Records from 1997 to 2025. Most recent: inspection, 9 December 2025.
Inspection history · 69
9 December 2025
Annual Inspection
Physical examination · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 8281806
4 May 2025
Type not recorded
No type recorded · Sector Mobile · USCG Heartland District (CGD-H) · Activity 8130265
23 December 2024
COI Inspection · Administrative Inspection
Physical examination · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 8050257
31 August 2023
Annual Inspection
Physical examination · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 7789226
15 September 2022
Annual Inspection
Physical examination · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 7560242
20 June 2022
Administrative Inspection
Administrative · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 7482235
24 February 2022
Administrative Inspection
Administrative · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 7404738
23 July 2021
Annual Inspection · Administrative Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 7265319
4 May 2021
Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 7188875
18 August 2020
In-Service Inspection · Annual Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 7059358
13 July 2020
Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 7005268
15 January 2020
Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6894596
26 June 2019
Administrative Inspection
Administrative · USCG Heartland District · USCG Heartland District (CGD-H) · Activity 6726343
4 June 2019
COI Inspection
Physical examination · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 6697928
29 May 2019
Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6706891
18 May 2019
Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6706925
25 April 2019
Administrative Inspection
Administrative · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 6706525
1 August 2018
Administrative Inspection
Administrative · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 6550087
17 May 2018
Annual Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6416913
16 June 2017
Deficiency Check · Administrative Inspection · COI Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6180541
9 April 2017
Administrative Inspection
Administrative · USCG Heartland District · USCG Heartland District (CGD-H) · Activity 6120555
26 January 2017
Administrative Inspection
Administrative · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 6077574
13 October 2016
Construction Oversight · Administrative Inspection
Physical examination · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 6021898
28 July 2016
COI Inspection · Administrative Inspection
Physical examination · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 5955529
13 October 2015
Annual Inspection
Physical examination · USCG Heartland District · USCG Heartland District (CGD-H) · Activity 5741806
1 May 2012
Administrative Inspection · Internal Structural Exam · Underwater Inspection in lieu of Drydock
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 4506201
11 August 2011
Administrative Inspection · Construction Oversight · COI Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 4103157
4 February 2011
Construction Oversight · Plan Review (Other than "T")
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 3939155
2 September 2010
Annual Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 3833454
24 March 2010
Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 3726860
15 January 2010
Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 3666339
6 January 2010
Construction Oversight
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 3666942
18 December 2009
Construction Oversight
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 3760833
7 November 2008
Construction Oversight · Administrative Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 3362932
12 August 2008
Annual Inspection · Administrative Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 3296379
8 July 2008
Administrative Inspection · In-Service Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 3271794
12 April 2007
Hull Examination
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 2907221
17 January 2007
Administrative Inspection · In-Service Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 2857887
25 October 2006
In-Service Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 2815241
14 August 2006
COI Inspection · MTSA Verification
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 2747502
9 August 2005
Annual Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 2456189
11 April 2005
In-Service Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 2331321
8 September 2004
MTSA Verification
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 2189023
8 September 2004
Periodic Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 2233047
2 July 2004
Administrative Inspection
Administrative · MSO Mobile · USCG Heartland District (CGD-H) · Activity 2118873
17 September 2003
Annual Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1897452
9 August 2002
Annual Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1657804
