Every line above is a count of records the US Coast Guard wrote, or a date it recorded.
A blank resolution means none was recorded in this data; it does not establish that a
deficiency is outstanding. Years with a record are calendar years in which a record
exists, not years in service. What Maury does
not do.
1567 - Regulatory (Subpart C or D), Gross Ton
2164 - Convention (Subpart B), Gross Ton
1066 - Regulatory (Subpart C or D), Net Ton
649 - Convention (Subpart B), Net Ton
Maury page id
psix-1047213
Vessel history report
Every record for this hull, in one document — $299
Every recorded inspection, 1972 to
2026, in one chronology · every deficiency, with system, dates
and resolution · operational controls imposed and removed · every name this
hull has been recorded under · the vessels it was inspected alongside, and when
· how its record compares with hulls of similar age and size, as a fact about the
population and never a judgement about this vessel.
This report is in development and is not for sale yet. There is
no date, and nothing is charged. Leave an email and we will tell you when it exists, once.
Used only to tell you when the report exists.
Not shared, not sold, and not added to a mailing list.
The Coast Guard recorded this vessel and the following in the same
inspection activity — normally a tug and the barges in its tow. Only barges and towing
vessels are in this archive, so any other vessel type in the same activity does not
appear here: these lists are a floor, not a complete manifest.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 11 June 2024Resolved
After any survey of the ship under regulations 7, 8, 9 or 10 has been completed, no change shall be made in the structural arrangements, machinery, equipment, and other items covered by the survey, without the sanction of the Administration. MI observed a bilge suction line which was augmented between flanges that added an additional bilge suction line.
74 SOLAS (14) I/11
14 A
Action required: 16 - Rectify deficiencies w/in 14 days
Due 25 June 2024
Resolved 12 June 2024
Resolution: Accepted by Class: At this time, bilge suction line was removed and piping returned to original configuration. Piping was examined and is considered satisfactory.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 11 June 2024Resolved
The construction of doors and door frames in "A" class divisions, with the means of securing then when closed, shall provide resistance to fire as well as the passage of smoke and flame. MI observed door would not latch upon closure.
74 SOLAS (04) II-2/9.4.1.1.2
10 C
Action required: 10 - Deficiency Rectified
Due 11 June 2024
Resolved 11 June 2024
Resolution: Door was adjusted to latch upon closure.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 11 June 2024Resolved
The machinery, boilers, and other pressure vessel, associated piping systems and fittings shall be of a design and construction adequate for the service for which they are intended. MI observed AC raw water line leaking from fitting.
74 SOLAS (14)II-1/26.1
16 A
Action required: 16 - Rectify deficiencies w/in 14 days
Due 25 June 2024
Resolved 12 June 2024
Resolution: Accept by class: At this time, raw water line elbow fitting that was found with leak was replaced with new fitting as original examined during operation and considered satisfactory.
11 - Life Saving Appliances › N/A - No Subsystem › Inflatable liferafts
Issued 12 June 2023Resolved
Each liferaft or group of liferafts shall be stowed with a float-free arrangement complying with the requirements of paragraph 4.1.6 of the code so that each floats free and, if inflatable, inflate automatically when the ship sinks. All liferaft hydrostatic releases were not arranged as per the manufacturer's instruction, which prevents the liferafts from automatically floating to the surface when the ship sinks.
The liferaft HRU arrangment was not IAW with Hammer specifications. Vessel had a rope for a weak link. Vessel had 02 extra HRU onboard and switch out the units.
74 SOLAS (14) III/13.4.2
Action required: 10 - Deficiency Rectified
Due 12 June 2023
Resolved 12 June 2023
Resolution: New HRU installed.
Navigation › Voyage Data Recorder › Voyage Data Recorder (VDR)