TIMELESS is a 1968 passenger vessel (inspected). The Coast Guard has recorded 27 inspections since 1992, most recently in July 2025, along with 22 deficiencies.

Records from 1992 to 2025. Most recent: inspection, 25 July 2025.

Built
1968
Last inspected
25 July 2025
Documentation
Valid · documentation file of 10 September 2026
Controls
None recorded without a removal date

Identity

WDG4763
Flag
UNITED STATES
367539850
Maury page id
psix-97826

Inspections, by type

…with no type recorded1
Years with a record 16 calendar years (1992–2025)
The 27 inspections in the strip above, split by the kind of activity the US Coast Guard recorded. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Coast Guard record current through 13 September 2026, retrieved 18 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Passenger Ship class in Maury's sources begin in 1977.

Documentation record

Registered dimensions (L × B × D)64.2 ft × 16.0 ft × 4.0 ft
Registered tonnagegross 27 / net 21
ITC dimensions (L × B × D)Not recorded
ITC tonnageNot recorded
BuilderBURGER BOAT COMPANY INC · MANITOWOC, WI, UNITED STATES · built 1968
Hull materialAluminum
PropulsionDiesel Reduction
Hull shapeShip
Hull configurationMonohull
Hailing portBOSTON, MA
Trade endorsementsCoastwise, unrestricted, Recreational
DocumentationValid · issued 5 February 2026 · expires 31 March 2027
Service, as the file records itPassenger (Inspected)
Hull formpowered (Maury's inference from propulsion, hull shape, material and length, rule hf-1; not a recorded fact)
Tonnage as PSIX records it27 - Simplified, Gross Ton
21 - Simplified, Net Ton
Every line above is a field of the National Vessel Documentation Center's file as served by NOAA Fisheries, dated 10 September 2026, matched to this hull on its Official Number. Registered and ITC measurements are two systems and are never combined. One snapshot is held so far; documentation history begins with the next.

Radio station licence

WDG4763MMSI 367539850 · active · compulsorily equipped · granted 17 May 2022, expires 20 July 2032
WDE8901MMSI 367411030 · expired · compulsorily equipped · granted 21 May 2009, cancelled 27 July 2019 · licensed under a name not among this hull’s recorded names (not shown)
FCC Universal Licensing System ship-station file of 6 September 2026, matched to this hull on its US Official Number. Status and dates are the file’s own. The licensee is not read from the file and is not shown. A lapsed licence’s MMSI is still the number the vessel transmitted under while it was valid.

Inspected as a tow unit · 1

The Coast Guard recorded this vessel and the following in the same inspection activity — normally a tug and the barges in its tow. A recreational or unclassed hull in the same activity is held and not published, so it does not appear here: these lists are a floor, not a complete manifest.

CARRIE B Passenger (Inspected) · MISLE 45214 · 20 April 1992 · activity 114524

Inspection history · 27

25 July 2025 Annual Inspection · Deficiency Check · Administrative Inspection
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 8188997
23 July 2024 Internal Structural Exam · Annual Inspection
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 7958469
7 May 2024 Internal Structural Exam · Hull Examination
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 7903296
16 August 2023 Internal Structural Exam · Annual Inspection
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 7763259
10 August 2022 Annual Inspection · Internal Structural Exam
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 7522146
18 May 2022 Hull Examination · Internal Structural Exam
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 7444419
19 May 2021 COI Inspection · Deficiency Check
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 7201025
14 December 2020 Administrative Inspection
Administrative · Sector Boston · USCG Northeast District (CGD-NE) · Activity 7111274
10 September 2020 Hull Examination
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 7053157
21 May 2020 Administrative Inspection
Administrative · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6957026
10 October 2019 Annual Inspection · Deficiency Check
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6831865
28 August 2018 Annual Inspection
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6525068
25 July 2018 Excursion Permit
Administrative · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6490041
1 May 2018 Hull Examination
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6403458
13 October 2017 Deficiency Check
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6288629
10 August 2017 Excursion Permit
Administrative · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6236365
26 July 2017 COI Inspection
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6220338
11 October 2016 Annual Inspection · Deficiency Check
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6019768
20 April 2016 Hull Examination
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5858391
21 July 2015 Annual Inspection · Deficiency Check
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5191366
20 October 2014 Annual Inspection · Deficiency Check
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5008757
16 June 2014 Hull Examination
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 4889927
30 July 2012 Deficiency Check · COI Inspection
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 4390910
11 July 2012 Hull Examination
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 4376158
6 December 2010 Administrative Inspection
Administrative · Sector Virginia · USCG East District (CGD-E) · Activity 3905303
21 January 1999 Plan Review "T" Boat
Administrative · GROUP/MSO LONG ISLAND SOUND · USCG Northeast District (CGD-NE) · Activity 815324
20 April 1992 Type not recorded
No type recorded · MSO MIAMI · USCG Southeast District (CGD-SE) · Activity 114524

