Records from 1998 to 2023. Most recent: inspection, 31 August 2023.
Inspection history · 56
31 August 2023
Drydock Exam
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 7776766
23 August 2023
In-Service Inspection
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 7775205
16 August 2022
Administrative Inspection · Annual Inspection
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 7535995
8 June 2022
Administrative Inspection · Drydock Exam
Physical examination · Sector Charleston · USCG Southeast District (CGD-SE) · Activity 7467633
25 February 2022
Simplified Stability Test
Physical examination · Marine Safety Center (MSC) · Activity 7411452
2 December 2021
Administrative Inspection · Simplified Stability Test
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 7361299
3 June 2021
Examination of Repairs · Deficiency Check · DAPI Audit · COI Inspection
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 7179339
20 October 2020
Type not recorded
No type recorded · Sector Charleston · USCG Southeast District (CGD-SE) · Activity 7084128
10 September 2020
Annual Inspection · Deficiency Check
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 7048647
30 March 2020
Hull Examination · Deficiency Check · Drydock Extension · Examination of Repairs · Drydock Exam · Administrative Inspection
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 6933147
10 September 2019
DAPI Audit · Annual Inspection
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 6790593
10 September 2018
DAPI Audit · Annual Inspection · Deficiency Check
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 6552683
5 March 2018
Internal Structural Exam · Hull Examination · Examination of Repairs · Deficiency Check
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 6364707
10 September 2017
Deficiency Check · Annual Inspection · DAPI Audit
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 6276210
25 July 2017
Type not recorded
No type recorded · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 6616218
8 June 2016
COI Inspection · DAPI Audit · Administrative Inspection
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 5901316
16 February 2016
Hull Examination
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 5819647
15 May 2014
DAPI Audit · Administrative Inspection · Annual Inspection
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 4991764
18 March 2014
Hull Examination · Administrative Inspection
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 4818829
11 July 2012
Simplified Stability Test
Physical examination · Sector Charleston · USCG Southeast District (CGD-SE) · Activity 4384376
21 May 2012
Annual Inspection · Administrative Inspection
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 4318483
23 March 2010
Administrative Inspection · Drydock Exam · Deficiency Check
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 3702659
31 July 2008
Type not recorded
No type recorded · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 3285136
21 April 2008
Simplified Stability Test
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 3191911
18 March 2008
Drydock Exam
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 3166893
17 March 2008
Annual Inspection
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 3247526
17 July 2007
Type not recorded
No type recorded · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 2997914
25 June 2007
Annual Inspection
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 2973386
30 May 2007
Administrative Inspection
Administrative · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 2946307
17 May 2006
COI Inspection
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 2651376
28 March 2006
Internal Structural Exam · Hull Examination
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 2610900
12 September 2005
Type not recorded
No type recorded · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 2490440
8 August 2005
Annual Inspection
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 2456055
26 October 2004
Type not recorded
No type recorded · MSO CHARLESTON · USCG Southeast District (CGD-SE) · Activity 2228740
20 October 2004
Type not recorded
No type recorded · MSO CHARLESTON · USCG Southeast District (CGD-SE) · Activity 2224831
20 October 2004
Annual Inspection · Deficiency Check
Physical examination · MSO CHARLESTON · USCG Southeast District (CGD-SE) · Activity 2225465
18 August 2004
Type not recorded
No type recorded · MSO CHARLESTON · USCG Southeast District (CGD-SE) · Activity 2228730
10 July 2004
Type not recorded
No type recorded · MSO CHARLESTON · USCG Southeast District (CGD-SE) · Activity 2128036
7 June 2004
Type not recorded
No type recorded · MSO CHARLESTON · USCG Southeast District (CGD-SE) · Activity 2091639
26 May 2004
Type not recorded
No type recorded · GROUP CHARLESTON · USCG Southeast District (CGD-SE) · Activity 2079237
4 May 2004
Type not recorded
No type recorded · GROUP CHARLESTON · USCG Southeast District (CGD-SE) · Activity 2059128
19 April 2004
Type not recorded
No type recorded · MSO CHARLESTON · USCG Southeast District (CGD-SE) · Activity 2047689
13 April 2004
Type not recorded
No type recorded · MSO CHARLESTON · USCG Southeast District (CGD-SE) · Activity 2043487
24 March 2004
Hull Examination
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 2030913
8 August 2003
Annual Inspection
