07 - Fire Safety › N/A - No Subsystem › Fire pumps and its pipes
Issued 16 July 2026
Resolved
"L. The minimum capacity of the power fire pump shall be 50 gallons per minute at a pressure of not less than 60 pounds per square inch at the pump outlet. The pump outlet shall be fitted with a pressure gauge." Gauge at fire pump had a constant erroneous reading. Replace gauge with operable gauge.
46 CFR 181.10-1(c)
(OLD T)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 29 July 2026
Resolved 18 July 2026
Resolution: Received photo of newly installed gauge for fire pump.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 16 July 2026
Resolved
"Switchboards shall be placed in dry, accessible and adequately ventilated locations preferably outside the engine compartment. The switchboard shall be adequately protected and provision shall be made for access thereto." Switchboard in main deck aft pantry had cover falling off. Reinstall panel cover.
46 CFR 183.05-15(a)
(OLD T)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 29 July 2026
Resolved 16 July 2026
Resolution: Reinstalled cover for electrical panel
02 - Structural Conditions › N/A - No Subsystem › Hull damage impairing seaworthiness
Issued 21 March 2025
Resolved
(a) The construction and arrangement of a vessel must allow the safe operation of the vessel in accordance with the terms of its Certificate of Inspection giving consideration to provisions for a seaworthy hull, protection against fire, means of escape in case of a sudden unexpected casualty, guards and rails in hazardous places, ventilation of enclosed spaces, and necessary facilities for passengers and crew. Vessel sustained damage to the bow and aft port corner.
- Submit a repair plan for approval
- Have an MI witness satisfactory repairs
46 CFR 116.100(a)
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 15 May 2025
Resolution: Repairs completed satisfactory.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 21 March 2025
Resolved
Propulsion machinery shall be suitable in type and design for propulsion requirements of the hull in whioch it is installed and capable of operating at constant marine load under such requirementsa without exceeding its designed limitations.
- Provide a technician report attesting to the proper operation of both main propulsion engines to ensure vesel is fit for its intended route and service.
- Have an MI witness a successful sea trial
Action required: 60 - Rectify deficiencies prior to movement
Resolved 19 May 2025
Resolution: Submitted all required documents and completed successful sea trial.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 17 March 2025
Resolved
Shutoff valves, installed so as to close against the fuel flow, shall be fitted in the fuel supply lines, one at
the tank connection and one at the engine end of the fuel line to stop fuel flow when servicing accessories. MI identified no fuel tank shut off valve at the fuel tank connection. Must have a fuel tank shut off valve at the tank connection accessible from the space within 14 days.
46 CFR 182.20-40(a)(3)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 26 March 2025
Resolution: Received satisfactory photographic evidence.
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 17 March 2025
Resolved
The general construction of the vessel must be such as to minimize fire hazards insofar as it is reasonable and practicable. MI identified missing insulation above the port engine. Address the missing insulation or submit risk mitigation plan for approval.
46 CFR 116.405(c)
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 19 March 2025
Resolution: New SFP insulation in place.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 17 March 2025
Resolved
At each initial and subsequent inspection for certification the marine inspector shall examine and test the following items to the extent necessary to determine that they are inproper operating condition and fit for the service for which they are intended: engine control mechanisms. MI identified twisted wire exposed on port engine. Repair within 14 days.
46 CFR 176.25-10(3)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 19 May 2025
Resolution: Wire is not exposed.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 17 March 2025
Resolved
At each initial and subsequent inspection for certification the marine inspector shall examine and test the following items to the extent necessary to determine that they are inproper operating condition and fit for the service for which they are intended: main propulsion machinery. MI identified leak in port and stbd shaft seals and excess water in bilge. Repair within 14 days.
46 CFR 176.25-10(1)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 19 May 2025
Resolution: Shaft seals were tightened and do not drip excessively.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 17 March 2025
Resolved
Switchboards shall be fitted with driphoods and non-conducting hand rails. Non-conducting mats or grating
shall be provided on deck in front and rear of switchboards.
Non-conducting mats or grating for electrical panel located in engine room within 14 days.
46 CFR 183.10-15
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 26 March 2025
Resolution: Received satisfactory photographic evidence.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 17 March 2025
Resolved
The intent of this part is to insure that each vessel is provided with safe, readily available and sufficient firefighting equipment. MI identified insufficient pressure when testing main fire pump and inaccurate pressure gauge readings.
