Records from 2002 to 2025. Most recent: inspection, 11 December 2025.
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 11 December 2025
Resolved
All escape hatches and other emergency exits used as means of escape must be marked on both sides in clearly legible letters at least 50 millimeters (2 inches) high: “EMERGENCY EXIT, KEEP CLEAR”.. Port and STBD E/R FWD emergency exit openings are not marked on the outside,
nor operating instructions on inside. 46 CFR 122.606
Condition: Design Flaw
Action required: 16 - Rectify deficiencies w/in 14 days
Due 26 December 2025
Resolved 12 February 2026
Resolution: Received sufficient photo evidence of installed E/R escape hatch markings.
01 - Certificates & Documentation › 013 - Documents › Signs, indications
Issued 11 December 2025
Resolved
On a vessel on which the number of passengers permitted on upper decks is limited by stability criteria, as indicated by the vessel's stability letter, the maximum number of passengers allowed on an upper deck must be indicated by a durable marking of at least 25 millimeters (1 inch) numbers and letters at the entranceway to that deck. Max number of passenger allowed on upper deck not marked at entrances. 46 CFR 122.602(f)
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 26 December 2025
Resolved 23 January 2026
Resolution: Received evidence of markings in required locations.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 11 December 2025
Resolved
Provision must be made for closing all supply duct cowls or scoops and exhaust duct discharge openings for a space protected by a fixed gas extinguishing system. All closure devices must be readily available and mounted in the vicinity of the vent. STBD E/R fire damper had several missing/wasted components (bolts and associated housing) potentially compromising intended operation. 46 CFR 119.465(h)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 26 December 2025
Resolved 15 January 2026
Resolution: Received photo evidence of installed new parts and proper function of damper components.
09 - Working and Living Conditions › 092 - Working Conditions › Pipes, wires (insulation)
Issued 11 December 2025
Resolved
Piping, including valves, pipe fittings and flanges, conveying vapor, gas, or liquid, the temperature of which exceeds 65.5 °C (150 °F), must be insulated where necessary to prevent injuries. Lagging found missing at STBD generator and M/E. 46 CFR 116.970
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 26 December 2025
Resolved 23 January 2026
Resolution: Received evidence of installed lagging where required.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Operation of machinery
Issued 11 December 2025
Resolved
At each initial and subsequent inspection for certification of a vessel, the owner or managing operator shall be prepared to conduct tests and have the vessel ready for inspections of machinery, fuel, and piping systems, including ..Inspection of all machinery essential to the routine operation of the vessel including generators and cooling systems. Cooling water leak found on Port generator. 46 CFR 115.804(c)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 26 December 2025
Resolved 23 January 2026
Resolution: Received video of port generator running with no leaks.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Operation of machinery
Issued 11 December 2025
Resolved
At each initial and subsequent inspection for certification of a vessel, the owner or managing operator shall be prepared to conduct tests and have the vessel ready for inspection of electrical equipment and systems, including ..Inspection of rotating electrical machinery essential to the routine operation of the vessel. STBD fire/bilge pump cover found loose, making contact/interference with moving parts. 46 CFR 115.806(d)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 26 December 2025
Resolved 15 January 2026
Resolution: Received photo evidence of motor cover plate secured.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 20 February 2025
Resolved
Electrical equipment on a vessel must be installed and maintained to: provide services necessary for safety under normal and emergency conditions. MI observed a pin hole leak occurring in the port generator raw water exhaust elbow along the weld seam leaking water above the adjacent battery bank. Conduct repairs to the elbow to prevent water leakage to MI satisfaction.
46 CFR 120.200(a)
Condition: Invalid
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 21 February 2025
Resolution: MI attended to witness satisfactory weld repair along former leaking elbow seam, OP test showed no leakage.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Railing, gangway, walkway and means for safe passage
Issued 20 February 2025
Resolved
Except as otherwise provided in this section, rails or equivalent protection must be installed near the periphery of all decks of a vessel accessible to passengers or crew. MI observed forward mid-rail close to midship on forward portion of vessel sheered. Conduct repairs to MI satisfaction.
