KRISTEN D is a 1987 passenger vessel (inspected). The Coast Guard has recorded 67 inspections since 1987, most recently in June 2026, along with 45 deficiencies and 3 casualty investigations between 2012 and 2022.

Records from 1987 to 2026. Most recent: inspection, 4 June 2026.

Built
1987
Last inspected
4 June 2026
Documentation
Valid · documentation file of 10 September 2026
Controls
None recorded without a removal date

Identity

WTK9856
284714
Flag
UNITED STATES
367311560
Maury page id
psix-284714

Inspections, by type

…with no type recorded10
Years with a record 35 calendar years (1987–2026)
The 67 inspections in the strip above, split by the kind of activity the US Coast Guard recorded. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Coast Guard record current through 13 September 2026, retrieved 18 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Passenger Ship class in Maury's sources begin in 1977.

Documentation record

Registered dimensions (L × B × D)90.7 ft × 35.0 ft × 7.3 ft
Registered tonnagegross 76 / net 51
ITC dimensions (L × B × D)90.7 ft × 35.0 ft × 7.3 ft
ITC tonnagegross 127 / net 50
BuilderBLOUNT MARINE CORP. · WARREN RI · built 1987
Hull materialSteel
PropulsionDiesel Reduction
Hull shapeNot recorded
Hull configurationNot recorded
Hailing portCHEBOYGAN, MI
Trade endorsementsCoastwise, unrestricted, Registry
DocumentationValid · issued 29 June 2026 · expires 30 June 2027
Service, as the file records itPassenger (Inspected)
Hull formpowered (Maury's inference from propulsion, hull shape, material and length, rule hf-1; not a recorded fact)
Tonnage as PSIX records it76 - Regulatory (Subpart C or D), Gross Ton
127 - Convention (Subpart B), Gross Ton
51 - Regulatory (Subpart C or D), Net Ton
50 - Convention (Subpart B), Net Ton
Every line above is a field of the National Vessel Documentation Center's file as served by NOAA Fisheries, dated 10 September 2026, matched to this hull on its Official Number. Registered and ITC measurements are two systems and are never combined. One snapshot is held so far; documentation history begins with the next.

Radio station licence

WTK9856MMSI 367311560 · active · compulsorily equipped · granted 21 June 2017, expires 3 September 2027
FCC Universal Licensing System ship-station file of 6 September 2026, matched to this hull on its US Official Number. Status and dates are the file’s own. The licensee is not read from the file and is not shown. A lapsed licence’s MMSI is still the number the vessel transmitted under while it was valid.

Inspected as a tow unit · 2

The Coast Guard recorded this vessel and the following in the same inspection activity — normally a tug and the barges in its tow. A recreational or unclassed hull in the same activity is held and not published, so it does not appear here: these lists are a floor, not a complete manifest.

G L OSTRANDER Towing Vessel · MISLE 140238 · 12 June 2014 · activity 4891242INTEGRITY Freight Barge · MISLE 442946 · 12 June 2014 · activity 4891242