Physical examination · MSO CHARLESTON · USCG Southeast District (CGD-SE) · Activity 1872914
29 March 2002
Annual Inspection · Hull Examination
Physical examination · MSO CHARLESTON · USCG Southeast District (CGD-SE) · Activity 1597661
16 May 2001
COI Inspection
Physical examination · MSO CHARLESTON · USCG Southeast District (CGD-SE) · Activity 1426591
27 June 2000
Re-Inspection
Physical examination · MSO CHARLESTON · USCG Southeast District (CGD-SE) · Activity 1413769
14 March 2000
Hull Examination
Physical examination · MSO CHARLESTON · USCG Southeast District (CGD-SE) · Activity 1457761
12 April 1999
Re-Inspection
Physical examination · MSO CHARLESTON · USCG Southeast District (CGD-SE) · Activity 1388786
16 November 1998
Administrative
Administrative · MSO TAMPA · USCG Southeast District (CGD-SE) · Activity 807071
23 June 1998
Type not recorded
No type recorded · MSO CHARLESTON · USCG Southeast District (CGD-SE) · Activity 225983
26 May 1998
Type not recorded
No type recorded · MSO CHARLESTON · USCG Southeast District (CGD-SE) · Activity 1126077
19 May 1998
Type not recorded
No type recorded · MSO MIAMI · USCG Southeast District (CGD-SE) · Activity 1126232
15 May 1998
Initial Certification · Hull Examination · Initial Construction-Excluding Oversight
Physical examination · MSO TAMPA · USCG Southeast District (CGD-SE) · Activity 1428991
30 January 1998
Plan Review "T" Boat
Administrative · MSO TAMPA · USCG Southeast District (CGD-SE) · Activity 1119937
02 - Structural Conditions › N/A - No Subsystem › Beams, frames, floors-op. damage
Issued 8 June 2022
Resolved
The construction and arrangement of a vessel must allow the safe operation of the vessing in accordance with the terms of its COI, giving consideration to provisions for necessary facilities for passendgers and crew. The deck for the bathroom has wasted decking as well as various handrails have cracked welds. All repairs to be made at the next dry dock in 2023
Action required: 705 - Other - as specified
Resolved 1 November 2023
Resolution: Vessel missed its COI examination and the COI was deactivated. Will have to undergo a full COI and Drydock examination prior to coming back into passenger service.
10 - Safety of Navigation › N/A - No Subsystem › Lights, shapes, sound-signals
Issued 3 June 2021
Resolved
Vessel required to be equipped with navigational lights. Vessel is not equipped with required navigation lights (mast light) (RULE 23).
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 3 July 2021
Resolved 6 September 2021
10 - Safety of Navigation › N/A - No Subsystem › Charts
Issued 3 June 2021
Resolved
Vessel required to carry current/up to date marine charts for areas transited. Exsiting marine charts were outdated.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 3 July 2021
Resolved 6 September 2021
10 - Safety of Navigation › N/A - No Subsystem › Nautical publications
Issued 3 June 2021
Resolved
Vessel required to carry current/up to date navigational publications for areas transited. Existing tidal tables were outdated.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 3 July 2021
Resolved 6 September 2021
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 3 June 2021
Resolved
Vessel required to be equipped with a suitable steering system/arrangement. Existing tie bar end links were found worn requiring replacement.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 3 July 2021
Resolved 6 September 2021
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 3 June 2021
Resolved
Vessel required to be equipped with suitable steering system/arrangement. Existing flexible hydraulic steering lines were found "crimped".
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 3 July 2021
Resolved 6 September 2021
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 3 June 2021
Resolved
Vessels batteries are required to be secured to prevent movement. Existing battery boxes were found deteriorated/rotted.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 3 July 2021
Resolved 6 September 2021
11 - Life Saving Appliances › N/A - No Subsystem › Distress flares
Issued 3 June 2021
Resolved
Vessels visual distress signals are required to be stowed in a portable watertight container. Existing portable container is not watertight and is corroded/wasted.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 3 July 2021
Resolved 6 September 2021
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 3 June 2021
Resolved
Vessels electrical conductors are required to terminate inside of an enclosure. Dead ended wiring was noted in way of operators console.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 3 July 2021
Resolved 6 September 2021
01 - Certificates & Documentation › 011 - Ships Certificates › USCG Certificate of Documentation (COD)
Issued 10 September 2020
Resolved
Vessels hailing port is required to be marked on some clearly visible exterior part of the stern of the vessel. Vessels existing hailing port does not match that of the Certificate of Documentation.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 10 October 2020
Resolved 6 September 2021
Resolution: superceded
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 10 September 2020
Resolved
Fuses must be of the cartridge type only and be listed by Underwriters Laboratories or another independent laboratory recognized by the Commandant. Existing fuse holder IWO electrical cabinet is improper type (blade style).