46 CFR 181.01-5(a)
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 19 March 2025
Resolution: Mi witness test of fire pumnp/hose. Sat pressure demonstrated.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Operation of machinery
Issued 17 March 2025
Resolved
An exposed hazard, such as gears or rotating machinery, must be properly protected by a cover, guard, or rail. MI identified exposed rotating machinery on port engine.
46 CFR 177.960
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 26 March 2025
Resolution: Received satisfactory photographic evidence.
04 - Emergency Systems › N/A - No Subsystem › Public address system
Issued 11 March 2024
Resolved
On a vessel of more than 19.8 meters (65 feet) in length, the public address system must be a fixed installation and be audible during normal operating conditions throughout the accommodation spaces and all other spaces normally manned by crew members [name withheld] system does not operate. Repair fixed PA system.
46 CFR 121.610 (b)
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 19 March 2024
Resolution: Vessel repaired PA system.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 11 March 2024
Resolved
.. all connections shall be made to the battery terminals with permanent type connectors. Spring
clips or other temporary type clamps are not permitted. Vessel has temporary type clamps on battery from charger. Vessel shall install permanent type connectors.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 19 March 2024
Resolution: Repaired wiring for PA
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Operation of machinery
Issued 11 March 2024
Resolved
All vessels shall be provided with a satisfactory arrangement for draining any watertight compartment...Vessel was not capable of dewatering void 4 & bilge pickup was not equipped w/ strainer. Complete repairs on bilge pump & install suitable strainer.
46 CFR 182.25-1 OLD-T
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 19 March 2024
Resolution: Replaced 8 inches of pipe. Tested. All sat.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 11 March 2024
Resolved
The general construction of the vessel shall be such as to minimize fire hazards. Vessel missing SFP above DJ
booth, office overhead. Vessel shall replace SFP.
46 CFR 177.10-5 (a)
OLD-T
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 19 March 2024
Resolution: Replaced missing SFP
03 - Water/Weathertight Conditions › N/A - No Subsystem › Doors
Issued 11 March 2024
Resolved
Vessel fitted with loading doors shall assure that all loading doors are closed watertight. Vessels port galley WTD door is difficult to operate & gasket is damaged. Vessel shall service door and prove watertight integrity.
46 CFR 185.20-17 (a)
OLD-T
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 5 April 2024
Resolution: Vessel has replaced gasket and performed satisfactory chalk test.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 11 March 2024
Resolved
..vessel that is reasonably safe from fire caused by and/or originating in electrical equipment, and reasonably safe from electrical shock of personnel. 01 bar receptacles are removed from bulkhead, exposing wiring. Vessel shall properly install electrical receptacles.
46 CFR 183.01-5
OLD-T
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 19 March 2024
Resolution: replaced w/ new receptacles.
04 - Emergency Systems › N/A - No Subsystem › Functionality of Safety Systems
Issued 11 March 2024
Resolved
All vessels shall be provided with a satisfactory arrangement for draining any watertight compartment... Vessel is missing suitable pickup strainer in void 2. Vessel shall install suitable strainer.
46 CFR 182.25-1
OLD-T
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 19 March 2024
Resolution: Replaced missing strainer.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 11 March 2024
Resolved
All electrical installations shall be to satisfaction of the Officer in Charge, Marine Inspection. 02 deck STBD floodlight has broken mounting hardware. Repair broken hardware.
46 CFR 183.01-15
OLD-T
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 19 March 2024
Resolution: Replaced broken hardware.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 11 March 2024
Resolved
All electrical installations shall be to satisfaction of the Officer in Charge, Marine Inspection. 02 deck STBD embarkation light is mounted w/ temporary zip ties. Vessel shall permanently mount light fixture.
46 CFR 183.01-15
OLD-T
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 19 March 2024
Resolution: Vsl removed light
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 11 March 2024
Resolved
Provide full electrical load analysis of vessels systems.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 1 April 2024
Resolution: Vessel has provided a load analysis report. MI's have reviewed report and approved. Deficiency has been resolved.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 11 March 2024
Resolved
..Machinery shall be suitable in type and design for propulsion requirements of the hull in which
it is installed and capable of operating at constant marine load under such requirements without exceeding its designed limitations. STBD reduction gear oil filter leaking oil. Repair leaking oil filter.
46 CFR 182.05-1 (a)
OLD-T
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 19 March 2024
Resolution: replaced L/O filter
07 - Fire Safety › N/A - No Subsystem › Fire pumps and its pipes
Issued 11 March 2024
Resolved
Auxiliary machinery shall be suitable in type and design for the purpose intended. Fire pump is not operational. Complete repairs on fire pump.