Inspection history · 67

4 June 2026 Annual Inspection
Physical examination · Sector Northern Great Lakes · USCG Great Lakes District (CGD-GL) · Activity 8390752
23 June 2025 Annual Inspection
Physical examination · Sector Northern Great Lakes · USCG Great Lakes District (CGD-GL) · Activity 8392524
20 June 2024 Annual Inspection
Physical examination · Sector Northern Great Lakes · USCG Great Lakes District (CGD-GL) · Activity 7963910
8 June 2023 Annual Inspection · Administrative Inspection
Physical examination · Sector Northern Great Lakes · USCG Great Lakes District (CGD-GL) · Activity 7751027
28 June 2022 Type not recorded
No type recorded · Sector Northern Great Lakes · USCG Great Lakes District (CGD-GL) · Activity 7489445
26 June 2022 Administrative Inspection
Administrative · Sector Northern Great Lakes · USCG Great Lakes District (CGD-GL) · Activity 7487546
1 June 2022 COI Inspection
Physical examination · Sector Northern Great Lakes · USCG Great Lakes District (CGD-GL) · Activity 7452997
19 April 2022 Drydock Exam · Administrative Inspection · Internal Structural Exam
Physical examination · Marine Safety Unit Sturgeon Bay · USCG Great Lakes District (CGD-GL) · Activity 7433911
6 July 2021 Deficiency Check · Administrative Inspection
Physical examination · Sector Northern Great Lakes · USCG Great Lakes District (CGD-GL) · Activity 7247039
2 July 2021 Type not recorded
No type recorded · Sector Northern Great Lakes · USCG Great Lakes District (CGD-GL) · Activity 7249679
14 June 2021 Annual Inspection
Physical examination · Sector Northern Great Lakes · USCG Great Lakes District (CGD-GL) · Activity 7225341
17 June 2020 Annual Inspection
Physical examination · Sector Northern Great Lakes · USCG Great Lakes District (CGD-GL) · Activity 6979101
17 June 2020 Annual Inspection
Physical examination · Sector Northern Great Lakes · USCG Great Lakes District (CGD-GL) · Activity 6989096
1 July 2019 Deficiency Check
Physical examination · Sector Northern Great Lakes · USCG Great Lakes District (CGD-GL) · Activity 6811293
19 June 2019 Deficiency Check · Annual Inspection
Physical examination · Sector Northern Great Lakes · USCG Great Lakes District (CGD-GL) · Activity 6719827
18 September 2018 Annual Inspection · Deficiency Check · DAPI Audit
Physical examination · Sector Northern Great Lakes · USCG Great Lakes District (CGD-GL) · Activity 6547547
25 April 2017 COI Inspection
Physical examination · Sector Northern Great Lakes · USCG Great Lakes District (CGD-GL) · Activity 6132010
7 April 2017 Internal Structural Exam · Drydock Exam · Administrative Inspection
Physical examination · Marine Safety Unit Sturgeon Bay · USCG Great Lakes District (CGD-GL) · Activity 6123959
18 July 2016 Deficiency Check
Physical examination · Sector Northern Great Lakes · USCG Great Lakes District (CGD-GL) · Activity 5988795
28 June 2016 Annual Inspection
Physical examination · Sector Northern Great Lakes · USCG Great Lakes District (CGD-GL) · Activity 5988790
17 July 2015 Deficiency Check