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 10 October 2020
Resolved 3 June 2021
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 10 September 2020
Resolved
Vessel required to carry a serviceable ring life buoy on board. Existing ring life buoy's peripheral grab line was frayed/damaged by UV.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 24 September 2020
Resolved 16 April 2021
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 10 September 2020
Resolved
Batteries in lifesaving appliances shall be renewed annually. Battery in way of floating water light for ring life buoy required annual replacement.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 24 September 2020
Resolved 16 April 2021
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 10 September 2020
Resolved
Vessel required to post emegency instructions on board IAW 46 CFR 185.512. Existing emergency instructions are incomplete and are not in compliance with 46 CFR 185.512.
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 24 September 2020
Resolved 16 April 2021
14 - Pollution Prevention › 144 - MARPOL Annex IV (Not Applicable to PSC Exams conducted in the U.S.) › Other (MARPOL Annex IV)
Issued 10 September 2020
Resolved
Vessels with installed toilets shall have operating instructions posted. Vessel is equipped with an installed Type III MSD system. Existing system has incomplete operating instructions.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 10 October 2020
Resolved 16 April 2021
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 10 September 2020
Resolved
[withheld — contains personal information; the deficiency system, dates, and resolution status are shown above]
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 24 September 2020
Resolved 16 April 2021
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 10 September 2020
Resolved
A seat must be constructed to minimize the possibility of injury and avoid trapping occupants. Existing seating hardware found loose in way of Row 1 (port) and Row 3 (starboard).
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 24 September 2020
Resolved 3 June 2021
10 - Safety of Navigation › N/A - No Subsystem › Lights, shapes, sound-signals
Issued 10 September 2020
Resolved
Vessel required to be equipped with proper sound signals (bell). Existing sound signal (bell) missing striker.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 25 September 2020
Resolved 16 April 2021
02 - Structural Conditions › N/A - No Subsystem › Hull - cracking
Issued 18 May 2020
Resolved
During drydock inspection, all accessible parts of the vessels underwater body and all through hull fittings shall be made available for inspection. Fractured FRP noted IWO starboard transom (@ engine mounting location).
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 22 May 2020
Resolution: Attending Inspector verified repairs made to starboard transom.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 18 May 2020
Resolved
During drydock inspection, all accessible parts of the vessels underwater body and all through hull fittings shall be made available for inspection. Fractured securing devices noted IWO centerline deck structure (below main deck) for electrical conductors.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 1 June 2020
Resolved 22 May 2020
Resolution: Attending Inspector verified renewal of clamps for electrical conductors.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 18 May 2020
Resolved
During drydock inspection, all accessible parts of the vessels underwater body and all through hull fittings shall be made available for inspection. Delamination of FRP overlay IWO starboard bow.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 1 June 2020
Resolved 22 May 2020
Resolution: Attending Inspector verified repairs made IWO starboard bow.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 18 May 2020
Resolved
An internal structural examination may be conducted while the vessel is out of the water. Attending Inspector(s) identified wasted mechanical clamps IWO electric bilge pump discharge flexible hose/piping.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 1 June 2020
Resolved 22 May 2020
Resolution: Attending Inspector verified renewal of hose clamps IWO electric submersible bilge pumps.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 10 September 2018
Resolved
Ring life buoy required to be marked with retro-reflective markings/tape. Vessels ring life buoy was missing required retro-reflective markings.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 10 October 2018
Resolved 28 November 2018
Resolution: Attending Inspector verified retro-reflective markings for ring life buoy.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 10 September 2018
Resolved
Vessel required to carry suitable first aid kit for service engaged in. Attending Inspectors identified expired items in first aid kit.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 10 October 2018
Resolved 28 November 2018
Resolution: Attending Inspector verified renewal of expired items in first aid kit.
