6654 - Dead Weight, Metric Ton
11128 - Displacement, Metric Ton
1985 - Convention (Subpart B), Net Ton
This hull's Official Number is not in the NVDC file dated 10 August 2026 as served by NOAA Fisheries, so no documentation record is shown. Absence from that file is a fact about the file, not about the hull.
Vessel history report

A report is not offered for this hull. Its record holds only 2 of the seven kinds of material a report is built from: inspections, deficiencies, operational controls, tow-unit appearances, casualty records, dimensions and documentation. That is a statement about the record, not about the vessel. What a sparse-record report looks like.

Inspection history · 14

19 March 2019 Administrative Inspection
Administrative · Sector Corpus Christi · USCG Heartland District (CGD-H) · Activity 6645443
21 January 2019 COE-Administrative
Administrative · Sector Corpus Christi · USCG Heartland District (CGD-H) · Activity 6613722
10 September 2018 COE-Dockside
Physical examination · Sector San Juan · USCG Southeast District (CGD-SE) · Activity 6536082
16 July 2018 COC-TVE Annual · ISPS III Exam · Ballast Water Examination
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 6481652
20 June 2018 In-Service Inspection · Administrative Inspection
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 6450091
4 March 2018 ISPS II Exam
Physical examination · Sector Corpus Christi · USCG Heartland District (CGD-H) · Activity 6364683
29 January 2018 Administrative Inspection
Administrative · Sector Mobile · USCG Heartland District (CGD-H) · Activity 6345364
4 January 2018 Deficiency Check
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 6330794
23 October 2017 In-Service Inspection · Deficiency Check
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 6290292
18 October 2017 Administrative Inspection
Administrative · Sector Mobile · USCG Heartland District (CGD-H) · Activity 6290168
21 July 2017 Deficiency Check
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 6216487
19 July 2017 COC-TVE Renew · Ballast Water Examination · ISPS II Exam
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 6210362
23 November 2016 Type not recorded
No type recorded · Sector Corpus Christi · USCG Heartland District (CGD-H) · Activity 6073463
27 July 2016 COC-TVE Annual · ISPS II Exam · COE-Dockside · Ballast Water Examination
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 5954525