Deficiency record · 22

07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 25 July 2025 Resolved
Use of non-approved fire detection systems may be acceptable as excess equipment provided that (1) Components are listed by an independent, nationally recognized testing laboratory as set forth in 29 CFR 1910.7, and are designed, installed, tested, and maintained in accordance with an appropriate industry standard and the manufacturer's specific guidance. Vessel was equipped with 02 expired smoke detectors in the main salon and galley areas. Install new smoke detectors.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 1 August 2025
Resolved 1 August 2025
Resolution: New smoke detectors were installed onboard.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 25 July 2025 Resolved
Unless other means are provided to ensure that a potential waste receptacle fire would be limited to the receptacle, waste receptacles must be constructed of non combustible materials with no openings in the sides or bottom. Vessel had plastic receptacles on board. Replace plastic receptacles with non combustible receptacles. 46 CFR 177.405 (f)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 1 August 2025
Resolved 1 August 2025
Resolution: New non-combustable waste receptacles were placed onboard.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Machinery space openings
Issued 19 May 2021 Resolved
Arrangement of a vessel must allow for the safe operation of the vessel giving consideration to provisions for a seaworthy hull. An approximate .5 inch wide by .25 inch deep hole was found in the port shaft housing.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 2 June 2021
Resolved 21 May 2021
Resolution: Received objective evidence of temp repair as approved. Permanendt repair will be completed NLT 31OCT2021.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 19 May 2021 Resolved
For each AC generator, a means for measuring frequency must be provided. There are currently no means to measure frequency for the vessels generator.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 2 June 2021
Resolved 3 June 2021
Resolution: Installed freequency meter.
05 - Radio Communications › N/A - No Subsystem › Distress messages: obligations and procedures
Issued 19 May 2021 Resolved
A durable placard must be posted next to all radiotelephone installations with emergency broadcast instructions. There is no emergency broadcast placard at the upper operating station.
Action required: 10 - Deficiency Rectified
Due 19 May 2021
Resolved 19 May 2021
Resolution: Corrected on the spot.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 10 October 2019 Resolved
The CO2 distribution line must extend at least 2 inches beyond the last orifice and be closed with a cap or plug. The vessel's distribution line does not extend beyond the last orifice.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 31 May 2020
Resolved 15 October 2019
Resolution: New piping installed to include the 2 inch extension.
01 - Certificates & Documentation › 011 - Ships Certificates › Certificate of Inspection (COI)
Issued 10 October 2019 Resolved
The COI must be posted under glass or suitable transparent material in a conspicuous place on the vessel where observation by passengers is likely. The vessel's COI is not posted for passengers to see.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 31 May 2020
Resolved 15 October 2019
Resolution: COI posted
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 10 October 2019 Resolved
The Stability letter shall be posted under glass or other suitable transparent material at the operating station. The vessel's Stability letter is not posted.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 31 May 2020
Resolved 15 October 2019
Resolution: Stability Letter posted
01 - Certificates & Documentation › 012 - Crew Certificates › Other (STCW)
Issued 10 October 2019 Resolved
The EAP hot-line number shall be displayed. The vessel does not have the Employee Assistance Program (EAP) community service hot-line telephone number displayed.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 31 May 2020
Resolved 10 September 2020