18 April 2002
Internal Structural Exam · Hull Examination
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1606428
15 February 2002
Construction Oversight
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1486702
12 December 2001
Deficiency Check
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1077387
17 August 2001
COI Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1454974
23 April 2001
Type not recorded
No type recorded · MSO Mobile · USCG Heartland District (CGD-H) · Activity 105798
5 April 2001
Deficiency Check
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1062228
20 March 2001
Deficiency Check
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1060370
5 February 2001
Type not recorded
No type recorded · MSO Mobile · USCG Heartland District (CGD-H) · Activity 138359
18 January 2001
Construction Oversight · Deficiency Check
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1437834
3 October 2000
Re-Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1460471
1 August 2000
Type not recorded
No type recorded · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1053523
1 August 2000
Type not recorded
No type recorded · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1460470
14 February 2000
Type not recorded
No type recorded · MSO Mobile · USCG Heartland District (CGD-H) · Activity 169872
19 August 1999
COI Inspection · Hull Examination
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1462019
4 November 1998
Construction Oversight
Physical examination · Activities Europe · Activity 804451
4 February 1998
Construction Oversight
Physical examination · Activities Europe · Activity 774616
14 November 1997
Administrative
Administrative · Activities Europe · Activity 1123481
11 November 1997
Construction Oversight
Physical examination · Activities Europe · Activity 1121790
22 September 1997
Administrative
Administrative · Activities Europe · Activity 776229
27 August 1997
Construction Oversight
Physical examination · Activities Europe · Activity 1120170
6 March 1997
Construction Oversight
Physical examination · Activities Europe · Activity 1108789
29 January 1997
Initial Construction-Excluding Oversight
Physical examination · MSO Corpus Christi · USCG Heartland District (CGD-H) · Activity 1434639
07 - Fire Safety › N/A - No Subsystem › Fire pumps and its pipes
Issued 13 July 2020
Resolved
...All welds, pipe, and piping components shall be capable of complying with the limitations on imperfections specified in the product specification under which the pipe or component was purchased, or with the limitations on imperfections specified in 56.70-15(b). A visual examination found leaking piping spool on MARLIN TLP. Repair as new.
Provide a proposal within 30 days stating method of renewal and timeline for completion. At that time we will push the completion date of this CG-835 item as necessary speaking with ABS about coordination of the same.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 13 August 2020
Resolved 20 July 2020
Resolution: OIM statement received indicating NDE and system test sat.
Electrical › Electrical Distribution System (service) › Circuit Breaker
Issued 16 June 2017
Resolved
Elevator on the Northeast column failed
Condition: Improper/Lack of Maintenance
Due 16 July 2017
Resolved 19 July 2017
Resolution: Unit provided satisfactory evidence of repairs to elevator as well as a corrective action report to prevent future occurences of elevator failure.
Fire Fighting › Structural - A Class Divisions › Doors
Issued 16 June 2017
Resolved
doors in a corridor bulkhead in an accommodation spaces may not have a louver
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 31 October 2017
Resolved 4 December 2017
Resolution: Email from [name withheld] of Anadarko with photo's of doors and paperwork.
Engineering › Electric Propulsion System › Battery
Issued 16 June 2017
Resolved
480 MCC battery linen was not sufficient and did not maintained waterthightness
Condition: Improper/Lack of Maintenance
Due 16 July 2017
Resolved 13 July 2017
Resolution: Unit operator provided pictures of the corrected battery tray to the satisfaction of the marine inspector.
Lifesaving › Lifeboat › Self-contained Air Support System
Issued 15 October 2015
Resolved
Breathing air regulators in lifeboats 1 and 2 leaked. Repair to original condition.
Condition: Improper/Lack of Maintenance
Due 15 November 2015
Resolved 22 October 2015
Resolution: Received email that regulators have been replaced.
Lifesaving › Lifeboat › Embarkation/Disembarkation Capabilities
Issued 25 October 2006
Resolved
Replace bow hook assembly on # 1 lifeboat.
Condition: Unknown
Due 20 December 2006
Resolved 20 December 2006
Resolution: New lifeboat installed.
Lifesaving › Lifeboat › Fire Protection (water spray system)
Issued 14 August 2006
Resolved
Prove launching of all lifeboats showing water spray system working.
Condition: Unknown
Due 23 August 2006
Resolved 18 August 2006
Documentation › Certificates/Documents › Certificate of Financial Responsibility
Issued 8 September 2004
Resolved
Prove valid COFR certificate.