Deficiency record · 21

Engineering › Fuel Oil Service System › Piping
Issued 23 October 2017 Resolved
0750-Means shall be provided to control leaks of flammable liquids. PSCO noted fuel oil leaks on both main engines, #2 & #3 aux engines and #2 circulator pump in the purifier room. 74SOLAS(14)II-2/4.1 40a,c
Condition: Improper/Lack of Maintenance
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 4 January 2018
Deck/Cargo › Cargo Transfer/Lightering (liquid) › Cargo Manifold
Issued 23 October 2017 Resolved
1150-The condition of the ship and its equip shall be maintained to conform with the provisions of the present regs to ensure that the ship in all respects will remain fit to proceed to sea without danger to the ship or persons on board. PSCO noted aft cargo manifold valve handles wasted off & air blow down line severely wasted & INOP. 74SOLAS(14)I/11 40a,c
Condition: Improper/Lack of Maintenance
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 4 January 2018
Engineering › Compressed Air System (control) › Receiver/Bottle
Issued 23 October 2017 Resolved
0999-In every ship means shall be provided to prevent overpressure in any part of compressed air systems, suitable pressure relief arrangements shall be provided for all systems. PSCO noted two pressure vessels on deck with no relief valves & no data plate stating MAWP. 74SOLAS(04)II-1/34.1 40a,c
Condition: Improper/Lack of Maintenance
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 4 January 2018
Accommodation/Occupational Safety › Occupational Safety › Tripping/Falling Hazard
Issued 23 October 2017 Resolved
0999-Every tanker shall be provided with means to enable the crew to gain safe access to the bow. PSCO noted grating severly wasted on the catwalk. 74SOLAS(04)II-1/3-3.2 40c
Condition: Improper/Lack of Maintenance
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 4 January 2018
Fire Fighting › Ventilation Systems › Duct Hatches
Issued 19 July 2017 Resolved
1275 - Ventilations air pipes - Ventilators in position 1 or 2 to spaces below freeboard deck or decks of enclosed superstructures shall have coamings of steel or other equivalent material, substantially constructed and efficiently connected to the deck. PSCO noted multiple ventilators not closing properly. ICLL I/19.1
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 21 July 2017
Resolution: Received class report
Engineering › Fuel Oil Storage/Transfer System › Hose
Issued 19 July 2017 Resolved
0750 - Fire prevention - Oil fuel lines shall be screened or otherwise suitably protected to avoid oil spray or oil leakage onto the sources of ignition. PSCO noted fuel lines throughout engine room not properly protected. 74 SOLAS (14) II-2/4.2.2.5.3
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Resolved 21 July 2017
Resolution: Received class report
Fire Fighting › Structural - A Class Divisions › Fire Doors
Issued 19 July 2017 Resolved
0750 - Fire prevention - The fire integrity of the divisions shall be maintained at openings at penetrations. PSCO noted fire doors in main stairwells not closing properly. 74 SOLAS (14) II-2/9.1.3
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 19 July 2017
Resolution: Stairwell self-closing fire doors all adjusted and close properly.
Fire Fighting › Portable CO2 Fire Extinguisher › Service
Issued 19 July 2017 Resolved
0720 - Fire fighting equipment - Maintenance, testing, and inspections shall be carried out based on the guidelines dveloped by the organization. PSCO noted several portable fire extinguishers not annually serviced as required. 74 SOLAS (14) II-2/14.2.2.1
Condition: Placed in Improper Service
Action required: 17 - Rectify deficiencies prior to departure
Resolved 21 July 2017
Resolution: Received class report
Fire Fighting › Means of Escape › Blocked
Issued 19 July 2017 Resolved
0999 - Other (Safety In General) - Escape routes shall be maintained in a safe condition, clear of obstacles. PSCO noted emergency exit in emergency generator room locked. 74 SOLAS (14) II-2/13.1
Condition: Placed in Improper Service
Action required: 17 - Rectify deficiencies prior to departure
Due 21 July 2017
Resolved 19 July 2017
Resolution: Emergency exit unlocked and obstacles removed.
Engineering › Fuel Oil Service System › Valve
Issued 19 July 2017 Resolved
2099 - Other (SOLAS Operational Def.) - The machinery, boilers, and other pressure vessels, associated piping systems and fittings shall be of a design and construction adequate for the service for which they are intended. PSCO found several valve handles on numerous vital systems in engine room missing. 74 SOLAS (14) II-2/26.1
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 21 July 2017
Resolution: Received class report
Fire Fighting › Structural - A Class Divisions › Flammable Liquids Storage Spaces
Issued 19 July 2017 Resolved
0750 - Fire prevention - Ignition sources shall be seperated from combustible materials and flammable liquids. PSCO noted combustible materials in the emergency generator space. 74 SOLAS (14) II-2/4.15
Condition: Placed in Improper Service