01 - Certificates & Documentation › 011 - Ships Certificates › USCG Certificate of Documentation (COD)
Issued 10 September 2018
Resolved
Vessel is required to be documented. Vessel is not equipped with a valid Certificate of Documentation. Vessels hailing port does not match Certificate of Documentation.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 10 October 2018
Resolved 10 September 2019
Resolution: Attending Inspector verified carriage/validity of vessel Certificate of Documentation.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 10 September 2018
Resolved
Vessel required to carry Type I PFD's for each person on board properly sized. Vessel was missing two Type I adult PFD's.
Action required: 701 - Prior to carriage of passengers/cargo
Due 10 September 2018
Resolved 28 November 2018
Resolution: Attending Inspector verified the carriage of proper qty of Type I PFD's (adult).
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 10 September 2018
Resolved
PFD stowage locations are required to be marked with size/qty. One of the vessels stowage locations was not properly marked with size/qty of Type I PFD's.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 10 October 2018
Resolved 28 November 2018
Resolution: Attending Inspector verified renewal of PFD stowage markings.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 10 September 2018
Resolved
Attending Inspector(s) identified fractured weldments IWO bow doors, port & starboard.
Condition: Damaged By Earlier Event
Action required: 705 - Other - as specified
Due 31 December 2018
Resolved 2 February 2019
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 10 September 2018
Resolved
Vessel required to be equipped with bilge piping system. Vessels bilge discharge piping IWO starboard void #2 was found leaking during operational testings.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 10 October 2018
Resolved 28 November 2018
Resolution: Attending Inspector verified repairs made to electric submersible bilge piping hoses/connections.
04 - Emergency Systems › N/A - No Subsystem › Emergency, lighting, batteries and switches
Issued 10 September 2018
Resolved
Vessel's emergency lighting was found extinguished during operatonal testing.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 10 October 2018
Resolved 28 November 2018
Resolution: Attending Inspector verified operation of main deck lighting.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 10 September 2018
Resolved
Gouges noted IWO port quarter gel coat/FRP IWO side shell & transom.
Condition: Damaged By Earlier Event
Action required: 705 - Other - as specified
Due 31 December 2018
Resolved 2 February 2019
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 10 September 2018
Resolved
Attending Inspector(s) identified delamination of FRP IWO starboard transom @ outboard motor mountings.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 31 December 2018
Resolved 2 February 2019
Construction/Loadline › Hull › Bottom Plating
Issued 5 March 2018
Resolved
Grind existing FRP overlay from port & starboard sponsons due to deterioration/wear.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 31 March 2018
Resolved 28 March 2018
Resolution: Attending Inspector(s) verified repairs made IWO FRP overlay for port/starboard sponsons.
Construction/Loadline › Hull › Hull Plating
Issued 5 March 2018
Resolved
Grind/fill existing chips/gouges in FRP IWO port & starboard sponsons (where marked by attending Inspector)
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 31 March 2018
Resolved 28 March 2018
Resolution: Attemding Inspector(s) verified repairs made IWO gel coat throughout vessels hull (where marked).
Construction/Loadline › Hull › Hull Plating
Issued 5 March 2018
Resolved
Effect repairs IWO port quarter sponson.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 31 March 2018
Resolved 28 March 2018
Resolution: Attending Inspector(s) verified repairs made IWO port quarter sponson.
Electrical › Electrical Distribution System (service) › Wiring
Issued 5 March 2018
Resolved
Properly secure electrical conductors beneath main deck (centerline).
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 31 March 2018
Resolved 28 March 2018
Resolution: Attending Inspector(s) verified installation of securing devices for cableways/conductors along the bottom of the main deck.
Engineering › Bilge Water Management System › Pump
Issued 5 March 2018
Resolved
Repair/replace existing electric submersible bilge pump IWO starboard Void #2.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 28 March 2018
Resolution: Attending Inspector(s) verified repairs made to electric submersible bilge pump IWO Starboard Void #2.
Documentation › Certificates/Documents › FCC SSL
Issued 10 September 2017
Resolved
[withheld — contains personal information; the deficiency system, dates, and resolution status are shown above]
Action required: 705 - Other - as specified
Due 10 October 2017
Resolved 31 October 2017
Communications › Radio Communications › VHF Radiotelephone
Issued 10 September 2017
Resolved
VHF-FM radiotelephone is not properly programmed with MMSI # (DSC equipped).
