Records from 1993 to 2026. Most recent: inspection, 30 May 2026.
Documentation record
Registered dimensions (L × B × D)65.0 ft × 26.0 ft × 6.0 ft
Registered tonnagegross 67 / net 54
ITC dimensions (L × B × D)Not recorded
ITC tonnageNot recorded
BuilderD H & D IRON WORKS INC · LAROSE, LA, UNITED STATES · built 1978
Hull materialSteel
PropulsionDiesel Reduction
Hull shapeShip
Hull configurationMonohull
Hailing portORANGE BEACH, AL
Trade endorsementsCoastwise, unrestricted
DocumentationValid · issued 18 May 2026 · expires 31 May 2027
Service, as the file records itTowing Vessel
Hull formpowered (Maury's inference from propulsion, hull shape, material and length, rule hf-1; not a recorded fact)
Tonnage as PSIX records it67 - Simplified, Gross Ton
54 - Simplified, Net Ton
Every line above is a field of the National Vessel Documentation Center's file as served by NOAA Fisheries, dated 10 September 2026, matched to this hull on its Official Number. Registered and ITC measurements are two systems and are never combined. One snapshot is held so far; documentation history begins with the next.
Inspection history · 29
30 May 2026
Deficiency Check · Administrative Inspection · Vessel Attendance
Physical examination · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 8384084
30 May 2026
Type not recorded
No type recorded · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 8391245
26 March 2026
COI Inspection
Physical examination · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 8329408
20 January 2026
Drydock Exam · Administrative Inspection · Internal Structural Exam
Physical examination · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 8296593
17 September 2025
Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 8236335
5 November 2024
Type not recorded
No type recorded · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 8029965
12 August 2024
Annual Inspection · Deficiency Check
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 7934908
22 June 2023
Deficiency Check · Annual Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 7681124
26 May 2022
Administrative Inspection · Initial Certification
Physical examination · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 7465377
4 September 2020
Type not recorded
No type recorded · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 7063705
3 July 2020
Administrative Inspection
Administrative · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 6994296
8 April 2019
Type not recorded
No type recorded · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6658442
22 August 2016
Type not recorded
No type recorded · Station Venice · USCG Heartland District (CGD-H) · Activity 5980145
13 November 2015
Industry Initiated Exam
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 5762840
3 April 2014
Type not recorded
No type recorded · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 4840155
5 February 2014
Type not recorded
No type recorded · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 4794937
23 February 2012
Industry Initiated Exam · DAPI Audit · Deficiency Check
Physical examination · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 4249086
2 March 2010
Type not recorded
No type recorded · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 3707766
28 September 2006
MTSA Verification · Annual Inspection
Physical examination · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 2789801
2 March 2006
Security Plan Review - VSP
Administrative · Marine Safety Center (MSC) · Activity 2594759
2 March 2006
Administrative Inspection
Administrative · Marine Safety Center (MSC) · Activity 2594833
8 February 2006
Security Plan Amendment Review - VSP
Administrative · Marine Safety Center (MSC) · Activity 2581459
20 December 2004
Security Plan Amendment Review - VSP
Administrative · Marine Safety Center (MSC) · Activity 2262417
24 November 2004
Administrative Inspection
Administrative · Marine Safety Center (MSC) · Activity 2247328
10 February 2004
Security Plan Review - VSP
Administrative · Marine Safety Center (MSC) · Activity 2004014
27 April 1998
Type not recorded
No type recorded · Marine Safety Unit Baton Rouge · USCG Heartland District (CGD-H) · Activity 10930
27 April 1998
Type not recorded
No type recorded · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 159249
22 November 1993
Type not recorded
No type recorded · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 666289
19 November 1993
Type not recorded
No type recorded · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 516626
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 30 May 2026
Resolved
Machinery and electrical systems must be designed and maintained to provide for safe operation of the towing vessel and safety of persons onboard under normal and emergency conditions. STBD main engine lost propulsion for unknown reason. Vessel shall obtain tech report prior to departure.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 30 May 2026
Resolution: Witnessed satisfactory propulsion testing & received tech report.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 26 March 2026
Resolved
Electrical systems and equipment must function properly and minimize system failures and fire and shock hazards. The distribution panel in the bridge is missing blanks.
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 2 April 2026
Resolved 27 March 2026
09 - Working and Living Conditions › 091 - Living Conditions › Laundry
Issued 26 March 2026
Resolved
All vessel equipment must be used in accordance with the manufacturer's recommended practice and in a manner that minimizes risk of injury or death. The washer and dryer were not secured from sliding around.
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 2 April 2026
Resolved 27 March 2026
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 26 March 2026
Resolved
The frame or support of any semi-portable fire extinguisher fitted with wheels must be welded or otherwise permanently attached to a steel bulkhead or deck to prevent it from rolling under heavy sea conditions. The 160B was not secured.