46 CFR 181.15-1 (a)
OLD-T
Action required: 10 - Deficiency Rectified
Resolved 19 March 2024
Resolution: Vessel repaired system while MI's were onbaord. Deficency has been resolved.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 11 March 2024
Resolved
All electrical installations shall be to satisfaction of the Officer in Charge, Marine Inspection. Wire runs & engine harnesses throughout vessel are unsupported. Vessel shall support wire harnesses throughout vessel.
46 CFR 183.01-15
OLD-T
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 19 March 2024
Resolution: installed metal supports.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Gauges, thermometers, etc
Issued 11 March 2024
Resolved
Engine control mechanisms. Such mechanisms shall be tested by operation and examined, visually. Vessel has active high J/W alarm on STBD generator. Vessel determine cause of alarm and conduct repair.
46 CFR 176.25-10 (a)(3)
OLD-T
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 19 March 2024
Resolution: vsl repaired wiring.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 11 March 2024
Resolved
Marine inspector conducts inspections of the hull structure and its appurtenances. Vessel has cracked windows on main deck on STBD side. Vessel shall repair cracked windows.
46 CFR 176.25-5
OLD-T
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 19 March 2024
Resolution: replaced cracked window.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 11 March 2024
Resolved
Vessel's STBD fuel cutoff valve did not operate. Vessel corrected deficiency w/ marine inspectors onboard.
46 CFR 182.20-40(b)(3)
OLD-T
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 11 March 2024
Resolution: Vessel completed repairs on valve while MI's were onboard. Valve was initially seized. Deficency has been resolved.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 11 March 2024
Resolved
Each life jacket kept in a stowage container must be readily available. Vessel's aft main deck life jacket locker door was obstructed and life jackets were not readily available. Vessel shall stow life jackets so they are readily available.
46 CFR 117.78 (2)
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 19 March 2024
Resolution: repaired door and added donning placard.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 17 May 2023
Resolved
At each....subsequent inspection for certification...the marine inspector shall require that all observed unsafe practices and hazardous situation be corrected. The fuel governor on the port main engine was leaking. The fuel filter transfer pump on the port main engine was leaking.
46 CFR 176.25-50(a)
"Old T"
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 26 May 2023
Resolution: Fuel filter leak has been rectified.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 17 May 2023
Resolved
At each intitial and subsequent inspection for certification...the maine inspector shall require that all observed unsafe practices and hazardous situations be corrected. The port service diesel generator was leaking oil from the rack handle causing a severe fire and electrical hazard.
46 CFR 176.25-50(a) "OLD T"
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 26 May 2023
Resolution: Leaking oil from rack handle has been secured.
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 17 May 2023
Resolved
Vessels contracted before on or after July 1, 1961 which carry more than 150 passengers shall meet the requirements of subpart 72.05 of Subchapter H of this chapter. An A Class door on the main deck on the port side midship was missing a handle and did not fully close.
46 CFR 177.10-5(a) "OLD T"
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 26 May 2023
Resolution: A class door handle was replaced and door was able to be fully closed.
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 17 May 2023
Resolved
All bulkheads and decks shall be classed....upon the type of space on each side of the bulkhead or above and below the deck. (1) bulkheads or decks of the "A" class shall be composed of steel or equivalent metal construction. structural fire protection insulation was missing between the underside of Deck 2 in the overhead drop ceiling.
46 CFR 177.10-5(a) "OLD T"
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 26 May 2023
Resolution: Drop ceiling fire protection was replaced.
04 - Emergency Systems › N/A - No Subsystem › Abandon ship drills
Issued 17 May 2023
Resolved
Crew is not familar with the procedures to follow in a situation where passengers and crew neet to abaondon the ship.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 26 May 2023
Resolution: Crew was able to preform abandon ship drill as required.