Physical examination · Sector Northern Great Lakes · USCG Great Lakes District (CGD-GL) · Activity 5191447
26 June 2014 Annual Inspection
Physical examination · Sector Northern Great Lakes · USCG Great Lakes District (CGD-GL) · Activity 4918459
12 June 2014 Damage Survey
Physical examination · Sector Northern Great Lakes · USCG Great Lakes District (CGD-GL) · Activity 4887937
12 June 2014 Type not recorded
No type recorded · Sector Northern Great Lakes · USCG Great Lakes District (CGD-GL) · Activity 4891242
19 December 2011 Deficiency Check
Physical examination · Sector Northern Great Lakes · USCG Great Lakes District (CGD-GL) · Activity 4210714
30 October 2010 Administrative Inspection
Administrative · Sector Northern Great Lakes · USCG Great Lakes District (CGD-GL) · Activity 3881151
20 September 2010 Excursion Permit
Administrative · Sector Northern Great Lakes · USCG Great Lakes District (CGD-GL) · Activity 3853712
12 July 2007 Excursion Permit
Administrative · Sector Northern Great Lakes · USCG Great Lakes District (CGD-GL) · Activity 2999431
26 April 2007 COI Inspection
Physical examination · Sector Northern Great Lakes · USCG Great Lakes District (CGD-GL) · Activity 2916189
18 April 2007 Hull Examination
Physical examination · Sector Northern Great Lakes · USCG Great Lakes District (CGD-GL) · Activity 2911767
28 June 2006 Periodic Inspection
Physical examination · Sector Northern Great Lakes · USCG Great Lakes District (CGD-GL) · Activity 2694037
23 July 2004 Type not recorded
No type recorded · MSO SAULT STE MARIE · USCG Great Lakes District (CGD-GL) · Activity 2142883
7 April 2004 Periodic Inspection
Physical examination · MSO SAULT STE MARIE · USCG Great Lakes District (CGD-GL) · Activity 2039324
23 April 2003 Hull Examination
Physical examination · MSO SAULT STE MARIE · USCG Great Lakes District (CGD-GL) · Activity 1779613
5 July 2002 Deficiency Check
Physical examination · MSO SAULT STE MARIE · USCG Great Lakes District (CGD-GL) · Activity 1641449
21 June 2002 Type not recorded
No type recorded · MSO SAULT STE MARIE · USCG Great Lakes District (CGD-GL) · Activity 1639501
25 April 2002 COI Inspection
Physical examination · MSO SAULT STE MARIE · USCG Great Lakes District (CGD-GL) · Activity 1607716
25 September 2001 Re-Inspection
Physical examination · MSO SAULT STE MARIE · USCG Great Lakes District (CGD-GL) · Activity 1458931
4 July 2001 Excursion Permit
Administrative · MSO SAULT STE MARIE · USCG Great Lakes District (CGD-GL) · Activity 1069570
11 July 2000 Re-Inspection
Physical examination · MSO SAULT STE MARIE · USCG Great Lakes District (CGD-GL) · Activity 1432364
3 July 2000 Excursion Permit
Administrative · MSO SAULT STE MARIE · USCG Great Lakes District (CGD-GL) · Activity 820694
10 September 1999 Type not recorded
No type recorded · MSO SAULT STE MARIE · USCG Great Lakes District (CGD-GL) · Activity 660677
27 July 1999 Deficiency Check
Physical examination · MSO SAULT STE MARIE · USCG Great Lakes District (CGD-GL) · Activity 1459541
1 July 1999 Excursion Permit