46 CFR 116.900
Condition: Invalid
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 17 March 2025
Resolution: Operator submitted SAT photos of rewelded forward rails.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 3 January 2025
Resolved
Propulsion machinery must be suitable in type and design for propulsion requirements of the hull in which it is installed and capable of operating at constant marine load under such requirements without exceeding its designed limitations. Vessel experienced a ruptured cooling pipe on its starboard main engine. Repair the cooling pipe system and conduct satisfactory sea trails in the presence of a Marine Inspector.
46 CFR 119.200(a)
Condition: Invalid
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 4 January 2025
Resolution: Attended vessel and conducted satisfactory sea trails after vessel replaced failed piping system, all sat.
07 - Fire Safety › N/A - No Subsystem › Fire control plan
Issued 28 March 2024
Resolved
A fire control plan must be posted on the vessel in a location that is accessible and visible to all passengers. The plan must show escape routes, areas of refuge, embarkation stations, the location of fire protection/emergency equipment, compartment titles and hazard classification of accommodation and service spaces, and structural fire protection boundaries. Fire control plan is missing approval from USCG.
Condition: Invalid
Action required: 705 - Other - as specified
Resolved 29 July 2024
Resolution: MI stamped FCP with approval.
02 - Structural Conditions › N/A - No Subsystem › Hull - cracking
Issued 29 November 2023
Resolved
The construction and arrangement of a vessel must allow the safe operation of the vessel in accordance with the terms of its Certificate of Inspection giving consideration to provisions for a seaworthy hull, protection against fire, means of escape in case of a sudden unexpected casualty, guards and rails in hazardous places, ventilation of enclosed spaces, and necessary facilities for passengers and crew. The vessel had a fracture in its port fuel void on the outboard side. Fix at next credit dry dock.
Condition: Damaged By Earlier Event
Action required: 705 - Other - as specified
Resolved 24 May 2024
Resolution: Vessel fracture repair SAT.
02 - Structural Conditions › N/A - No Subsystem › Beams, frames, floors-op. damage
Issued 29 November 2023
Resolved
The construction and arrangement of a vessel must allow the safe operation of the vessel in accordance with the terms of its Certificate of Inspection giving consideration to provisions for a seaworthy hull, protection against fire, means of escape in case of a sudden unexpected casualty, guards and rails in hazardous places, ventilation of enclosed spaces, and necessary facilities for passengers and crew. The vessel had a broken fairlead on its forward starboard side. Fix at next credit dry dock.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 24 May 2024
Resolution: Fairlead satisfactorily repaired.
07 - Fire Safety › N/A - No Subsystem › Ventilation
Issued 29 November 2023
Resolved
The construction and arrangement of a vessel must allow the safe operation of the vessel in accordance with the terms of its Certificate of Inspection giving consideration to provisions for a seaworthy hull, protection against fire, means of escape in case of a sudden unexpected casualty, guards and rails in hazardous places, ventilation of enclosed spaces, and necessary facilities for passengers and crew. The vent on the aft, starboard side of the vessel is missing its cover. Fix at next credit dry dock.
Condition: Design Flaw
Action required: 705 - Other - as specified
Resolved 27 May 2024
Resolution: Vent repaired to satisfaction of MI.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 29 November 2023
Resolved
A door in a stairtower, stairway, and main vertical zone bulkhead must meet the following additional requirements: A door must be of the self-closing type capable of closing against a 3.5 list of the vessel. The battery disconnect door on the top deck, port side, had broken hinges. Fix at next credit dry dock.
Condition: Improper Installation
Action required: 705 - Other - as specified
Resolved 24 May 2024
Resolution: Battery Door repaired to satisfaction of MI.
11 - Life Saving Appliances › N/A - No Subsystem › Other (life saving)
Issued 29 November 2023
Resolved
Each inflatable buoyant apparatus must be equipped in accordance with the manufacturer's approved servicing manual. The hydrostatic releases on the starboard side IBAs were not dated. Fixed to the satisfaction of the present Marine Inspector.
