Inspection record

Last inspected 18 November 2025
…with no type recorded1
Operational controls None recorded without a removal date
Years with a record 10 calendar years (2016–2025)
Every line above is a count of records the US Coast Guard wrote, or a date it recorded. A blank resolution means none was recorded in this data; it does not establish that a deficiency is outstanding. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Identity

WDJ 5765
360058
Flag
UNITED STATES
Maury page id
psix-360058

Documentation record

Registered dimensions (L × B × D)30.2 ft × 15.9 ft × 4.4 ft
Registered tonnagegross 14 / net 11
ITC dimensions (L × B × D)Not recorded
ITC tonnageNot recorded
BuilderWESTERLY MARINE INC · COSTA MESA, CA, UNITED STATES · built 1991
Hull materialFRP (Fiberglass)
PropulsionDiesel Reduction
Hull shapeShip
Hull configurationMonohull
Hailing portBOSTON, MA
Endorsements, as the file codes themcw_un
DocumentationValid · issued 6 August 2025 · expires 30 September 2026
Service, as the file records itPassenger (Inspected)
Hull formpowered (Maury's inference from propulsion, hull shape, material and length, rule hf-1; not a recorded fact)
Tonnage as PSIX records it14 - Simplified, Gross Ton
11 - Simplified, Net Ton
Every line above is a field of the National Vessel Documentation Center's file as served by NOAA Fisheries, dated 10 August 2026, matched to this hull on its Official Number. Registered and ITC measurements are two systems and are never combined. One snapshot is held so far; documentation history begins with the next.
Professional
The full record for this vessel

Behind this panel: 19 inspections, each with its date, unit and type; 13 deficiencies with the resolution recorded against each; operational controls, none recorded without a removal date; 2 other vessels inspected with it; no other recorded names; the documentation record: dimensions, tonnage, builder, hailing port and endorsements. Every line is a record the Coast Guard wrote; the counts above are the same counts as in the summary, and they are free.

Professional is $39 a month or $299 a year, or $19.99 a month locked for life at the founding rate, for the first 200 subscribers. It unlocks every detail section on every vessel page, fleet watch tied to your account, and ownership records on request. Already a subscriber? Sign in.

Maury does not score, rate or grade vessels, at any price.

Vessel history report
Every record for this hull, in one document — $299

Every recorded inspection, 1972 to 2026, in one chronology · every deficiency, with system, dates and resolution · operational controls imposed and removed · every name this hull has been recorded under · the vessels it was inspected alongside, and when · how its record compares with hulls of similar age and size, as a fact about the population and never a judgement about this vessel.

Read one first, in full: a forty-year chronology · a hull that changed operators four times · the sparse case, shown as an example, not for sale.

This report is in development and is not for sale yet. There is no date, and nothing is charged. Leave an email and we will tell you when it exists, once.

Inspected as a tow unit · 2

The Coast Guard recorded this vessel and the following in the same inspection activity — normally a tug and the barges in its tow. A recreational or unclassed hull in the same activity is held and not published, so it does not appear here: these lists are a floor, not a complete manifest.

ASTERIA Passenger (Inspected) · MISLE 478192 · 23 September 2022 · activity 7565414CETACEA Passenger (Inspected) · MISLE 486258 · 23 September 2022 · activity 7565414

Inspection history · 19

18 November 2025 Vessel Attendance · Annual Inspection
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 8265612
21 August 2025 Vessel Attendance · Drydock Exam · Internal Structural Exam
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 8213232
28 October 2024 Annual Inspection
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 8028126
28 November 2023 Deficiency Check · Annual Inspection
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 7828031
7 June 2023 Internal Structural Exam · Examination of Repairs · Deficiency Check · Hull Examination
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 7689550
13 January 2023 Annual Inspection
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 7619142
23 September 2022 Deficiency Check · Damage Survey
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 7565251
23 September 2022 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 7565414
29 October 2021 COI Inspection · Deficiency Check
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 7337026
21 May 2021 Hull Examination
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 7200041
12 August 2020 Annual Inspection · Deficiency Check
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 7032184
25 October 2019 Administrative Inspection
Administrative · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6841870
20 August 2019 Deficiency Check · Annual Inspection
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6788512
24 April 2019 Hull Examination
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6669409
12 July 2018 Annual Inspection
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6476602
19 July 2017 Administrative Inspection
Administrative · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6216247
9 May 2017 COI Inspection · Hull Examination
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6144010
25 May 2016 Annual Inspection
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 5797036
13 April 2016 Hull Examination
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 5796736