Action required: 17 - Rectify deficiencies prior to departure
Resolved 21 July 2017
Resolution: Received class report
Electrical › Electric Supply System (service) › Cable
Issued 19 July 2017 Resolved
0830 - Pipes wires (insulat.) - accident prev. - Cables and wiring shall be installed and supported in such a manner as to avoid chafing or other damage. PSCO noted loose connections on both pumps in the steering gear room. 74 SOLAS (04) II-1/45
Condition: Improper/Lack of Maintenance
Due 19 July 2017
Resolved 19 July 2017
Resolution: Loose wiring properly supported and secured.
Electrical › Electric Supply System (service) › Cable
Issued 19 July 2017 Resolved
0830 - Pipes wires (insulat.) - accident prev. - Cables and wiring shall be installed and supported in such a manner as to avoid chafing or other damage. PSCO noted loose wire connection in engine room above the OWS. 74 SOLAS (04) II-1/45
Condition: Improper/Lack of Maintenance
Due 19 July 2017
Resolved 19 July 2017
Resolution: Exposed wiring properly covered and supported.
Fire Fighting › Structural - A Class Divisions › Flammable Liquids Storage Spaces
Issued 19 July 2017 Resolved
0750 - Fire prevention - Means shall be provided to control leaks of flammable liquids. PSCO noted excessive oil in the steering gear and main engine room. 74 SOLAS (14) II-2/4.1
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 19 July 2017
Resolved 19 July 2017
Resolution: Flammable liquids removed from space.
Electrical › Electric Generation Source (emergency) › Generator
Issued 19 July 2017 Resolved
1499 - Other (Prop. & Aux. Machinery) - The emergency source of electrical power shall be located above the uppermost continuous deck and shall be readily accessible from the open deck. PSCO noted the emergency generator is below the uppermost continuous deck and not readily accessible from the open deck. 74 SOLAS (04) II-1/43.1.2
Condition: Improper Installation
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 23 October 2017
Resolution: Received Class report attesting to construction.
Documentation › Safety/Response Plans/Programs › Fire Control Plans
Issued 19 July 2017 Resolved
2035 - Fire control plan - Plans and booklets shall be kept up to date, any alteration thereto shall be recorded as soon as practicable. PSCO noted multiple discrepancies with their fire control plan. 74 SOLAS (14) II-2/15.2.4.1
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 19 August 2017
Resolved 21 July 2017
Resolution: Received class report
Documentation › Logs/Records › Bunker Delivery Notes/Samples
Issued 19 July 2017 Resolved
2490 - Other - The bunker delivery note shall be accompanied by a representative sample of fuel oil delivered taking into account the guidelines developed by the Organization. PSCO noted improper stowage of the bunker samples. MARPOL VI/18.8.1
Condition: Placed in Improper Service
Due 19 July 2017
Resolved 19 July 2017
Resolution: Bunker samples moved and placed into proper storage area as required.
Documentation › Manuals/Policy Documentation › Transfer Procedures
Issued 19 July 2017 Resolved
1720 - Control of discharge of oil - The operator of a vessel with a capacity of 250 or more barrels of oil shall provide transfer procedures that meet the requirements of this part. PSCO noted incomplete transfer procedures. 33 CFR 155.720.
Condition: Improper/Lack of Maintenance
Action required: 60 - Rectify deficiencies prior to movement
Resolved 20 July 2017
Resolution: Complete and accurate transfer procedures for vessel provided.
Deck/Cargo › Cargo Transfer/Lightering (liquid) › Emergency Shut-down
Issued 19 July 2017 Resolved
1720 - Control of discharge of oil - A tank vessel with a capacity of 250 barrels or more than is carrying oil must have on board an emergency means to enable the PIC of a transfer operation to stop the flow of oil. PSCO noted no means to stop the flow of oil. 33 CFR 155.780.
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 19 August 2017
Resolved 21 July 2017
Resolution: Received class report
Lifesaving › Emergency Outfit › Fire ax
Issued 19 July 2017 Resolved
0720 - Fire fighting equipment - The location and arrangement of fire axes shall be as set forth in subpart 34.60. PSCO noted only 4 axes on board. 46 CFR 34.05-20 (b)
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 19 August 2017
Resolved 21 July 2017
Resolution: Received class report
Fire Fighting › Fire Pumps › Pressure
Issued 27 July 2016 Resolved
UPON TEST OF VESSEL'S MAIN FIRE PUMP, IDENTIFIED IMPROPER INSTALLATION OF VESSEL'S MECHANICAL SEAL FOR THE MAIN FIRE PUMP.
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Resolved 29 July 2016
Resolution: MECHANICAL SEAL WAS REPLACED. FIRE PUMP TESTED AND FOUND IN GOOD WORKING CONDITION.

Ownership record

The Coast Guard's documentation record for this hull -- the Abstract of Title, with its owners and liens as filed -- is not in PSIX. Ask, and Maury buys it from the National Vessel Documentation Center, files it here with its date, and every reader of this page gets it.