Records from 2012 to 2025. Most recent: inspection, 20 February 2025.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 27 October 2024
Resolved
While testing the watermist system, it did not activate automatically with heat and smoke detectors were activated. While testing the system in manual mode nozzles were observed to be clogged or obstructed.
Condition: Improper/Lack of Maintenance
Action required: 60 - Rectify deficiencies prior to movement
Resolved 4 November 2024
Resolution: ABS has accepted finding.
02 - Structural Conditions › N/A - No Subsystem › Steering gear
Issued 27 October 2024
Resolved
Vessels steering gear motor controllers 3 & 4 are not automatically switching during loss of power on either motor. Ship shall be designed, constructed, and maintained in compliance with the structural, mechanical and electrical requirements of the administration.
Condition: Improper/Lack of Maintenance
Action required: 60 - Rectify deficiencies prior to movement
Resolved 4 November 2024
Resolution: ABS has accepted finding.
07 - Fire Safety › N/A - No Subsystem › Fire-dampers
Issued 27 October 2024
Resolved
Starboard side engine room emergency exhaust damper will not close on activation.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 4 November 2024
Resolution: ABS has accepted finding.
01 - Certificates & Documentation › 013 - Documents › Oil record book
Issued 27 October 2024
Resolved
Vessels oil record book has improper entries that do not align with company's/MARPOL procedures for bunkering. These entries are dated: 10June24, 19June24, 02AUG24. Company to provide addition training to ensure proper entries are made in the ORB going forward.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 November 2024
Resolved 10 November 2024
Resolution: ABS has accepted finding.
14 - Pollution Prevention › 141 - MARPOL Annex I › Oil filtering equipment
Issued 27 October 2024
Resolved
Vessels OWS #2 has a data error not allowing the C/E to recover history of operation.
Condition: Damaged By Earlier Event
Action required: 16 - Rectify deficiencies w/in 14 days
Due 10 November 2024
Resolved 10 November 2024
Resolution: ABS has accepted finding.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Operation of machinery
Issued 27 October 2024
Resolved
Vessels Port & Starboard HUB HPU's located in the tank alley are leaking.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 10 November 2024
Resolved 10 November 2024
Resolution: ABS has accepted finding.
04 - Emergency Systems › N/A - No Subsystem › Means of communication between safety centre and other control stations
Issued 27 October 2024
Resolved
Sound powered telephone located at the emergency steering station was inoperative when tested.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 10 November 2024
Resolved 4 November 2024
Resolution: ABS has accepted finding.
09 - Working and Living Conditions › 092 - Working Conditions › Lighting (Working spaces)
Issued 27 October 2024
Resolved
Two overhead lights in tank alley were extinguished.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 10 November 2024
Resolved 10 November 2024
Resolution: ABS has accepted finding.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 27 October 2024
Resolved
Both vessels UPS system were discovered to have low voltage indicators displayed. Ensure system is being properly charged at all times.
Condition: Damaged By Earlier Event
Action required: 17 - Rectify deficiencies prior to departure
Resolved 4 November 2024
Resolution: Entire 'Integrated Bridge UPS A' unit was dismounted. However, due to the problem verified, it was necessary to replace the entire UPS unit.
The new UPS unit was subjected to operational testing for 30 minutes and was found satisfactory.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 27 October 2024
Resolved
General Alarm horn located near the steering compartment was seen obstructed with rags, not allowing the signal to perform as designed.
Condition: Placed in Improper Service
Action required: 10 - Deficiency Rectified
Resolved 27 October 2024
Resolution: Rag removed on the spot
11 - Life Saving Appliances › N/A - No Subsystem › Launching arrangements for survival craft
Issued 27 October 2024
Resolved
Both Port & Starboard life raft launching handles and pins were observed painted over not allowing equipment to be ready and available to deploy.
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Resolved 27 October 2024
Resolution: Pins and handled cleaned allowing equipment to be ready and available to deploy.