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 10 October 2017
Resolved 31 October 2017
Documentation › Certificates/Documents › Proof of Consortium Enrollment (DAPI)
Issued 10 September 2017
Resolved
Vessels owner/operator could not produce proof of enrollment letter form consortium.
Action required: 705 - Other - as specified
Due 10 October 2017
Resolved 26 October 2017
Resolution: Attending Inspector(s) verified enrollment into an approved drug/alcohol testing consortium.
Operations/Management › Drug and Alcohol Testing › EAP Display Requirements
Issued 10 September 2017
Resolved
Vessels does not carry/post EAP (policy) on board.
Action required: 705 - Other - as specified
Due 10 October 2017
Resolved 31 October 2017
Documentation › Manuals/Policy Documentation › Emergency Instructions
Issued 10 September 2017
Resolved
Vessel does not carry/post emergency instructions.
Action required: 705 - Other - as specified
Due 10 October 2017
Resolved 31 October 2017
Navigation › Piloting/Steering › US Coast Pilot
Issued 10 September 2017
Resolved
Vessels navigation publications were out of date.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 10 October 2017
Resolved 31 October 2017
Navigation › Piloting/Steering › Marine Charts
Issued 10 September 2017
Resolved
Vessels marine charts for areas transited were out of date.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 10 October 2017
Resolved 26 October 2017
Resolution: Attending Inspector(s) verified carriage of current/up to date marine charts for areas transited.
Lifesaving › Lifebuoys › Serviceable
Issued 10 September 2017
Resolved
Vessels ring buoy required replacement due to UV damage to outer covering.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 10 October 2017
Resolved 26 October 2017
Resolution: Attending Inspector(s) verified replacement of ring life buoy.
Accommodation/Occupational Safety › Medical/First Aid › Medicine Chest
Issued 10 September 2017
Resolved
Expired items were identified in First Aid Kit.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 10 October 2017
Resolved 26 October 2017
Resolution: Attending Inspector(s) verified renewal of expired items in first aid kit.
Fire Fighting › Remote Fuel Shutoff › General
Issued 10 September 2017
Resolved
Vessels emergency fuel shut off piping/valves were found "loose" (required repair/replacement).
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 10 October 2017
Resolved 26 October 2017
Resolution: Attending Inspector(s) verified repairs made to emergency fuel shut off valves/piping.
Construction/Loadline › Hull › Bottom Plating
Issued 23 March 2010
Resolved
Repair hull fiberglass on both hulls IWO the fwd strakes where the vessel is beached to unload passengers. Fiberglass doubler reinforcement that was put in place is worn.
Action required: 705 - Other - as specified
Resolved 24 March 2010
Construction/Loadline › Structures › Manhole
Issued 23 March 2010
Resolved
Repair fiberglass IWO stbd aft access plate fwd of the stbd outboard engine.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 1 April 2010
Resolution: Fiberglass fixed and glassed
Engineering › Shafting/Propeller Arrangements › Propeller (fixed pitch)
Issued 23 March 2010
Resolved
Replace both propellers.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 18 May 2010
Construction/Loadline › Structures › Superstructure
Issued 23 March 2010
Resolved
Repair or replace worn stanchion on canopy as marked.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 1 April 2010
Resolution: Repaired stantion on canopy
Fire Fighting › Remote Fuel Shutoff › General
Issued 23 March 2010
Resolved
Replace both fuel shut-off valves
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 1 April 2010
Resolution: Replaced both shut-offs
Engineering › Fuel Oil Storage/Transfer System › Piping
Issued 23 March 2010
Resolved
Tighten fuel piping connections at both fuel tanks.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 1 April 2010
Resolution: Piping cnnections fixed and replaced
Construction/Loadline › Structures › Superstructure
Issued 23 March 2010
Resolved
Repair broken welds on canopy as marked.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 1 April 2010
Resolution: Welds fixed
Personnel › Certificates/Documents/Licenses › License, Master
Issued 31 July 2008
Resolved
During random boarding vsl master did not have his license available for inspection.
Condition: Unknown
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 17 August 2009
Engineering › Gasoline Engine (propulsion) › Connecting Rod (4 cycle)
Issued 18 March 2008
Resolved
Tighten stbd side engine mount bolt.
Condition: Unknown
Action required: 705 - Other - as specified
Resolved 19 March 2008
Resolution: Tightened loose bolt.
Accommodation/Occupational Safety › Occupational Safety › Deck Rail
Issued 18 March 2008
Resolved
Repair all welds on port and stbd railings.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 19 March 2008
Resolution: New welds.