Resolution: EAP hotline number posted IAW 46 CFR 16.401.
Engineering › Fuel Oil Service System › Ventilation
Issued 1 May 2018 Resolved
Fuel vents did not have 30/30 mesh; install 30/30 mesh by annual inspection. Annual inspection required by 26OCT18.
Action required: 705 - Other - as specified
Due 26 October 2018
Resolved 28 August 2018
Resolution: Installed 4 new fuel vent screens to replace the wasted screens.
Construction/Loadline › Hull › Hull Plating
Issued 26 July 2017 Resolved
Crop and renew hull sections in lazzerette for exhaust and intake ducts, aluminum wasted due to dissimilar metal covers. Complete by 30AOR2018 next D/D; 46CFR176.802.
Action required: 705 - Other - as specified
Due 30 April 2018
Resolved 30 October 2017
Resolution: Fan was removed and descaled, insulation installed and S/S fan remounted. cleared.
Documentation › Logs/Records › Drug Test Records
Issued 11 October 2016 Resolved
Provide proof of enrollment in drug testing program for all crew members.
Condition: Invalid
Action required: 705 - Other - as specified
Due 25 October 2016
Resolved 13 October 2016
Resolution: Proof provided.
Accommodation/Occupational Safety › Medical/First Aid › Medicine Chest
Issued 11 October 2016 Resolved
Provide aspirin for first-aid kit.
Condition: Invalid
Action required: 705 - Other - as specified
Due 25 October 2016
Resolved 13 October 2016
Resolution: Purchased aspirin.
Construction/Loadline › Penetrations › Gasket
Issued 11 October 2016 Resolved
Replace gasket on access hatch on collision bulkhead.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 25 October 2016
Resolved 13 October 2016
Resolution: Gasket replaced.
Lifesaving › Lifejacket/PFD (Type I) › Quantity
Issued 21 July 2015 Resolved
Missing 01 adult PFD; provide 52 adult PFD's. Reduce passenger count by 01 until corrected.
Action required: 705 - Other - as specified
Resolved 31 July 2015
Resolution: Vessel provided new PFD as required. Vessel can now board entire compliment of PAX as per COI.
Lifesaving › Lifejacket/PFD (General) › Storage
Issued 21 July 2015 Resolved
Label life jacket stowage with appropriate amounts.
Action required: 705 - Other - as specified
Due 4 August 2015
Resolved 31 July 2015
Resolution: Stowage markings have been added as required.
Fire Fighting › Fixed Fire Detection System › Smoke Detectors
Issued 21 July 2015 Resolved
Install independent smoke detecting unit in accomodation spaces.
Action required: 705 - Other - as specified
Due 4 August 2015
Resolved 31 July 2015
Resolution: New smoke detector has been provided with the correct UL approval.
Lifesaving › Hand Flares › Quantity
Issued 21 July 2015 Resolved
Provide 03 hand red flares and 03 hand orange smoke distress signals or appropriate substitutions.
Action required: 705 - Other - as specified
Due 4 August 2015
Resolved 31 July 2015
Resolution: Vessel has provided new package of 04 flares.
Lifesaving › Lifejacket/PFD (Type I) › Quantity
Issued 20 October 2014 Resolved
Vessel must carry 6 child size lifejackets onboard. There are only 5 child size PFD's onboard. Vessel must add one more child size lifejacket prior to carrying children onboard.
Action required: 705 - Other - as specified
Resolved 27 October 2014
Resolution: Owner purchased 1 child size PFD for a total of 6 child size PFD''s onboard.
Electrical › Electrical Distribution System (service) › Switchboard
Issued 30 July 2012 Resolved
Main switchboard missing two breakers. Replace/blank off openings.
Action required: 705 - Other - as specified
Due 13 August 2012
Resolved 8 August 2012
Resolution: Blanked off opening in switchboard.
Electrical › Electric Supply System (service) › Battery Installation
Issued 30 July 2012 Resolved
Battery for generator not properly secured. Secure battery for generator.
Action required: 705 - Other - as specified
Due 13 August 2012
Resolved 8 August 2012
Resolution: Secure battery for generator.
Operations/Management › Pollution › Control of Discharge of Sewage
Issued 30 July 2012 Resolved
Sewage discharge valve was found open. Close sewage discharge valve and lock/secure.
Action required: 701 - Prior to carriage of passengers/cargo
Due 30 July 2012
Resolved 30 July 2012
Resolution: Closed valve, removed handle.