Deficiency record · 13

13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 18 November 2025 Resolved
Propulsion machinery must be suitable in type and design for propulsion requirements of the hull in which it is installed and capable of operating at constant marine load under such requirements without exceeding its designed limitations. Main engine was inoperable and was not able to start. Rectify issue to the satisfaction of a qualified MI.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 3 December 2025
Resolution: Attended vessel and witnessed operable main engine.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 18 November 2025 Resolved
A pre-engineered fixed gas fire extinguishing system must:(1) Be approved by the Commandant;(2) Be capable of manual actuation from outside the space in addition to automatic actuation by a heat detector;(3) Automatically shut down all power ventilation systems and all engines that draw intake air from within the protected space; and(4) Be installed in accordance with the manufacturer's instructions. Engine shutdown, visual and audible alarms, and engine bypass were not able to be tested due to inoperable main engine.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 2 December 2025
Resolved 3 December 2025
Resolution: Witnessed engine shutdown with audible and visual alarms. Verified override function for fireboy was operable as well.
11 - Life Saving Appliances › N/A - No Subsystem › Distress flares
Issued 18 November 2025 Resolved
A vessel on a lakes, bays, and sounds, or rivers route must carry:(1) Three hand red flare distress signals and 2) Three hand orange smoke distress signals. Vessel was missing 02 hand red flares.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 2 December 2025
Resolved 3 December 2025
Resolution: Provided missing red hand flares.
11 - Life Saving Appliances › N/A - No Subsystem › Distress flares
Issued 18 November 2025 Resolved
Each flare carried to meet this section must be stowed in one of the following:(1) A portable watertight container marked as required by § 185.614 of this chapter, carried at the operating station. Flares were not stored in a separate labeled container. Obtain watertight container for flares marked "DISTRESS SIGNALS."
Action required: 16 - Rectify deficiencies w/in 14 days
Due 2 December 2025
Resolved 3 December 2025
Resolution: Provided suitable separate watertight container for flares.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 18 November 2025 Resolved
Each floating waterlight must be approved in accordance with § 161.010 in subchapter Q of this chapter, or other standard specified by the Commandant, including, but not limited to, approval series 160.110. Battery for waterlight was expired. Replace with an approved type battery. Limited to daytime operations until rectified.
Action required: 705 - Other - as specified
Resolved 3 December 2025
Resolution: New battery installed with 2027 expiration year.
08 - Alarms › N/A - No Subsystem › Other (alarms)
Issued 18 November 2025 Resolved
Gauges to indicate engine cooling water discharge temperature and lubricating oil pressure shall be provided for all propulsion engines and located so as to be in view of the operator. Gauges were not able to be tested due to inoperable main engine.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 2 December 2025
Resolved 3 December 2025
Resolution: Verified operable gauges at helm for engine cooling water discharge temperature and lubricating oil pressure.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 21 August 2025 Resolved
The owner or managing operator shall make a vessel available for drydock examinations, internal structural examinations, and underwater surveys (UWILD) required by this section. A vessel that is exposed to salt water more than three months in any 12 month period since the last examination must undergo a drydock examination and an internal structural at least once every two years. Vessel missed drydock exam date. Must complete credit hull exam prior to carrying passengers.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 15 October 2025
Resolution: Vessel drydocked.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 28 November 2023 Resolved
Propulsion machinery shall be suitable in type and design for propulsion requirements of the hull in which it is installed and capable of operating at constant marine load under such requirements without exceeding its designed limitations. Shaft seal was found with considerable leak. 46 CFR 182.05-1 - 16 c.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 12 December 2023
Resolved 12 December 2023
Resolution: Shaft seal verified tightened with no visible leaks, all sat.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 23 September 2022 Resolved
Repairs or alterations to the hull, machinery, or equipment that affect the safety of the vessel must not be made without the approval of the cognizant [name withheld] damage exists on STBD side amidships from allision with another vessel. Communicate repair plan with OCMI and receive approval for repair prior to commencing work. Complete repairs to the satisfaction of the OCMI.
Condition: Damaged By Earlier Event
Action required: 701 - Prior to carriage of passengers/cargo
Due 7 October 2022
Resolved 25 October 2022
Resolution: Repaired damage to fiberglass hull. See general information narrative for details pertaining repair.
10 - Safety of Navigation › N/A - No Subsystem › Charts
Issued 29 October 2021 Resolved
As appropriate for the intended voyage, a vessel must carry adequate and up to date charts of large enough scale to make safe navigation possible. The charts on the vessel were last updated in 2016. Vessel to provide current charts for the areas to be navigated.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 12 November 2021
Resolved 17 November 2021
Resolution: Verified current charts were onboard.
09 - Working and Living Conditions › 092 - Working Conditions › Personal equipment
Issued 29 October 2021 Resolved
Each vessel must be equipped with at least two operable portable battery lights. One of these lights must be located at the operating station and the other at the access to the propulsion machinery space. The vessel did not have any portable lights onboard. Vessel to provide adequate portable lights.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 12 November 2021
Resolved 17 November 2021
Resolution: Verified portable lights were onboard.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 12 August 2020 Resolved
Each pre-engineered fixed gas fire extinguishing system installed must have an audible alarm that sounds upon discharge. The fixed gas fire extinguisher in the engine space has an inoperable alarm.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 26 August 2020
Resolved 13 August 2020
Resolution: Vessel provided a video showing the correct operation of the fireboy.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 20 August 2019 Resolved
A visual indicator must be provided at the operating station to indicate when any automatic bilge pump is operating. There is no visual indicator at the operating station.
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 3 September 2019
Resolved 10 September 2019
Resolution: Rectified visual indicator

Ownership record

The Coast Guard's documentation record for this hull -- the Abstract of Title, with its owners and liens as filed -- is not in PSIX. Ask, and Maury buys it from the National Vessel Documentation Center, files it here with its date, and every reader of this page gets it.