04 - Emergency Systems › N/A - No Subsystem › Fire drills
Issued 17 May 2023
Resolved
While conducting a fire drill onboard for an engine room fire, the crew did not display strong competence.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 26 May 2023
Resolution: Drill was preformed by the crew up to standards.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Doors
Issued 17 May 2023
Resolved
two weathertight side loading doors do not seal properly. There is no closure device on the door to a storage closet on the port side of the vessel near the bow.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 26 May 2023
Resolution: A latch was placed on the door.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 17 May 2023
Resolved
Multiple power strips were found on the vessel. Specifically in the DJ storage room on deck 2, there were two power strips to charge approx 20 radios. Must prove a need and amp/watts does not exceed the the assigned circuit breaker. Must be mounted and stored properly during use to prevent fire.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 26 May 2023
Resolution: The power strips were removed.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 17 May 2023
Resolved
The owner must submit drawings, sketchs, or written specifications describing the details of any proposed alterations the cognizant [name withheld] new installations were found, to include the addition of a bilge alarm panel on the bridge, an air conditioning unit, shore tie connection and led lighting on deck 1 and 2.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 June 2023
Resolved 4 April 2024
Resolution: Verified operation of bildge panel and air condition unit was removed and openiong was sealed. Led lighting one line drawing for the circuit protection was requested.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 17 May 2023
Resolved
Vessels over 65 feet in length shall be equipped with two fixed fire pumps. Vessels port MDE PTO bilge pump was not functioning and crew had no knowledge of operation.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 26 May 2023
Resolution: Witnessed a satisfactory test of the MDE PTO bilge pump.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Doors
Issued 17 May 2023
Resolved
Examine and test by operation all watertight closures in the hull, decks and bulkheads. The watertight door on the port side of the storage room near the entrance to the steering compartment did not completely seal when closed. There were hidden temporary repairs made in the coaming that the CG was not made aware of.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 26 May 2023
10 - Safety of Navigation › N/A - No Subsystem › Charts
Issued 17 May 2023
Resolved
As appropriate for the intended voyage, a vessel must carry adequate and up-to-date: (1) Charts of large enough scale to make safe navigation possible…Vsl did not have adequate charts onboard.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 26 May 2023
11 - Life Saving Appliances › N/A - No Subsystem › Distress flares
Issued 17 May 2023
Resolved
Each flare carried to meet this section must be stowed in one of the following: (1) A portable watertight container carried at the operating station, and marked as required by § 122.614 of this subchapter; or (2) A pyrotechnic locker secured above the freeboard deck, away from heat, in the vicinity of the operating station. The hand red flare distress signals were in plastic bags on the bridge.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 26 May 2023
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 17 May 2023
Resolved
An ammeter that is readily visible shall be included in the battery charger circuit. There was not an ammeter connected to the battery charger underneath the operating station on the bridge.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 26 May 2023
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 17 May 2023
Resolved
This part is intended to provide a minimum standard of regulations for electrical installations and equipment that will result in a vessel that is reasonably safe from fire caused by and/or originating in electrical equipment, and reasonably safe from electrical shock of personnel. There were dead end wires in the cabinet underneath the operating station on the bridge.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 26 May 2023
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 17 May 2023
Resolved
Each child size life jacket must be stowed in a location that is appropriately marked and separated from adult life jackets so the child size life jackets are not mistaken for adult life jackets. The children and adult lifejackets stored in the aft locker located on Deck 3 were mixed.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 26 May 2023
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 17 May 2023
Resolved
Portable fire extinguishers shall be installed and located to the satisfaction of the Officer in Charge, Marine Inspection. The portable fire extinguisher located in the DJ storage room on Deck 2 was not properly secured in a mount.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 26 May 2023
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 17 May 2023
Resolved
At all inspections special attention shall be paid to ensure that no fire hazards exist and that guards or protective devices are provided in all hazardous places. A section of lagging was missing on the starboard main engine exhaust line.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 26 May 2023
Resolved 14 June 2023
Resolution: Lagging good may have a small exahust leak
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 17 May 2023
Resolved
This part is intended to provide a minimum standard of regulations for electrical installations and equipment that will result in a vessel that is reasonably safe from fire caused by and/or originating in electrical equipment, and reasonably safe from electrical shock of personnel. Water was leaking from the exhaust water separator on the starboard ship service diesel generator.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 8 June 2023
Resolved 14 June 2023
Resolution: New part installed.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Manholes/flush scuttles
Issued 17 May 2023
Resolved
Examine and test by operation all watertight closures in the…decks…The watertight hatch for the steering compartment had a wasted ring.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 26 May 2023
01 - Certificates & Documentation › 012 - Crew Certificates › Other (STCW)
Issued 17 May 2023