Administrative · MSO SAULT STE MARIE · USCG Great Lakes District (CGD-GL) · Activity 1095118
29 June 1999 Deficiency Check · COI Inspection
Physical examination · MSO SAULT STE MARIE · USCG Great Lakes District (CGD-GL) · Activity 1401028
19 August 1998 Re-Inspection
Physical examination · MSO SAULT STE MARIE · USCG Great Lakes District (CGD-GL) · Activity 799038
13 March 1998 Hull Examination · Inclining Experiment
Physical examination · MSO SAULT STE MARIE · USCG Great Lakes District (CGD-GL) · Activity 1406310
24 July 1997 Re-Inspection
Physical examination · MSO SAULT STE MARIE · USCG Great Lakes District (CGD-GL) · Activity 786514
25 July 1996 COI Inspection
Physical examination · MSO SAULT STE MARIE · USCG Great Lakes District (CGD-GL) · Activity 1089860
25 June 1996 Hull Examination
Physical examination · MSO SAULT STE MARIE · USCG Great Lakes District (CGD-GL) · Activity 1085633
12 September 1995 Deficiency Check
Physical examination · MSO SAULT STE MARIE · USCG Great Lakes District (CGD-GL) · Activity 880906
10 August 1995 Re-Inspection
Physical examination · MSO SAULT STE MARIE · USCG Great Lakes District (CGD-GL) · Activity 1079155
10 August 1994 Re-Inspection
Physical examination · MSO SAULT STE MARIE · USCG Great Lakes District (CGD-GL) · Activity 1177103
3 December 1993 Type not recorded
No type recorded · MSO SAULT STE MARIE · USCG Great Lakes District (CGD-GL) · Activity 1158267
11 August 1993 COI Inspection
Physical examination · MSO SAULT STE MARIE · USCG Great Lakes District (CGD-GL) · Activity 843816
12 August 1992 Re-Inspection
Physical examination · MIO ST. IGNACE · USCG Great Lakes District (CGD-GL) · Activity 957713
6 August 1991 Re-Inspection
Physical examination · MIO ST. IGNACE · USCG Great Lakes District (CGD-GL) · Activity 938395
11 April 1991 Hull Examination
Physical examination · MIO ST. IGNACE · USCG Great Lakes District (CGD-GL) · Activity 1215535
14 August 1990 COI Inspection
Physical examination · MIO ST. IGNACE · USCG Great Lakes District (CGD-GL) · Activity 919311
21 June 1989 Re-Inspection
Physical examination · MIO ST. IGNACE · USCG Great Lakes District (CGD-GL) · Activity 894618
13 April 1989 Type not recorded
No type recorded · MIO ST. IGNACE · USCG Great Lakes District (CGD-GL) · Activity 888539
28 September 1988 Administrative
Administrative · MIO ST. IGNACE · USCG Great Lakes District (CGD-GL) · Activity 1044271
7 August 1988 Excursion Permit
Administrative · MIO ST. IGNACE · USCG Great Lakes District (CGD-GL) · Activity 1349414
6 May 1988 Re-Inspection
Physical examination · MIO ST. IGNACE · USCG Great Lakes District (CGD-GL) · Activity 1351037
16 October 1987 Type not recorded
No type recorded · MIO ST. IGNACE · USCG Great Lakes District (CGD-GL) · Activity 1322299
21 August 1987 Type not recorded
No type recorded · MIO ST. IGNACE · USCG Great Lakes District (CGD-GL) · Activity 1338444
14 August 1987 Initial Certification · Hull Examination
Physical examination · MSO PROVIDENCE · USCG Northeast District (CGD-NE) · Activity 1030366