Condition: Improper Installation
Action required: 10 - Deficiency Rectified
Resolved 29 November 2023
Resolution: Hydrostatic release on the IBAs were dated
07 - Fire Safety › N/A - No Subsystem › Maintenance of Fire protection systems
Issued 27 January 2023
Resolved
For fixed gas fire extinguishing systems, a qualified servicing facility shall conduct the inspections and tests required by Table 115.810(b): Test time delays, and ventilation shutdowns. On December 30, 2022, Global Fire and Safety identified the starboard CO2 time delay needs replacement due to corrosion. A qualified servicing facility is required to replace the time delay, and subsequently test the system to prove compliance with NFPA 12.
46 CFR 115.810(b)(2)
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 February 2023
Resolved 6 June 2023
Resolution: GFS replaced starboard CO2 time delay.
07 - Fire Safety › N/A - No Subsystem › Maintenance of Fire protection systems
Issued 27 January 2023
Resolved
For fixed gas fire extinguishing systems, a qualified servicing facility shall conduct the inspections and tests required by Table 115.810(b): Test time delays, and ventilation shutdowns. On December 30, 2022, Global Fire and Safety identified that all dampers need modification and repair in order to simplify testing and resetting. Repair engine room fire dampers to original CG approval of installed system.
46 CFR 115.810(b)(2)
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 February 2023
Resolved 6 June 2023
Resolution: GFS repaired engine room fire dampers to satisfaction of Marine Inspector.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 25 January 2023
Resolved
At each subsequent inspection, the operator shall be prepared to conduct operational tests of the means provided for pumping bilges. The vessel’s crew was unfamiliar with the labeling on the bilge manifold. Update or clarify labeling on bilge manifold to ensure ease of use during emergency situations.
46 CFR 115.804(h)
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 22 February 2023
Resolved 15 June 2023
Resolution: Received sat evidence of updated bilge manifold labeling.
09 - Working and Living Conditions › 092 - Working Conditions › Warning notices
Issued 25 January 2023
Resolved
Each entrance to a space storing carbon dioxide cylinders must be conspicuously marked IAW 46 CFR 122.612(i)(1). Starboard CO2 storage compartment was not labeled with warning sign. Install sign with required verbiage to satisfaction of the Marine Inspector.
46 CFR 122.612(i)(1)
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 22 February 2023
Resolved 15 June 2023
Resolution: Received sat evidence of installed sign.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Covers (hatchway-, portable-, tarpaulins, etc.)
Issued 25 January 2023
Resolved
A hatch cover must be attached to the hatch frame or coaming by hinges, captive chains, or other devices of substantial strength to prevent its loss. 02 watertight hatches on the main deck port hole had missing securing devices. Install securing devices.
46 CFR 116.1160 (b)(2)
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 22 February 2023
Resolved 15 June 2023
Resolution: Received sat evidence of installed securing devices.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 25 January 2023
Resolved
Electrical equipment in a machinery space must be drip proof. The port fuel oil tank electronic sounding device has exposed conductors. Properly insulate the conductors to ensure a drip proof arrangement.
46 CFR 120.210 (a)(1)
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 22 February 2023
Resolved 15 June 2023
Resolution: Received sat evidence of insulated conductors.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 25 January 2023
Resolved
Flexible hoses must meet the requirements of 56.60-25 in subchapter F. Nonmetallic flexible hose must be in accordance with SAE J1942 and may be installed in fuel systems. The port fuel tank return line has 02 sections of non-metallic flexible hose that is not rated for fuel oil service. Replace with appropriate SAE J1942 fuel rated hose.
46 CFR 119.455 (a)(1)(iii), 46 CFR 56.60-25 (b)(1)
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 22 February 2023
Resolved 15 June 2023
Resolution: Received sat evidence of replaced flexible hose.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 25 January 2023
Resolved
Machinery and equipment installed on the vessel must be suitable for the vessel and its operation and for the purpose intended. The port black water non-ferrous piping is actively leaking at a rate of one drop every five seconds in the port engine room. Repair leak to the satisfaction of the Marine Inspector.