07 - Fire Safety › N/A - No Subsystem › Maintenance of Fire protection systems
Issued 27 October 2024
Resolved
Fire pump pressure gauge located on bridge is inoperable
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 10 November 2024
Resolved 4 November 2024
Resolution: Fire pump pressure gauge located on bridge was fixed, tested and found satisfactory
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Operation of machinery
Issued 20 September 2024
Resolved
Vessels OS12 automation monitors in the ECR was seen blacked out and non-operational. Repair and return to original design.
Condition: Placed in Improper Service
Action required: 16 - Rectify deficiencies w/in 14 days
Due 10 November 2024
Resolved 10 November 2024
Resolution: ABS has accepted finding.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 20 October 2023
Resolved
Vessels local emergency stop on both MDE are inoperable.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 30 October 2023
Resolution: Rectified
The Vessel's local emergency stop on the Main Diesel Engine Portside was repaired, tested, and found satisfactory to the undersigned Surveyor.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 20 October 2023
Resolved
Fuel filter base mount on the aft generator has fuel leak. Generator restricted from use until repair.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 30 October 2023
Resolution: The fuel filter was replaced, tested and found satisfactory by the undersigned surveyor.
04 - Emergency Systems › N/A - No Subsystem › Emergency source of power - Emergency generator
Issued 20 October 2023
Resolved
Vessels emergency generator compressor is locked and tagged out needing a gasket for repair.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 30 October 2023
Resolution: The vessel's emergency generator compressor n° 02 was repaired, tested, and found satisfactory to the undersigned Surveyor.
04 - Emergency Systems › N/A - No Subsystem › Emergency, lighting, batteries and switches
Issued 20 October 2023
Resolved
Emergency light located aft tank room port side walkway is out.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 30 October 2023
Resolution: The Emergency light located on after tank room port side walkway was replaced, tested, and found satisfactory by the undersigned surveyor.
10 - Safety of Navigation › N/A - No Subsystem › Rudder angle indicator
Issued 20 October 2023
Resolved
Vessel starboard side rudder angle indicator is off by 5 degrees.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 30 October 2023
Resolution: The Vessel's starboard side rudder angle indicator was rectified and tested to the satisfaction of the undersigned surveyor.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Machinery space openings
Issued 20 October 2023
Resolved
Steering compartment escape door indicator is not working as designed.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 30 October 2023
Resolution: The Steering compartment escape door indicator was repaired and tested to the satisfaction of the undersigned Surveyor.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Gauges, thermometers, etc
Issued 20 October 2023
Resolved
Steering gear motor controller #3 source light missing.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 30 October 2023
Resolution: The Steering gear motor controller #3 source light was replaced and tested to the satisfaction of the attending surveyor.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 20 October 2023
Resolved
Main bilge motor controller inoperable, wires not connected. Emergency stan-by pump back up is working.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 30 October 2023
Resolution: The motor and wires were rectified and tested to the satisfaction of the undersigned surveyor.
09 - Working and Living Conditions › 092 - Working Conditions › Protection machinery
Issued 20 October 2023
Resolved
Guard for FIFI pump broken causing no protection from rotating machinery. FIFI pump not to be used until guard is replaced.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 30 October 2023
Resolution: The Guard for the FIFI pump was repaired and tested to the satisfaction of the undersigned surveyor.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Doors
Issued 14 October 2022
Resolved
ABS issued an exemption certificate for SOLAS Chap. II-1, Reg. 25-9.3 (sliding WTD) to allow QAWTD below the waterline. Cameras are to be installed at each QAWTD (in addition to the indicators). Cameras are not currently installed.
Vsl is restricted to domestic voyages only until ABS issues a condition of class to allow international voyages.
SOLAS II-1/25-9.3
Action required: 702 - Prior to embarking on international voyage
Resolved 14 October 2022
Resolution: ABS re-issued short term exemption certificate no. 08195209-5283340-165