Deficiency record · 45

11 - Life Saving Appliances › N/A - No Subsystem › Distress flares
Issued 8 June 2023 Resolved
4 flares short, must acquire 4 additional day/night flares.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 22 June 2023
Resolved 12 June 2023
Resolution: corrected.
11 - Life Saving Appliances › N/A - No Subsystem › Rigid liferafts
Issued 8 June 2023 Resolved
Life floats missing several paddles. Install properly marked paddles.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 22 June 2023
Resolved 12 June 2023
Resolution: corrected.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 8 June 2023 Resolved
1 maindeck PFE gauge indicates low pressure, must be serviced or replaced.
Action required: 10 - Deficiency Rectified
Due 8 June 2023
Resolved 8 June 2023
Resolution: replaced prior to my departure.
10 - Safety of Navigation › N/A - No Subsystem › Electronic charts (ECDIS)
Issued 8 June 2023 Resolved
E charting system requires update.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 8 July 2023
Resolved 7 July 2023
Resolution: updated.
11 - Life Saving Appliances › N/A - No Subsystem › Operational readiness of lifesaving appliances
Issued 19 June 2019 Resolved
Each battery used in an item of lifesaving equipment, except for inflatable survival craft equipment, must be replaced during the annual inspection if the expiration date of the battery has passed. Two waterlights on both buoyant apparatus are expired. Replace with approved battery listed on the waterlight container, to the satisfaction of the marine inspector. Until new batteries are installed, check to ensure waterlights are operable prior to getting underway.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 3 July 2019
Resolved 1 July 2019
Resolution: Batteries replaced.
10 - Safety of Navigation › N/A - No Subsystem › Nautical publications
Issued 19 June 2019 Resolved
Light list is outdated. Replace with most up to date light list to the satisfaction of the marine inspector.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 3 July 2019
Resolved 1 July 2019
Resolution: Updated light list present on the vessel
11 - Life Saving Appliances › N/A - No Subsystem › Operational readiness of lifesaving appliances
Issued 19 June 2019 Resolved
Each item of survival craft equipment must be of good quality, and efficient for the purpose it is intended to serve. The life floats have multiple one inch cracks around the pendants for the lifeline. Repair cracks in accordance with manufactures instructions or replace with serviceable life floats.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 July 2019
Resolved 1 July 2019
Resolution: Life floats were sufficiently patched with jim buoy patching kit
05 - Radio Communications › N/A - No Subsystem › Other (radio communication)
Issued 19 June 2019 Resolved
[withheld — contains personal information; the deficiency system, dates, and resolution status are shown above]
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 July 2019
Resolved 1 July 2019
Resolution: New station license obtained and present onboard
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 18 September 2018 Resolved
Child size life jackets must be separated from adult life jackets.
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 2 October 2018
Resolved 5 October 2018
Resolution: received e-mail from vessel Master with photo documenting full compliance.
11 - Life Saving Appliances › N/A - No Subsystem › Maintenance and inspections
Issued 18 September 2018 Resolved
Life float retro-reflective tape faded and must be replaced with new 2 inch SOLAS approved taped. Paddles must be lashed to life floats.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 2 October 2018
Resolved 5 October 2018
Resolution: received e-mail from vessel Master with photo documenting full compliance.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 18 September 2018 Resolved
Generator battery box must be secured from movement and battery must be chocked in box.
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 2 October 2018
Resolved 5 October 2018
Resolution: received e-mail from vessel Master with photo documenting full compliance.
10 - Safety of Navigation › N/A - No Subsystem › Nautical publications
Issued 18 September 2018 Resolved