46 CFR 119.100
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 22 February 2023
Resolved 15 June 2023
Resolution: Pipe run replaced in kind.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 25 January 2023
Resolved
Shutoff valves, installed so as to close against the fuel flow, must be fitted in the fuel supply lines, one at the tank connection. The fuel shutoff valve at the tank connection was seized in the open position. Prove proper operation of fuel shutoff valve.
46 CFR 119.455(b)(3)
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 26 January 2023
Resolved 26 January 2023
Resolution: Operator corrected deficiency on the spot and demonstrated proper operation to the satisfaction of the Marine Inspector.
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 25 January 2023
Resolved
At each inspection, all observed unsafe practices, fire hazards, and other hazardous situations must be corrected. Port Engine Room and Starboard Engine Room had an excessive amount of flammable liquids contained in 5 gallon containers stored on the battery compartments. Remove flammable liquids from the port and starboard engine room.
46 CFR 115.830 (a)
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 26 January 2023
Resolved 26 January 2023
Resolution: Operator removed flammable liquids from vessel.
04 - Emergency Systems › N/A - No Subsystem › Emergency source of power - Emergency generator
Issued 10 January 2023
Resolved
At 0650 local on 10 January 2023, Sector San [name withheld] Center (SCCSF) received a notification from [name withheld] on the Ferry Peralta ([phone withheld]) reporting that the Ferry has lost electricity due to the port side generator malfunctioning. Further investigation from the duty IO [name withheld] confirmed that the vessel temporarily had a loss of steering for approximately 2 minutes before fixing their generator issue and regaining electricity to the vessel. Ferry Peralta then safely made their way back to the ferry terminal.
46 CFR 120.200 (a)
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 11 January 2023
Resolution: Vessel replaced 120v to 24v inverter for Generator digital control display. Numerous tests conducted satisfactorily
08 - Alarms › N/A - No Subsystem › Other (alarms)
Issued 30 November 2021
Resolved
Each alarm must be provided with a visual and audible alarm at the operating station to indicate high water level in normally unmanned spaces. Stbd lazarette audio alarm inoperable.
Condition: Design Flaw
Action required: 10 - Deficiency Rectified
Due 27 December 2021
Resolved 30 November 2021
Resolution: Received video evidence from operator of audible and visual stbd lazarette alarm working.
02 - Structural Conditions › N/A - No Subsystem › Openings to cargo area, doors, ... scuttles
Issued 30 November 2021
Resolved
A storage cylinder space must have doors that open outwards. Door to CO2 cylinders seized in closed position.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 30 December 2021
Resolved 27 December 2021
Resolution: Resolved during dry dock, see MISLE activity 7367494.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 30 November 2021
Resolved
At each initial and subsequent inspection for certification, the owner or managing operator shall have the vessel ready for inspection of its fire protection equipment, including hand portable fire extinguishers. Pressure gauge on portable fire extinguisher at top of starboard engine room was outside operational zone.
Condition: Invalid
Action required: 10 - Deficiency Rectified
Due 27 December 2021
Resolved 13 January 2022
Resolution: Operator provided evidence of extinguisher pressure gauge in satisfactory operational zone.
04 - Emergency Systems › N/A - No Subsystem › Emergency, lighting, batteries and switches
Issued 30 November 2021
Resolved
Each lighting fixture globe,lens or diffuser must have a guard. Cracked lighting fixture in engine room, does not meet requirements.
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 30 December 2021
Resolved 27 December 2021
Resolution: Light fixture cover replaced.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 30 November 2021
Resolved
At each inspection, the operator shall be prepared to conduct tests and have the vessel ready for inspection, including the following: Inspection of piping, controls, and valves for each fixed gas fire extinguishing system. CO2 line directly over port engine sheared at one of the threaded connections, leaving two of the discharge horns disconnected.
Condition: Damaged By Earlier Event
Action required: 60 - Rectify deficiencies prior to movement
Due 30 November 2021
Resolved 1 December 2021
Resolution: CO2 line repaired and sat tested.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 30 November 2021
Resolved
Piping, valves, and fittings must be securely supported, and where necessary protected against damage. CO2 support for pipe over starboard engine found broken and no longer supporting pipe.