Accommodation/Occupational Safety › Occupational Safety › Deck Rail
Issued 18 March 2008
Resolved
Tighten Stbd side forward railing.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 19 March 2008
Resolution: Tightened railing.
Construction/Loadline › Hull › Bottom Plating
Issued 18 March 2008
Resolved
Repair patches on forward of both pontoons.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 19 March 2008
Resolution: Put new FRP patches on pontoons.
Engineering › Steering Gear System › Pin
Issued 18 March 2008
Resolved
Replace rusted bolt on port engine ram.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 19 March 2008
Resolution: Installed new bolt.
Documentation › Markings/Placards › Lifejacket Placard
Issued 25 June 2007
Resolved
Provide donning placard
Condition: Unknown
Due 3 July 2007
Resolved 3 July 2007
Resolution: New placards posted
Lifesaving › Lifejacket/PFD (General) › Storage
Issued 25 June 2007
Resolved
Stencil PFD stowage areas.
Condition: Unknown
Due 3 July 2007
Resolved 3 July 2007
Lifesaving › Lifejacket/PFD (General) › Quantity
Issued 25 June 2007
Resolved
Provide 04 PFD's
Condition: Unknown
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 25 June 2007
Resolution: New PFDs provided
Fire Fighting › Means of Escape › Escape Route Signs
Issued 25 June 2007
Resolved
Re-stencil stbd. emg exit sign
Condition: Improper/Lack of Maintenance
Due 3 July 2007
Resolved 3 July 2007
Lifesaving › Hand Flares › Storage
Issued 25 June 2007
Resolved
Stencil flare and first aid kit storage.
Condition: Placed in Improper Service
Due 3 July 2007
Resolved 3 July 2007
Lifesaving › Hand Flares › Storage
Issued 25 June 2007
Resolved
Stencil flare box "distress flares"
Condition: Unknown
Due 3 July 2007
Resolved 3 July 2007
Documentation › Certificates/Documents › Certificate of Documentation (CG-1270)
Issued 25 June 2007
Resolved
Provide valid C.O.D.
Condition: Unknown
Due 3 July 2007
Resolved 5 July 2007
Engineering › Steering Gear System › Pin
Issued 25 June 2007
Resolved
Provide new bolt for port side steering linkage & invert all other bolts on steering assembly.
Condition: Improper/Lack of Maintenance
Due 3 July 2007
Resolved 3 July 2007
Fire Fighting › Miscellaneous Items › Waste Receptacles
Issued 17 May 2006
Resolved
Provide non-combustible trash can or liner
Condition: Unknown
Due 17 June 2006
Resolved 1 June 2006
Resolution: Metal trash can provided.
Operations/Management › Drills/Instruction › Making Voice Radio Distress Call
Issued 17 May 2006
Resolved
Provide emergency radio broadcast placard
Condition: Unknown
Due 17 June 2006
Resolved 1 June 2006
Resolution: Emergency instruction provided.
Construction/Loadline › Hull › Bottom Plating
Issued 28 March 2006
Resolved
Repair port/stbd forward areas noted by inspectors to original hull design
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 28 March 2006
Resolution: O/O repaired hull with new glass work
Accommodation/Occupational Safety › Occupational Safety › Deck Rail
Issued 28 March 2006
Resolved
Repair port side fore and aft railings.
Condition: Damaged By Earlier Event
Action required: 705 - Other - as specified
Resolved 28 March 2006
Resolution: O/O repaired handrails
Electrical › Lighting (emergency) › Lighting Fixture
Issued 8 August 2005
Resolved
Repair emergency lighting.
Condition: Improper/Lack of Maintenance
Due 22 August 2005
Resolved 16 August 2005
Resolution: Properly installed lighting.
Electrical › Lighting (emergency) › Battery Operated Lantern
Issued 8 August 2005
Resolved
Provide 2 means of portable lighting.
Condition: Improper Installation
Due 22 August 2005
Resolved 16 August 2005
Resolution: 2 flashlights on board.
Documentation › Markings/Placards › Warning Signs
Issued 8 August 2005
Resolved
Properly mark exits "emergency exit, keep clear"
Condition: Improper Installation
Due 22 August 2005
Resolved 16 August 2005
Resolution: Exits marked.
