Records from 2017 to 2021. Most recent: inspection, 16 October 2021.
Inspection history · 5
16 October 2021
PSC B
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7334774
15 October 2021
Type not recorded
No type recorded · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7335955
1 October 2021
Type not recorded
No type recorded · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7557355
29 June 2021
PSC B
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7239280
13 December 2017
Ballast Water Examination · PII Safety Exam · ISPS II Exam
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 6323721
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 18 October 2021
Resolved
74SOLAS(14) II-1/45.5.5
Cable and wiring shall be installed in such a manner as to avoid chafing or other damage. PSCO observed total wastage of all wire/cable securing bands on a vertical cable ladder in the steering gear room. Circuit label L0LB-8501 and L-LB 0116.
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 18 October 2021
Resolved 18 October 2021
Resolution: New metallic securing bands were installed prior to the departure of the exam team.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 18 October 2021
Resolved
74SOLAS(14) II-2/7.2.2
Afixed sample extraction smoke detection system shall be an approved type and comply with the Fire Safety System Code. PSCO observed multiple loose hose clamps and compression fittings at the cargo space smoke extraction/sampling manifold.
Action required: 10 - Deficiency Rectified
Due 18 October 2021
Resolved 18 October 2021
Resolution: All clamps and fitting were tightened prior to the departure of the exam team.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 18 October 2021
Resolved
74SOLAS(14) II-2/2.3
Where a fixed fire detection and fire alarm system is required at least one detector complying with the Fire Safety System Code shall be installed. The smoke detector located in the chemical locker was found to be inoperable.
Action required: 10 - Deficiency Rectified
Due 18 October 2021
Resolved 18 October 2021
Resolution: A new smoke detector head was installed and tested prior to the departure of the exam team.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 18 October 2021
Resolved
74SOLAS(14) II-2/1.3
The following fictional requirements shall be met: the fire integrity of the divisions shall be maintained at all openings and penetrations. PSCO observed the fire door from the EDG room to an accommodation space failed to close.
Action required: 10 - Deficiency Rectified
Due 18 October 2021
Resolved 18 October 2021
Resolution: The door closure was repaired and tested prior to the departure of the exam team.
11 - Life Saving Appliances › N/A - No Subsystem › Lifeboats
Issued 29 June 2021
Resolved
74SOLAS(14)III/20.2
Before the ship leaves port andat all times during the voyage, all life-saving appliances shall be in working order and ready for immediate use. PSCO observed that the propeller on the port side lifefboat would not engage, and the motor would stall-out repeatedly.
Condition: Invalid
Action required: 17 - Rectify deficiencies prior to departure
Resolved 1 July 2021
Resolution: Received class report attesting to satisfactory repair.
11 - Life Saving Appliances › N/A - No Subsystem › Operational readiness of lifesaving appliances
Issued 29 June 2021
Resolved
74SOLAS(14)III/13.4.2 - LSA CHAPTER IV/4.1.6.1
The liferaft painter system shallprovide a connection between the ship and the liferaft and shall be so arranged as to ensure that the liferaft when released and, inflated is not dragged under by the sinking ship. PSCO observed improper installation of the liferaft free float arrangements. the sea painter line was shackled to the vessel and not to the weak link, preventing proper function of the free float arrangement.
Condition: Improper Installation
Action required: 10 - Deficiency Rectified
Resolved 29 June 2021
Resolution: PSC witnessed satisfactory rectification during exam.