Condition: Damaged By Earlier Event
Action required: 50 - Rectify deficiencies w/in 30 days
Due 29 December 2021
Resolved 27 December 2021
Resolution: Operator provided photo evidence of loose pipe clamp secured.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 30 November 2021
Resolved
A control cabinet or space containing valves, manifolds, or controls for any fixed gas fire extinguishing system must be conspicuously marked in clearly legible letters "CARBON DIOXIDE FIRE EXTINGUISHING APPARATUS". No marking present on starboard CO2 room door.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 30 December 2021
Resolved 30 December 2021
Resolution: Operator provided signage for CO2.
08 - Alarms › N/A - No Subsystem › Other (alarms)
Issued 24 August 2021
Resolved
Each vessel must be provided with a visual and audible alarm at the operating station to indicate a high water level in any space subject to flooding from sea water. Starboard and port lazarette audible alarm not operable. Master to verify bilge alarm status via the alarm logbook on electronic display in operation station before every departure. This check is to be logged in the vessel's underway soft log until audible alarm is operable. Send video of operable alarm to marine inspector.
Action required: 705 - Other - as specified
Resolved 31 August 2021
Resolution: Vessel rep verified PLC had incorrect setting (single beep vs. continuous alarm loop) and confirmed proper alarm via videos.
11 - Life Saving Appliances › N/A - No Subsystem › Stowage and provision of liferafts
Issued 27 November 2019
Resolved
Each survival craft must be stowed so that when the vessel sinks the survival craft floats free and, if inflatable, inflates automatically. The bowsing line for each IBA was attached to the vessel via a secondary bowsing line. Arrangement prevented the IBA from being able to float free. Operator corrected the deficiency on the spot and stowed the IBA IAW 46 CFR 117.130.
Condition: Improper Installation
Action required: 10 - Deficiency Rectified
Due 27 November 2019
Resolved 27 November 2019
Resolution: Arranged survival craft to make them float-free.
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 27 November 2019
Resolved
A-Class bulkheads or decks must be composed of steel or equivalent material and must be insulated with approved structural insulation, bulkhead panels, or deck coverings. The stbd engine room escape hatch insulation had multiple cracks and was not fully intact. Maintain A-Class boundary IAW 46 CFR 116.415.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 11 December 2019
Resolved 13 January 2020
Resolution: Received photos regarding new, intact insulation.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Covers (hatchway-, portable-, tarpaulins, etc.)
Issued 27 November 2019
Resolved
A hatch cover must have securing devices. One of the dogs on the port, void #2 hatch was missing. Replace to meet watertight integrity regulations. 46 CFR 116.1160(b)(1)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 11 December 2019
Resolved 9 December 2019
Resolution: Replaced 01 dog on the hatch.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 27 November 2019
Resolved
Spanner wrenches must be provided for each fire hydrant. The spanner wrench was missing for Fire Station #1. Place a spanner wrench in the vicinity of Fire Station #1.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 11 December 2019
Resolved 9 December 2019
Resolution: Placed wrench at fire station #1.
01 - Certificates & Documentation › 013 - Documents › Fire control plan - all
Issued 15 November 2018
Resolved
A fire control plan must show the fire protection boundaries depicted on the vessel. Vessel primary port and starboard engine room fire doors not self closing. Port side main deck electrical space fire door not self closing. Operator must confirm with MSC and provided documentation to the Coast Guard.
Condition: Invalid
Action required: 701 - Prior to carriage of passengers/cargo
Due 30 November 2018
Resolved 21 November 2018
Resolution: Operator provided approved MSC letter
02 - Structural Conditions › N/A - No Subsystem › Stability/strength/loading information and instruments
Issued 15 November 2018
Resolved
Up to date signed stability letter must be displayed on the vessel, in an accessible place for passengers and crew. Vessel must obtain new stability letter signed by MSC and post it on board the vessel.
Condition: Invalid
Action required: 701 - Prior to carriage of passengers/cargo
Due 30 November 2018
Resolved 26 November 2018
Resolution: Vessel provided signed stability letter.
