Records from 2016 to 2024. Most recent: inspection, 26 February 2024.
Documentation record
Tonnage as PSIX records it321300 - Dead Weight, Ton
364050 - Displacement, Ton
162198 - Regulatory (Subpart C or D), Gross Ton
162198 - Convention (Subpart B), Gross Ton
112192 - Regulatory (Subpart C or D), Net Ton
112192 - Convention (Subpart B), Net Ton
This hull's Official Number is not in the NVDC file dated 10 August 2026 as served by NOAA Fisheries, so no documentation record is shown. Absence from that file is a fact about the file, not about the hull.
Inspection history · 6
26 February 2024
PSC B · COC-TVE Renew
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 7864952
5 November 2019
Ballast Water Examination · ISPS II Exam · Deficiency Check · Administrative Inspection · COC-TVE Renew
Physical examination · Sector Corpus Christi · USCG Heartland District (CGD-H) · Activity 6842669
16 March 2018
Ballast Water Examination · COC-TVE Renew · ISPS II Exam
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 6364308
13 October 2017
COE-Administrative
Administrative · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 6287050
13 April 2017
ISPS II Exam · COC-TVE Annual · Ballast Water Examination
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 6121445
25 February 2016
COC-TVE Renew · Ballast Water Examination · ISPS II Exam
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 5814410
14 - Pollution Prevention › 141 - MARPOL Annex I › Oil filtering equipment
Issued 26 February 2024
No resolution recorded
14104 "Oil filtering equipment refered to in paragraph 2 of this regulation shall comply with paragraph 6 of this regulation. In addition, it shall be provided with alarm arrangements to indicate when this level cannot be maintained. The system shall also be provided with arrangements to ensure that any discharge of oily mixtures is automatically stopped when the oil content of the effluent exceeds 15 ppm. In considering the design of such equipment and approvals, the administration shall have regard to the specification recommended by the Organization." The oil content meter seal was broken. MARPOL 73/78 I/14
Condition: Placed in Improper Service
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Due 26 March 2024 — due date passed with no resolution recorded
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 26 February 2024
Resolved
07199 - "In tankers, electrical cables shall not be installed in hazardous areas unless it conforms to standards acceptable to the organization." Electrical cable sealant pulled out of wire on #4 cargo pump in cargo pump room. Cable should be gas tight. 74 SOLAS (04) II-1 / 45.10
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 26 February 2024
Resolved 26 February 2024
Resolution: Resolved on site.
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Other (cargo)
Issued 26 February 2024
No resolution recorded
06199 - "Each vessel vapor connection must have a stud and it must be located on the top of the flange face." Port/Fwd vapor flange stud located at 10 o clock position. 46CFR39.2001(J)
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 26 March 2024 — due date passed with no resolution recorded
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 5 November 2019
Resolved
Stairways and lift trunks which penetrate more than a single deck shall be surrounded by at least "A-0" class divisions and be protected by self-closing doors at all levels. "Food Lift" from Galley, which penetrates two decks, leading to the Dry-Provision Room, is not fitted with self-closing devices. Doors are labeled as A-class self-closing doors on the Fire Control Plan and on the physical door in the Galley, but not labeled in the Dry-Provision Room. 74 SOLAS (14) II-2/ 9.2.3.4.1.
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 19 November 2019
Resolved 7 November 2019
Resolution: Class survey report provided with pictures verifing deficiencies have been corrected.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 5 November 2019
Resolved
Doors required to be self-closing shall not be fitted with hold-back hooks. Numerous A-class and B-class fire doors throughout the Accommodation, which are labeled as self-closing according to the Fire Control Plan, are fitted with hold-back hooks. 74 SOLAS (14) II-2/ 9.4.2.2.
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 19 November 2019
Resolved 7 November 2019
Resolution: Class survey report provided with pictures verifing deficiencies have been corrected.