Due 10 October 2004
Resolved 24 October 2004
Lifesaving › Lifeboat › Self-contained Air Support System
Issued 8 September 2004
Resolved
Prove proper operation of breathing air system on lifeboat #2.
Due 10 October 2004
Resolved 24 September 2004
Fire Fighting › Fixed Pressure Water-Spraying Fire Extinguishing System
Issued 17 September 2003
Resolved
Prove proper start sequencing on NE column Deluge Diesel Pump. LEGACY COMPONENT DESC: Deluge Diesel Pump
Condition: Unknown
Action required: 705 - Other - as specified
Due 17 October 2003
Resolved 2 October 2003
Resolution: Received e-mail stating that the manual start solenoid and starter were replace and tested sat.
Navigation › Collision/Grounding Avoidance
Issued 17 September 2003
Resolved
Prove proper operation of Foghorn. LEGACY COMPONENT DESC: Foghorn
Condition: Unknown
Action required: 705 - Other - as specified
Due 27 September 2003
Resolved 22 September 2003
Resolution: Received e-mail stating that the foghorn had been repaired and tested sat.
Construction/Loadline › Hull › Hull Plating
Issued 19 July 2002
Resolved
Provide complete library of videos for underwater survey and written dive report to include all NDE certificates and credentials of NDE Techs.
Due 19 August 2002
Resolved 14 April 2005
Documentation
Issued 17 August 2001
Resolved
VESSEL IS TO REVISE AND POST AN ACCURATE MUSTER LIST (STATION BILL) INCLUDING LIFEBOAT ASSIGNMENTS, LIFEBOAT COMMAND ASSIGNMENTS AND KEY SUBSTITUTES (ORDER OF SUCCESSION) IN ACCORDANCE WITH 46 CFR 108.901.
Condition: Unknown
Due 17 August 2001
Resolved 17 August 2001
Fire Fighting
Issued 17 August 2001
Resolved
PROVIDE AND PROVE AMENDED PROCEDURE TO ENSURE THE CONTINUED OPERATIONAL ABILITY OF THE MARS TURBINE ENCLOSURES LOUVER SYSTEM.
Condition: Unknown
Due 17 August 2001
Resolved 17 August 2001
Fire Fighting
Issued 17 August 2001
Resolved
VESSEL IS TO PROVE PROPER OPERATION (SELF CLOSING, POSITIVE LATCHING) OF ALL FIRE DOORS THROUGHOUT THE ACCOMIDATION SPACES.
Condition: Unknown
Due 17 August 2001
Resolved 17 August 2001
Documentation
Issued 17 August 2001
Resolved
VESSEL IS TO DEVELOP AND IMPLEMENT A TRAINING SCHEME TO COMPLY WITH THE REQUIREMENTS FOUND IN 46 CFR 109.213 (a)-(h).
Condition: Unknown
Due 17 August 2001
Resolved 17 August 2001
Construction/Loadline
Issued 17 August 2001
Resolved
VESSEL MUST COMPLETE A DRYDOCK AND INTERNAL STRUCTURAL EXAM OF THE ENTIRE HULL OR COMPLETE THE FIRST THREE PHASES OF AN "APPROVED" IN SERVICE INSPECTION PLAN NOT LATER THAN THE ABOVE DUE DATE IN ACCORDANCE WITH 46 CFR107.265.
Condition: Unknown
Due 19 August 2002
Resolved 19 July 2002
Engineering
Issued 3 October 2000
Resolved
Free-up and/or replace faulty (sticking) fuel gas automated supply valves on each gas turbine generator set.
Condition: Unknown
Due 10 January 2001
Resolved 10 January 2001
Electrical
Issued 3 October 2000
Resolved
Make no. 1 lifeboat/rescue boat davit winch capable of operation from emergency generator switchboard.