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 15 November 2018
Resolved
Bilges must be keep clear of excessive oil to reduce the possible of a fire or clogging a bile pumping system. Vessel must remove the excessive oil in both the port and starboard engine rooms. 1 week to get bilges clean.
Condition: Damaged By Earlier Event
Action required: 705 - Other - as specified
Due 23 November 2018
Resolved 29 November 2018
Resolution: Bilges have been cleaned to the satisfaction of the CG.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 15 November 2018
Resolved
One life ring on board the vessel must be fitted with a operational floating watertight. The floating water light needs to get a new battery.
Condition: Damaged By Earlier Event
Action required: 10 - Deficiency Rectified
Due 15 November 2018
Resolved 15 November 2018
Resolution: New battery
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 15 November 2018
Resolved
Each child size life jacket must be stowed in a location that is appropriately marked. Vessel needs to properly label the fire plan to show locations of child life jackets.
Condition: Damaged By Earlier Event
Action required: 50 - Rectify deficiencies w/in 30 days
Due 16 December 2018
Resolved 30 November 2018
Resolution: Fire plan was updated with locations of child PFD's
11 - Life Saving Appliances › N/A - No Subsystem › Other (life saving)
Issued 15 November 2018
Resolved
The man overboard equipment is has a placard indicating the that storage compartment is for life rafts. The placard needs to corrected to show that the stowage box houses the man over board equipment.
Condition: Improper Installation
Action required: 10 - Deficiency Rectified
Due 15 November 2018
Resolved 15 November 2018
Resolution: Placard was fixed
10 - Safety of Navigation › N/A - No Subsystem › Other (navigation)
Issued 15 November 2018
Resolved
The vessels bell was not installed in the correct position. The bell needs to be installed on the bow IAW with vessel design.
Condition: Improper Installation
Action required: 10 - Deficiency Rectified
Due 15 November 2018
Resolved 15 November 2018
Resolution: Bell instaled
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 15 November 2018
Resolved
Insulation is required on aluminum vessels in order to full fill the requirements of a fire control boundary. A piece of insulation in the main deck port side electrical room had a piece of insulation missing, it must be replaced.
Condition: Improper Installation
Action required: 10 - Deficiency Rectified
Due 15 November 2018
Resolved 15 November 2018
Resolution: Securing device was attached
09 - Working and Living Conditions › 092 - Working Conditions › Other (accident prevention)
Issued 15 November 2018
Resolved
Securing device for a void hatch was missing. Securing device needs to be established on the hatch.
Condition: Improper Installation
Action required: 10 - Deficiency Rectified
Due 15 November 2018
Resolved 15 November 2018
Resolution: Securing device was attached.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 15 November 2018
Resolved
valve handle missing on the starboard MDE engine cooling system. Valve must be replaced so that the system can be operated as designed.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 December 2018
Resolved 29 November 2018
Resolution: Valve has been replaced.
07 - Fire Safety › N/A - No Subsystem › Ventilation
Issued 15 November 2018
Resolved
Ventilation closures for both steering spaces missing securing device. Securing devices must be installed to secure ventilation for the steering gear spaces.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 December 2018
Resolved 29 November 2018
Resolution: Securing devices were installed on the ventilation closures for the steering gear space.
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 15 November 2018
Resolved
Engine rooms must be lined with insulation IAW fire boundary policy. Starboard engine room had a piece of insulation missing near the through deck penetration.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 December 2018
Resolved 29 November 2018
Resolution: Insulation replaced in starboard MDE room.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 15 November 2018
Resolved
Starboard engine room MDE exhaust, In proximity of the muffler is missing lagging. Lagging needs to be replaced to prevent personal injury and reduce fire risk.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 December 2018
Resolved 24 December 2018
Resolution: Lagging was installed.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 15 November 2018
Resolved
Strainers on bilge system are plastic. Because it is a vital system bilge strainers need to be metallic, plastic can be used only if approved by the Commandant. Strainers will be replaced during next dry dock.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 14 December 2018
Resolved 19 March 2021
Resolution: Vessel is authorized to have a plastic bilge strainer installed in bilge systems, provided it is not in the machinery space. There is a local policy regarding this matter that will be released in the near future.