Engineering › Gasoline Engine (propulsion) › Crankshaft (4 cycle)
Issued 8 August 2005
Resolved
Repair/Replace stbd. engine.
Condition: Unknown
Due 15 August 2005
Resolved 16 August 2005
Resolution: Engine repaired.
Pollution Prevention/Response › Response Equipment › Non-sparking Portable Pump/Hoses
Issued 8 August 2005
Resolved
Provide acceptable portable bilge pump.
Condition: Improper Installation
Due 22 August 2005
Resolved 8 August 2005
Resolution: Provide acceptable portable pump.
Documentation › Markings/Placards › Lifejacket Placard
Issued 8 August 2005
Resolved
Provide more PFD donning placards.
Condition: Improper Installation
Due 22 August 2005
Resolved 16 August 2005
Resolution: Placards have been posted.
Lifesaving › Lifejacket/PFD (General) › Quantity
Issued 8 August 2005
Resolved
Provide 4 Adult PFD's.
Condition: Damaged By Earlier Event
Due 22 August 2005
Resolved 16 August 2005
Resolution: Purchased 4 pfd''s
Documentation › Certificates/Documents › FCC SSL
Issued 8 August 2005
Resolved
Provide FCC license.
Condition: Improper Installation
Due 22 August 2005
Resolved 16 August 2005
Resolution: Obtained license.
Operations/Management › Drills/Instruction › Man Overboard Recovery
Issued 8 August 2005
Resolved
Conduct satisfactory man overboard drill.
Condition: Unknown
Due 15 August 2005
Resolved 16 August 2005
Resolution: Drill Sat.
Operations/Management › Drills/Instruction › Making Voice Radio Distress Call
Issued 8 August 2005
Resolved
Provide Emergency broadcast placard.
Condition: Placed in Improper Service
Due 22 August 2005
Resolved 8 August 2005
Resolution: Replace placard.
Lifesaving › Lifejacket/PFD (Type I) › Condition
Issued 20 October 2004
Resolved
31 Adult PFD's found in unsatisfactory condition ( dry rot, wear, etc)
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 25 October 2004
Resolution: Replaced 31 PFD''''s
Lifesaving › Lifebuoys › Serviceable
Issued 20 October 2004
Resolved
lifering found in unsatisfactory condition (outer cover wasted, exposing internal material)
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 4 November 2004
Resolved 25 October 2004
Resolution: Replaced unsatisfactory lifering with new lifering.
Lifesaving › Hand Flares › Storage
Issued 20 October 2004
Resolved
Distress signal storage container not properly marked.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 4 November 2004
Resolved 25 October 2004
Resolution: Distress signal storage container properly marked.
Documentation › Certificates/Documents › Certificate of Documentation (CG-1270)
Issued 20 October 2004
Resolved
Original Certificate of Documentation for vessel not available for inspection.
Condition: Improper Installation
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 25 October 2004
Resolution: Original COD placed on vessel
Navigation › Piloting/Steering › Magnetic Compass
Issued 20 October 2004
Resolved
Magnetic compass unable to be illuminated during night operations.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 4 November 2004
Resolved 25 October 2004
Resolution: Corrected
Accommodation/Occupational Safety › Other Accommodation Spaces › Open Deck Space
Issued 20 October 2004
Resolved
Four passenger benches found not to be properly secured to deck. (screws missing)
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 4 November 2004
Resolved 25 October 2004
Resolution: Secured all benches to the deck.
Engineering › Gasoline Engine (propulsion) › Fuel Intake (2 stroke)
Issued 20 October 2004
Resolved
STBD fuel line to outboard engine cracked and wasted.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 4 November 2004
Resolved 25 October 2004
Resolution: Replaced fuel hose on STBD engine.
Engineering › Bilge Water Management System › Not Operational
Issued 20 October 2004
Resolved
Bilge hand pumping system for port and stbd sides are inoperable.
Condition: Unknown
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 25 October 2004
Resolution: Owner installed check valve at the bottom of each pipe allowing suction to be drawn to the satisfaction of attending marine inspector.
Accommodation/Occupational Safety › Medical/First Aid › Medicine Chest
Issued 20 October 2004
Resolved
Entire contents of First Aid kit were expired.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 4 November 2004
Resolved 25 October 2004
Resolution: Replaced First Aid Kit with new materials.