Resolved
Each ship transporting more than six passengers for hire equipped with a radiotelephone station in accordance with Part III of Title III of the Communications Act must carry a radio operator who meets the following requirements: (1) Where the station power does not exceed 250 watts carrier power or 1500 watts peak envelope power, the radio operator must hold a marine radio operator permit or higher class license. Neither Master had their Marine Radio Operator permit available for inspection.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 26 May 2023
04 - Emergency Systems › N/A - No Subsystem › Emergency, lighting, batteries and switches
Issued 17 May 2023
Resolved
Vessels shall be equipped with a suitable number of portable battery lights. Vsl did not have portable lights onboard.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 26 May 2023
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 17 May 2023
Resolved
The fuel systems for the main propulsion engines, all auxiliaries and all other fuel systems installed shall be checked. The plugs on the bottom of fuel filter shields were plastic causing a fire hazard
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 26 May 2023
09 - Working and Living Conditions › 092 - Working Conditions › Other (accident prevention)
Issued 17 May 2023
Resolved
Suitable covers, guards, or rails shall be installed in way of all exposed and hazardous places such as gears, machinery, etc. There was no guard on the rotating belt on the front side of the starboard main engine.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 26 May 2023
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 17 May 2023
Resolved
Each…ring life buoy must be marked with Type II retroreflective material approved in accordance with § 164.018 in subchapter Q of this chapter, or other standard specified by the Commandant. The letters of the vessel’s name covered the retroreflective material on a ring lifebuoy on Deck 3.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 26 May 2023
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 17 May 2023
Resolved
This part is intended to provide a minimum standard of regulations for electrical installations and equipment that will result in a vessel that is reasonably safe from fire caused by and/or originating in electrical equipment, and reasonably safe from electrical shock of personnel. The cover for the lights in Void #2 was removed.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 26 May 2023
03 - Water/Weathertight Conditions › N/A - No Subsystem › Other (load lines)
Issued 17 May 2023
Resolved
After loading and prior to departure, and at all other times necessary to assure the safety of the vessel, the master shall determine that the vessel complies with all applicable stability requirements in the vessel's…stability letter, Certificate of Inspection…as the case may be. Large speakers on Deck 1 and Deck 2 were not safely secured for sea. There were multiple areas, to include the storage room where access to the steering compartment is, the two alcohol storage areas adjacent to the engine room, by the bar, in the storage locker on the port side of the vsl, the DJ storage room, and in the cabinets on the bridge where MIs identified excess stowage. Additionally, there was combustible gear that was stored on top of the compressor for the walk-in refrigerator located near the main entrance the engine room. Boxes were taken out of the engine room by crew during the inspection.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 8 June 2023
Resolution: Stability boolet aquired and 1200lbs of misc gear allowed
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 17 May 2023
Resolved
Every vessel subject to Part III of Title III of the Communications Act must have a detailed inspection of the radio installation by an FCC-licensed technician in accordance with § 80.59 once every five years…If the ship passes the inspection, the technician will issue a Communications Act Safety Radiotelephony Certificate. The ship did not have a Communications Act Safety Radiotelephony Certificate onboard at the time of inspection.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 26 May 2023
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 17 May 2023
Resolved
At each…subsequent inspection for certification the marine inspector shall examine and test the following items to the extent necessary to determine that they are in proper operating condition, safe electrical condition, and fit for the service for which they are intended: (2) Overload or circuit protective devices. The dead front covers were bent and not properly secured on the port and starboard distribution panels in the engine room causing a personnel electrical hazard.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 26 May 2023
04 - Emergency Systems › N/A - No Subsystem › Public address system
Issued 17 May 2023
Resolved
Except as allowed by paragraphs (b) and (c) of this section, before getting underway on a voyage or as soon as practicable thereafter, the master of a vessel shall ensure that suitable public announcements are made. Vessels safety orientation did not contain all information in 46 CFR 122.506.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 26 May 2023
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 17 May 2023
Resolved
All electrical installations shall be to the satisfaction of the OCMI including the IEE and NEC. Electrical panel in galley port side was not marked properly and spare number three was energized.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 26 May 2023
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 17 May 2023
Resolved
Vessels contracted before or after July 1, 1961, which carry more than 150 passengers shall meet the requirement of subpart 72.05 of Subchapter H (Passenger Vessels) of this chapter. An A-Class door on the 2nd deck aft failed to fully close.
Action required: 10 - Deficiency Rectified
Resolved 19 May 2023
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 27 October 2022
Resolved
At least one ring life buoy must be fitted with fitted with a lifeline. The lifeline must be buoyant, 60 feet in length & dark color.
46 CFR 117.70(c)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 November 2022
Resolved 5 December 2022
Resolution: Operator emailed picture to MI of satisfactory life buoy lifeline.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 27 October 2022
Resolved
A vessel of more than 65 feet in length must carry a minimum of three life buoys of not less than 24 inches in diamter.