Construction/Loadline › Hull › Hull Plating
Issued 30 October 2017
Resolved
Make permanent repairs to holed section of port bow resulting from buoy strike at next Credit Dry Dock.
Action required: 705 - Other - as specified
Resolved 1 August 2018
Resolution: Repair completed see comments in activity# 6351181
Construction/Loadline › Hull › Bottom Plating
Issued 15 June 2017
Resolved
Vessel had small portion of cracked bottom plate and several cracked welds all within the port lazarette. Cause is due to known issue of additional stresses to the lazarettes. Re-inspection of port laz due on 23JUN17 to assess the condition after the vessel has been in service for a week following repairs to above mentioned cracks.
Condition: Design Flaw
Action required: 705 - Other - as specified
Due 23 June 2017
Resolved 23 June 2017
Resolution: Cleared.
Construction/Loadline › Hull › Bracket
Issued 14 October 2016
Resolved
Provide written repair proposal approved by OEM to install additional structure IWO port and stbd lazarettes to address ongoing fractures.
Action required: 705 - Other - as specified
Due 1 December 2017
Resolved 16 March 2018
Construction/Loadline › Hull › Bracket
Issued 14 October 2016
Resolved
Complete additional structure repairs IAW OEM recommendations and crop / renew all known fractures on structural members in port and stbd lazarettes.
Action required: 705 - Other - as specified
Due 1 December 2017
Resolved 10 August 2018
Resolution: Corrected during Drydock 2018; Act# 6351181
Construction/Loadline › Hull › Longitudinal Frame
Issued 14 October 2016
Resolved
Provide updated map of all fractures that were found during October 2016 drydock and were repaired or remain.
Action required: 705 - Other - as specified
Due 14 November 2016
Resolved 25 November 2016
Resolution: Map provided 09NOV16.
Construction/Loadline › Hull › Bottom Plating
Issued 14 October 2016
Resolved
Provide results of vibrations study following modifications to prop locations.
Action required: 705 - Other - as specified
Due 14 November 2016
Resolved 4 November 2016
Resolution: Report provided, added to documents.
Construction/Loadline › Hull › Bottom Plating
Issued 14 October 2016
Resolved
Conduct weekly rounds of both lazarettes. Inspection shall be logged and signed by the master or B&G engineer. Any new fractures shall be noted and reported to OCMI until final OEM repairs are completed.
Action required: 705 - Other - as specified
Resolved 16 November 2018
Resolution: Customs propellers were constructed and installed to help cut down on vibration. NCE vibration survey is attached in documents are well.
Construction/Loadline › Hull › Bottom Plating
Issued 11 August 2016
Resolved
Crop and renew 9 inch crack in hull bottom plating IWO port lazarette.
Condition: Damaged By Earlier Event
Action required: 701 - Prior to carriage of passengers/cargo
Due 20 August 2016
Resolved 20 August 2016
Resolution: Resolved on the phone with [name withheld] (Senior DMI)
Construction/Loadline › Hull › Bottom Plating
Issued 11 August 2016
Resolved
Daily rounds of both lazarettes, to be conducted prior to the vessel starting service for the day and again once service has been completed. Inspections shall be logged and signed by the master or B&G engineer. Any changes to fracture length shall be noted.
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Resolved 7 October 2016
Construction/Loadline › Hull › Bottom Plating
Issued 11 August 2016
Resolved
Engineering drawings of all identified bottom plating/frame/weld fractures, previous drill stops, previous crop & renews, and all added/deleted frames/equipment/fittings shall be submitted to the local OCMI and an engineering firm of B&G's choice.
Due 25 November 2016
Resolved 7 October 2016
Construction/Loadline › Hull › Bottom Plating
Issued 11 August 2016
Resolved
Repairs to lazarette fractures shall be IAW submitted repair proposal and completed NLT 31 December 2016.
Due 31 December 2016
Resolved 7 October 2016