Condition: Unknown
Due 3 October 2000
Resolved 3 October 2000
Electrical
Issued 3 October 2000
Resolved
Install light(s) on the Northeast column to illuminate the davit-launched liferaft installation. Light(s) must be on the emergency lighting circuit and must provide lighting for embarkation, launching and lowering all the way to water's edge.
Condition: Unknown
Due 3 October 2000
Resolved 3 October 2000
Documentation
Issued 3 October 2000
Resolved
Provide documentation of annual crane inspection/testing by ABS for ABS registered cranes iaw 46 CFR 107.259.
Condition: Unknown
Due 18 October 2000
Resolved 18 October 2000
Documentation
Issued 3 October 2000
Resolved
Submit to Commandant (MOC-3) via MSo New Orleans detailed plans for conducting the in-service inspection plan (ISIP) as equivalent to the drydocking and/or special examination in lieu of drydocking (SEILODD) required BY 46 CFR 107.261 and/or 107.265.
Condition: Unknown
Due 3 October 2000
Resolved 3 October 2000
Lifesaving
Issued 1 August 2000
Resolved
Remove plywood/fiberglass smoking shack or replace with shack constructed of non-combustible materials (steel).
Condition: Unknown
Due 18 October 2000
Resolved 18 October 2000
Fire Fighting
Issued 19 August 1999
Resolved
COKPLETE PIPING AND NOZZLE INSTALLATION ON DIESEL FUEL/METHANOL LOADING AREAS ON NORTH AND SOUTH SIDES OF PLATFORM.
Condition: Unknown
Due 19 August 1999
Resolved 19 August 1999
Lifesaving
Issued 19 August 1999
Resolved
DEVELOP AND INCORPORATE INTO PRACTICE A DRILL/TRAINING/INSTRUCTIONAL PROGRAM THAT MEETS THE INTENT OF 46 CFR 109.213.
Condition: Unknown
Due 19 August 1999
Resolved 19 August 1999
Electrical
Issued 29 January 1997
Resolved
INSTALL AND PROVE OPERATION OF ADDITIONAL EMERGENCY LIGHTS FOR NORTHWEST AND SOUTHWEST COLUMNS.
Condition: Unknown
Due 29 January 1997
Resolved 29 January 1997
Fire Fighting
Issued 29 January 1997
Resolved
PROVE OPERATION OF NORTHEAST AND SOUTHEAST FIRE MAIN DIESEL PUMPS LOCATED IN NORTHEAST AND SOUTHEAST COLUMNS AT THE 88' LEVEL.
Condition: Unknown
Due 29 January 1997
Resolved 29 January 1997
Lifesaving
Issued 29 January 1997
Resolved
PROVIDE CORRECT SMALL BOAT WINCH PLACARDS FOR INSTALLATION ON THREE SMALL BOAT DAVIT WINCHES. (AMOCO HAS PLACARDS ON ORDER)
Condition: Unknown
Due 29 January 1997
Resolved 29 January 1997
Fire Fighting
Issued 29 January 1997
Resolved
PROVE OPERATION OF COMBUSTIBLE GAS SENSOR LOCATED IN DIESEL/METHANOL ROOM PRIOR TO USE OF METHANOL FUEL.
Condition: Unknown
Due 26 June 1999
Resolved 16 July 1999
Fire Fighting
Issued 29 January 1997
Resolved
REMOVE TEMPORARY FIRE FOAM AND INSTALL PERMANENT FIRE STOPS FOR THE FOLLOWING BUILDINGS. EMERGENCY SWITCHGEAR BUILDING, INSTRUMENTATION BUILDING, SWGR/MCC BUILDING (FIRST & SECOND FLOOR).
Condition: Unknown
Due 29 January 1997
Resolved 29 January 1997
Engineering
Issued 29 January 1997
Resolved
PROVE OPERATION OF HELO FUEL SYSTEM PRIOR TO FUELING OPERATIONS.
Condition: Unknown
Due 26 June 1999
Resolved 16 July 1999