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 2 April 2026
Resolved 27 March 2026
11 - Life Saving Appliances › N/A - No Subsystem › Operational readiness of lifesaving appliances
Issued 26 March 2026
Resolved
Each life float and rigid buoyant apparatus must be fitted with a lifeline, pendants, a painter, and floating electric water light approved under approval series 161.010. The life float was not properly installed.
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 2 April 2026
Resolved 27 March 2026
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 26 March 2026
Resolved
A 40-B portable fire extinguisher must be located near the storage room or cabinet. The paint locker did not have a 40-B.
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 2 April 2026
Resolved 27 March 2026
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 26 March 2026
Resolved
An exposed hazard such as gears and rotating machinery, must be protected by a cover, guard or rail. Both shafts were uncovered and the belts on the engines were not sufficiently covered.
Condition: Design Flaw
Action required: 16 - Rectify deficiencies w/in 14 days
Due 2 April 2026
Resolved 27 March 2026
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 26 March 2026
Resolved
Each towing vessel must have a fire-detection system installed to detect engine room fires. The heat detector above the generator was painted over.
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 2 April 2026
Resolved 27 March 2026
03 - Water/Weathertight Conditions › N/A - No Subsystem › Machinery space openings
Issued 26 March 2026
Resolved
All towing vessels must be operated in a manner that minimizes the risk of down-flooding and progressive flooding. The FWD bulkhead in the engine room (near centerline and close to the overhead)has an opening that needs to be plugged.
Condition: Design Flaw
Action required: 16 - Rectify deficiencies w/in 14 days
Due 2 April 2026
Resolved 27 March 2026
01 - Certificates & Documentation › 011 - Ships Certificates › Certificate of Inspection (COI)
Issued 17 September 2025
Resolved
A towing vessel subject to this subchapter and choosing the Coast Guard inspection option, or required to have the Coast Guard inspection option, must undergo an annual inspection within 3 months before or after the COI anniversary date.
Vessel is currently outside of the 3 month inspection window and is restricted from commercial service until a satisfactory annual inspection is completed.
Action required: 701 - Prior to carriage of passengers/cargo
Due 17 September 2025
Resolved 11 June 2026
Resolution: Noted that MSU Houma completed a COI inspection of the vessel on 26 March 2026.
11 - Life Saving Appliances › N/A - No Subsystem › Buoyant apparatus
Issued 12 August 2024
Resolved
Each item of survival craft equipment must be of good quality, effective for the purpose it is intended to serve, and secured to the craft. The life float is worn with multiple holes. Renew to the satisfaction of the attending marine inspector. 46CFR 141.325(a)
Action required: 60 - Rectify deficiencies prior to movement
Due 12 August 2024
Resolved 13 August 2024
Resolution: Purchased new BA.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Doors
Issued 12 August 2024
Resolved
The master must ensure that all hatches, doors, and other openings designed to be watertight or weather-tight function properly. Gasket to watertight doors are deteriorating and melting. Replace with proper material. 46CFR 140.610(b)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 26 August 2024
Resolved 15 August 2024
Resolution: Installed.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 12 August 2024
Resolved
An exposed hazard such as gears and rotating machinery, must be protected by a cover, guard or rail. This is not meant to restrict access to towing equipment such as winches, drums, towing gear or steering compartment equipment necessary for the operation of the vessel. Guards are missing on accessory pulleys on main engines. 46CFR 144.820
Action required: 16 - Rectify deficiencies w/in 14 days
Due 26 August 2024
Resolved 15 August 2024
Resolution: Installed.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 12 August 2024
Resolved
Machinery and electrical systems must be designed and maintained to provide for safe operation of the towing vessel and safety of persons onboard under normal and emergency conditions. There are exposed wires topside.
Make repairs satisfactory to attending marine inspector.
46CFR 143.205(a)
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 11 September 2024
Resolved 13 August 2024
Resolution: Wires pulled.
01 - Certificates & Documentation › 012 - Crew Certificates › Medical certificate
Issued 12 August 2024
No resolution recorded
The Coast Guard will issue a medical certificate to a mariner meeting the medical and physical standards for merchant mariners. The medical certificate will be issued for various periods of time based upon the endorsements the mariner holds. Mariner's medical card expired May 2023. Must have valid medical card. 46CFR 10.301(a)
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 11 September 2024 — due date passed with no resolution recorded
04 - Emergency Systems › N/A - No Subsystem › Emergency, lighting, batteries and switches
Issued 22 June 2023
Resolved
Emergency lighting must be provided for all internal crew working and living areas. Emergency lighting sources must provide for sufficient illumination under emergency conditions to facilitate egress from each space and must be either: (1) Automatic, battery-operated with a duration of no less than 2 hours; or (2) Non-electric, phosphorescent adhesive lighting strips that are installed along escape routes and sufficiently visible to enable egress with no power. Observed lack of emergency lighting in crew accommodation space (galley head and ladderwell). Install Non-electric, phosphorescent adhesive lighting strips.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 23 July 2023
Resolved 7 July 2023
Resolution: Received objective evidence that non-electric, phosphorescent adhesive lighting strips installed in crew accommodation spaces (galley head and ladderwell).