Records from 2016 to 2026. Most recent: inspection, 3 February 2026.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 19 June 2019
Resolved
Intrinsically safe instruments and equipment or wiring may be installed in any hazardous area for which it has been approved. Drill floor lighting panel #1 has been drilled, bondoed, and bushings are wasted/improper (46 CFR 111.80-5(a)(3)(i).
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 July 2019
Resolved 5 September 2019
Resolution: Administratively cleared after rcvg picture of newly installed drill floor lighting panel.
08 - Alarms › N/A - No Subsystem › Other (alarms)
Issued 27 June 2018
Resolved
Purged equipment should meet NFPA 496. Top drive purge control box alarm is continuous (46 CFR 108.170, 46 CFR 111.105-7(b)).
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 28 June 2018
Resolution: Examined/cleared by RO.
07 - Fire Safety › N/A - No Subsystem › Ready availability of fire fighting equipment
Issued 27 June 2018
Resolved
Emergency equipment provided shall be maintained in good condition at all times. Low bottle in Fire Locker 1.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 28 June 2018
Resolution: Examined/cleared by RO.
02 - Structural Conditions › N/A - No Subsystem › Closing devices/watertight doors
Issued 27 June 2018
Resolved
Before getting underway, the master or person in charge shall ensure that each appliance for watertight integrity is closed and watertight (CO2 room, Sack room, Between day tank, and SCR room Watertight doors are difficult to close and dog).
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 28 June 2018
Resolution: Examined/cleared by RO.
08 - Alarms › N/A - No Subsystem › Other (alarms)
Issued 27 June 2018
Resolved
If there is no means of remote control there must be an alarm system which signals whether the appliance is open or closed both locally at each appliance and in a normally manned control station. Watertight doors local indicators inoperative (46 CFR 108.114(c)(ii)).
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 28 June 2018
Resolution: Examined/cleared by RO.
11 - Life Saving Appliances › N/A - No Subsystem › Immersion suits
Issued 27 June 2018
Resolved
Each immersion suit must have a lifejacket light securely attached to the front shoulder area of the immersion suit. Lights attached in armpit area (46 CFR 108.580(c)(2)(ii).
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Resolved 28 June 2018
Resolution: Examined/cleared by CG.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 27 June 2018
Resolved
Each deckhouse must be made of steel or equivalent material. Fire door missing knobs at stairwell to Mud Pump Room (compromised boundary).
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 28 June 2018
Resolution: Examined/cleared by RO.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 27 June 2018
Resolved
Instructions for the operation of a fixed fire extinguishing system must be posted next to a fire apparatus. CO2 system activation directions are not clear (46 CFR 108.631(b)).
Condition: Invalid
Action required: 17 - Rectify deficiencies prior to departure
Resolved 28 June 2018
Resolution: Examined/cleared by RO.
07 - Fire Safety › N/A - No Subsystem › Ventilation
Issued 27 June 2018
Resolved
There must be a means to close each vent or ventilating system. Welding area awning chainfall blocking vent closure (46 CFR 108.181(b)).
Condition: Placed in Improper Service
Action required: 17 - Rectify deficiencies prior to departure
Resolved 28 June 2018
Resolution: Examined/cleared by CG.
07 - Fire Safety › N/A - No Subsystem › Ventilation
Issued 27 June 2018
Resolved
Mechanical ventilation for spaces protected by a CO2 system must be designed to shut down automatically when the system is activated. Open pipe penetration and louvers not fully cloasing/sealing in EDG Room.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 28 June 2018
Resolution: Examined/cleared by CG.
11 - Life Saving Appliances › N/A - No Subsystem › Lifeboat inventory
Issued 27 June 2018
Resolved
Each lifesaving appliance must be in good working order and ready for immediate use at all times when the unit is in operation. Lifeboats 1 and 2 searchlight electrical cables are wasted (46 CFR 109.301(a)).
Condition: Improper/Lack of Maintenance
Action required: 60 - Rectify deficiencies prior to movement
Resolved 29 June 2018
Resolution: Examined/cleared by CG via email w/ attached videos dtd 29Jun2018.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 27 June 2018
Resolved
The end of each branch line in a CO2 system must extend at least 50 millimeters (2 inches) beyond the last discharge outlet and be closed with a cap or plug. CO2 branch lines in EDG Room and fuel oil Daytank Room don't extend and no cap or plug (46 CFR 108.447(e)).
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 16 August 2018
Resolution: Examined/cleared by RO. Rcvd email fm ABS dtd 15Aug2018 indicating they confirmed installation of CO2 cleanouts on 26Jul2018.
09 - Working and Living Conditions › 092 - Working Conditions › Other (accident prevention)
Issued 27 June 2018
Resolved
Each safety belt, harness, lanyard, lifeline, and drop line must meet the specifications of ANSI 10.14/10.32. Some fall protection devices not serviced or comply or exceed standard (33 CFR 142.42(b)).
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 28 June 2018
Resolution: Examined/cleared by CG.
09 - Working and Living Conditions › 092 - Working Conditions › Other (accident prevention)
Issued 27 June 2018
Resolved
Portable eyewash equipment providing emergency relief must be immediately available where there is a reasonable probability that eye injury may occur. Expired eyewash solution in Engineering Workshop.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 19 July 2018
Resolution: Examined/cleared by CG. Rcvd email w/ pictures attached dtd 12Jul2018 showing new eyewash solution.
09 - Working and Living Conditions › 092 - Working Conditions › Other (accident prevention)
Issued 27 June 2018
Resolved
Fixed eyewash equipment providing emergency relief must be immediately available where there is reasonable probability that eye injury may occur. Eyewash stations didn't have adequate water pressure.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 28 June 2018
Resolution: Examined/cleared by RO.
10 - Safety of Navigation › N/A - No Subsystem › Lights, shapes, sound-signals
Issued 27 June 2018
Resolved
Obstruction lights shall be of sufficient candlepower as to be visible at a distance of at least five nautical miles. The lens of the bow obstruction light has condensation inside.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 28 June 2018
Resolution: Examined/cleared by CG.
10 - Safety of Navigation › N/A - No Subsystem › Lights, shapes, sound-signals
Issued 27 June 2018
Resolved
The obstruction lights shall all be mounted on the same horizontal plane. Aft obstruction lights not on same horizontal plane as bow obstruction light (33 CFR 67.05-1(d).
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Resolved 28 June 2018
Resolution: Examined/cleared by CG.
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 27 June 2018
Resolved
Each weather deck area where personnel may be employed must have 2 means of escape. Fire control plan indicates an escape that is blocked making escape nearly impossible (46 CFR 108.151(a)(3)).
Condition: Design Flaw
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 28 June 2018
Resolution: Examined/cleared by CG.