Update excerpts of the Coast Pilot & Light List for the operating area.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 2 October 2018
Resolved 5 October 2018
Resolution: received e-mail from vessel Master with photo documenting full compliance.
Navigation › Piloting/Steering › Inland Navigation Rules
Issued 25 April 2017 Resolved
Provide current edition of navigation rules.
Condition: Improper/Lack of Maintenance
Due 26 May 2017
Resolved 18 September 2018
Resolution: Corrected.
Documentation › Manuals/Policy Documentation › Emergency Instructions
Issued 25 April 2017 Resolved
Post emergency instruction placard at operating station.
Condition: Improper Installation
Due 3 May 2017
Resolved 18 September 2018
Resolution: Corrected.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Operating Instructions
Issued 25 April 2017 Resolved
Post operating instructions and diagram for fixed CO2 system at the storage cylinders.
Condition: Improper Installation
Due 26 May 2017
Resolved 18 September 2018
Resolution: Corrected.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Remote Pulls
Issued 25 April 2017 Resolved
Label CO2 system pull stations.
Condition: Improper/Lack of Maintenance
Due 26 May 2017
Resolved 18 September 2018
Resolution: Corrected.
Fire Fighting › Ventilation Systems › Ventilation Fire Dampers
Issued 25 April 2017 Resolved
Provide effective means to close ventiliation to engineroom to be used during a fire.
Condition: Invalid
Due 26 May 2017
Resolved 18 September 2018
Resolution: Corrected.
Electrical › Electric Supply System (service) › Overcurrent Device
Issued 28 June 2016 Resolved
Provide means of disconnection for ship service generator engine cranking battery.
Condition: Improper Installation
Due 15 July 2016
Resolved 18 July 2016
Electrical › Electrical Distribution System (service) › Switchboard
Issued 28 June 2016 Resolved
Provide frequency meter, ammeter and voltmeter for ship service generator.
Condition: Improper Installation
Due 15 July 2016
Resolved 18 July 2016
Documentation › Manuals/Policy Documentation › Emergency Instructions
Issued 28 June 2016 Resolved
Provide radio emergency broadcast placard at the operating station.
Condition: Improper/Lack of Maintenance
Due 15 July 2016
Resolved 18 July 2016
Operations/Management › Drills/Instruction › Man Overboard Recovery
Issued 28 June 2016 Resolved
Demonstrate satisfactory man-overboard recovery drill.
Condition: Invalid
Action required: 705 - Other - as specified
Due 15 July 2016
Resolved 18 July 2016
Fire Fighting › Fire Hoses › Condition
Issued 28 June 2016 Resolved
One 50' fire hose excessively abraded from deck nonskid, replaced in kind during inspection.
Condition: Improper/Lack of Maintenance
Due 28 June 2016
Resolved 28 June 2016
Resolution: corrected during inspection.
Lifesaving › Lifejacket/PFD (Type III) › Condition
Issued 26 April 2007 Resolved
remove all manufacturers tags from Personal Flotation Devices
Due 26 May 2007
Resolved 28 June 2007
Resolution: TAGS REMOVED
Lifesaving › Buoyant Apparatus › Serviceable
Issued 26 April 2007 Resolved
Install spacers between buoyant apparatus and make repairs to dry rotting in several places on shell IAW 46CFR180.137
Due 26 May 2007
Resolved 28 June 2007
Resolution: SPACERS INSTALLED
Lifesaving › Lifebuoys › Markings (ship name/port)
Issued 26 April 2007 Resolved
Mark lifering on port side amidships with name of vessel and homeport
Due 25 May 2007
Resolved 28 June 2007
Resolution: LIFE RING MARKED
Engineering › Fuel Oil Storage/Transfer System › Piping
Issued 26 April 2007 Resolved
relabel emergency fuel shutoffs port and starboard
Due 26 May 2007
Resolved 28 June 2007
Resolution: FUEL SHUTOFFS LABELED
Engineering › Freshwater System (jacketwater cooling) › Piping
Issued 26 April 2007 Resolved
Generator keel cooler must be inspected (new install) operational and installation prior to use.
Action required: 705 - Other - as specified
Resolved 30 April 2008
Resolution: SSM inspectors verified instillation and operation of SSDG keel cooler.
Fire Fighting › Fire Pumps
Issued 25 April 2002 Resolved
Make port fire pump operable from wheelhouse and engineroom. LEGACY COMPONENT DESC: Arrangement
Condition: Design Flaw
Due 25 August 2002
Resolved 5 September 2002
Fire Fighting › Fixed Gas Fire Extinguishing System
Issued 25 April 2002 Resolved
Provide main engine shutdowns to function automatically with discharge of fixed CO2 extinguishing system. LEGACY COMPONENT DESC: Operating Controls