46 CFR 117.70 (a)(3)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 November 2022
Resolved 5 December 2022
Resolution: Vessel's Operator sent satisfactory photograph of 03 life ring buoys.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 27 October 2022
Resolved
Each life jacket kept in a storage container must be readily available. Each child size life jacket must be stowed in a location that is appropriately marked and separated from adult life jackets so the child size life jackets are not mistaken for adult life jackets.
46 CFR 117.78 (a)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 November 2022
Resolved 5 December 2022
Resolution: Vessel's Operator sent satisfactory photograph of life jacket storage showing proper separation of child/adult life jackets.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 16 August 2021
Resolved
Provide documentation attesting to newly installed
pressure vessel size and operating capabilities.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 12 September 2022
Resolved 27 October 2022
Resolution: MI witnessed/viewed documentation attesting to newly installed pressure vessel.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 3 October 2019
Resolved
1)Battery switch for #2gen needs to be mounted
2)Rotating guard is required for #2 gen
3)Battery terminal loose
4)misc pump switch needs cover and mounted properly
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 1 November 2019
Resolved 26 August 2021
Resolution: Added deficiencies to MISLE ID 7288505
09 - Working and Living Conditions › 092 - Working Conditions › Machinery
Issued 3 October 2019
Resolved
1)Slight J/W leak on #2 gen
2)Small oil leak on #1 MDE
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 November 2019
Resolved 26 August 2021
Resolution: Attended vessel and saw proper operation of gen/MDE
09 - Working and Living Conditions › 092 - Working Conditions › Cleanliness of engine room
Issued 26 July 2018
Resolved
Clean engine room.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 August 2018
Resolved 24 September 2018
Resolution: engineroom was clean during time of visit to clear def
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 26 July 2018
Resolved
Properly install battery wires (tighten).
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 August 2018
Resolved 24 September 2018
Resolution: battery cable terminals was tighten to battery post.
02 - Structural Conditions › N/A - No Subsystem › Hull damage impairing seaworthiness
Issued 17 June 2018
Resolved
33 CFR 160.216 Failure to immediately notify the nearest Coast Guard unit of a hazardous condition.
Action required: 705 - Other - as specified
Resolved 17 June 2018
Stability › Watertight Integrity › Watertight Subdivision Standard
Issued 29 November 2016
Resolved
Wire penetration portside forward engine room are not watertight.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 30 December 2016
Resolved 16 December 2016
Resolution: Attended vessel.
Fire Fighting › Ventilation Systems › Fans
Issued 29 November 2016
Resolved
Replace exhaust blower in portside engine room.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 30 December 2016
Resolved 16 December 2016
Resolution: Attended vessel.
Engineering › Bilge Water Management System › Strainer
Issued 29 November 2016
Resolved
Replace plastic bilge strainer.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 30 December 2016
Resolved 16 December 2016
Resolution: Attended vessel.
Engineering › Shafting/Propeller Arrangements › Bearing
Issued 29 November 2016
Resolved
Replace cutless bearings on both shafts.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 30 December 2016
Resolved 16 December 2016
Resolution: Attended vessel.
Stability › Watertight Integrity › General
Issued 29 November 2016
Resolved
Weld the backside of insert deck plate in galley.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 30 December 2016
Resolved 16 December 2016
Resolution: Attended vessel.
Engineering › Freshwater System (jacketwater cooling) › Fitting
Issued 29 November 2016
Resolved
Replace seals on keel coolers.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 30 December 2016
Resolved 16 December 2016
Resolution: Attended vessel.
Accommodation/Occupational Safety › Potable Water System › General
Issued 29 November 2016
Resolved
Fabricate a permanent mount for fresh water bladder tank.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 30 December 2016
Resolved 16 December 2016
Resolution: Attended vessel.
Fire Fighting › Fire Pumps › Capacity
Issued 8 April 2016
Resolved
Fire pump wasted and leaking from bottom of housing. Replace to the satisfaction of MI.
Action required: 701 - Prior to carriage of passengers/cargo
Due 8 April 2016
Resolved 21 April 2016
Resolution: Attended vessel and observed a stream of fire fighting water provided from fire pump, pressure of 60 psi on pressure guage and no leaks from new pump housing.
Communications › Alarms/Indicators › Fire Alarm
Issued 8 April 2016
Resolved
Fire detection system showing fault. Rectify and prove proper operation.
Action required: 701 - Prior to carriage of passengers/cargo
Due 8 April 2016
Resolved 21 April 2016
Resolution: Attended vessel and observed properly operating panel with no errors or alarms.