Condition: Design Flaw
Due 25 August 2002
Resolved 23 April 2003
Navigation
Issued 25 September 2001 Resolved
PROVIDE CURRENT EDITION OF NAVIGATION RULES BEFORE THE COMPLIANCE DATE.
Condition: Unknown
Due 25 November 2001
Resolved 19 October 2001
Unknown
Issued 25 September 2001 Resolved
DEMONSTRATE FULL COMPLIANCE WITH 46 CFR PART 16 DRUG TESTING RULES AS PER AUDIT SHEET DATED 9/25/01 BEFORE THE COMPLIANCE DATE.
Condition: Unknown
Due 25 November 2001
Resolved 19 October 2001
Lifesaving
Issued 11 July 2000 Resolved
LABEL DISTRESS SIGNALS CONTAINER PER 46 CFR 185.614 BEFORE THE COMPLIANCE DATE.
Condition: Unknown
Due 18 July 2000
Resolved 10 August 2000
Accommodation/Occupational Safety
Issued 11 July 2000 Resolved
MARK ENGINEROOM EXITS AS PER 46 CFR 185.606 BEFORE THE COMPLIANCE DATE.
Condition: Unknown
Due 18 July 2000
Resolved 10 August 2000
Documentation
Issued 27 July 1999 Resolved
Failed to submit annual MSI report to Commandant as require by 46 CFR 16.500(c).
Condition: Unknown
Due 1 August 1999
Resolved 10 September 1999
Construction/Loadline
Issued 29 June 1999 Resolved
REMOVE HYDRAULIC OIL FROM BILGE IN BOW THRUSTER SPACE.
Condition: Unknown
Due 29 June 1999
Resolved 29 June 1999
Lifesaving
Issued 29 June 1999 Resolved
DEVELOP/UTILIZE PASSENGER SAFETY BRIEFING IN ACCORDANCE WITH 46 CFR 185.506
Condition: Unknown
Due 29 June 1999
Resolved 29 June 1999
Lifesaving
Issued 29 June 1999 Resolved
RE-POST LIFE JACKET DONNING INSTRUCTIONS WHERE ACCESSIBLE TO ALL PASSENGERS
Condition: Unknown
Due 29 June 1999
Resolved 29 June 1999
Fire Fighting
Issued 29 June 1999 Resolved
DEMONSTRATE FIREMAIN PRESSURE GAUGE OPERATION TO INDICATE 60 PSI ON THE FIREMAIN.
Condition: Unknown
Due 29 June 1999
Resolved 29 June 1999
Fire Fighting
Issued 29 June 1999 Resolved
INSTALL MEANS OF MANUALLY SECURING VENTILLATION TO ENGINEROOM IN THE EVENT OF DISCHARGE OF THE FIXED CO2 SYSTEM.
Condition: Unknown
Due 29 June 1999
Resolved 29 June 1999
Lifesaving
Issued 29 June 1999 Resolved
ESTABLISH/MAINTAIN TRAINING/MAINTENANCE LOG FOR DRILLS/TRAINING AND LIFE SAVING EQUIPMENT TRAINING.
Condition: Unknown
Due 29 June 1999
Resolved 29 June 1999
Fire Fighting
Issued 19 August 1998 Resolved
Install pressure gauge on firemain in vicinity discharge side of pump.
Condition: Unknown
Due 1 April 1999
Resolved 1 April 1999
Fire Fighting
Issued 19 August 1998 Resolved
Install fire detecting system in engine room in accordance with 46 CFR 76.27.
Condition: Unknown
Due 19 August 1998
Resolved 19 August 1998
Fire Fighting
Issued 19 August 1998 Resolved
Install fixed gas fire extinguishing system in Engine Room, in accordance with 46 CFR 181.410 and to satisfaction of attending Marine Inspector.
Condition: Unknown
Due 19 August 1998
Resolved 19 August 1998
Construction/Loadline
Issued 19 August 1998 Resolved
Equip vessel with bilge high water level alarms in the bow thruster space, engine room, and steering gear space; with audible/visual indicators at operating station.
Condition: Unknown
Due 19 August 1998
Resolved 19 August 1998
Fire Fighting
Issued 10 August 1995 Resolved
Service all portable fire extinguishers as follows:_x001C_ a. Engine room CO2's shall be hydro-tested, filled, and re-weighed._x001C_ b. All other stored pressure dry chemical ext. shall have 6 year servicingperformed. Send servicing certificates to [name withheld] when completed.
Condition: Unknown
Due 10 August 1995
Resolved 10 August 1995

Casualty record · 3

20 November 2012Routine · role: Involved in a Marine Casualty · activity 4488355
2 July 2021Routine · role: Involved in a Marine Casualty · activity 7249679
28 June 2022Routine · role: Involved in a Marine Casualty · activity 7489445
Each line is an incident investigation the Coast Guard recorded with this hull among the vessels involved, with the date and the classification the Coast Guard gave it, and the bridge, lock or dam the investigation names where it names one. Involvement is not fault. The investigation narrative is not published. Source: IIR, through 2026.

Ownership record

The Coast Guard's documentation record for this hull -- the Abstract of Title, with its owners and liens as filed -- is not in PSIX. Ask, and Maury buys it from the National Vessel Documentation Center, files it here with its date, and every reader of this page gets it.