Fire Fighting › Remote Fuel Shutoff › General
Issued 20 October 2004
Resolved
Remote Fuel Shutoff markings not in a conspiquous area visable by crew and passengers.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 4 November 2004
Resolved 25 October 2004
Resolution: Remote fuel shutoff moved to a more conspiquous area.
Construction/Loadline › Hull
Issued 24 March 2004
Resolved
See narrative.
Action required: 705 - Other - as specified
Resolved 31 March 2004
Resolution: Glassed area ivo port outboard engine - all sat.
Engineering › Gasoline Engine (propulsion)
Issued 24 March 2004
Resolved
See narrative.
Action required: 705 - Other - as specified
Resolved 31 March 2004
Resolution: Removed 130hp outboard and installed 90hp IAW COI.
Construction/Loadline › Structures
Issued 24 March 2004
Resolved
See narrative.
Action required: 705 - Other - as specified
Resolved 31 March 2004
Resolution: Welded crack in hand rail ivo fwd stbd top rail.
Engineering › Bilge Water Management System
Issued 8 August 2003
Resolved
replace foundation bolts on both bilge pumps LEGACY COMPONENT DESC: Pump
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 4 September 2003
Resolved 5 September 2003
Resolution: corrected sat
Accommodation/Occupational Safety › Other Accommodation Spaces
Issued 8 August 2003
Resolved
Properly secure forward starboard bench seat to deck LEGACY COMPONENT DESC: Open Deck Space
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 4 September 2003
Resolved 5 September 2003
Resolution: corrected sat
Engineering › Fuel Oil Storage/Transfer System
Issued 8 August 2003
Resolved
Provide flame screen for fuel tank LEGACY COMPONENT DESC: Ventilation
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 22 August 2003
Resolved 8 August 2003
Resolution: flame screen provided
Engineering › Fuel Oil Service System
Issued 8 August 2003
Resolved
Replace port and starboard fuel shut off valves on fuel tank LEGACY COMPONENT DESC: Valve
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 4 September 2003
Resolved 5 September 2003
Resolution: corrected sat
Engineering › Fuel Oil Service System
Issued 8 August 2003
Resolved
properly label fuel shut off valves
Action required: 705 - Other - as specified
Due 4 September 2003
Resolved 5 September 2003
Resolution: corrected sat
Engineering › Fuel Oil Service System
Issued 8 August 2003
Resolved
Run fuel supply line for port engine so it goes through filter LEGACY COMPONENT DESC: Filter
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 4 September 2003
Resolved 5 September 2003
Resolution: corrected sat
Lifesaving › Lifebuoys
Issued 8 August 2003
Resolved
Replace lifering hand line LEGACY COMPONENT DESC: Buoyant Lifeline
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 4 September 2003
Resolved 5 September 2003
Resolution: corrected sat
Electrical › Electric Supply System (service)
Issued 8 August 2003
Resolved
Provide battery box covers LEGACY COMPONENT DESC: Battery Installation
Condition: Unknown
Action required: 705 - Other - as specified
Due 4 September 2003
Resolved 5 September 2003
Resolution: corrected sat
Navigation › Piloting/Steering
Issued 8 August 2003
Resolved
Provide proper navigation publications LEGACY COMPONENT DESC: US Coast Pilot
Condition: Unknown
Action required: 705 - Other - as specified
Due 4 September 2003
Resolved 5 September 2003
Resolution: corrected sat
Lifesaving › Lifejacket/PFD (General)
Issued 8 August 2003
Resolved
Remove "lifejacket" stensiling from unused lifejacket stowage box LEGACY COMPONENT DESC: Marking
Action required: 705 - Other - as specified
Due 4 September 2003
Resolved 5 September 2003
Resolution: corrected sat
Lifesaving › Lifejacket/PFD (Type I)
Issued 8 August 2003
Resolved
Provide three (3) more child sized lifejackets. Number of child passengers is limited to number of available appropriate PFD's. LEGACY COMPONENT DESC: Quantity
Condition: Unknown
Action required: 705 - Other - as specified
Due 4 September 2003
Resolved 5 September 2003
Resolution: corrected sat
Accommodation/Occupational Safety › Occupational Safety
Issued 8 August 2003
Resolved
Repair cracked weld in top portion of hand rail on the starboard forward corner of vessel, to be repaired at next drydock. LEGACY COMPONENT DESC: Deck Rail
Condition: Unknown
Action required: 705 - Other - as specified
Due 4 September 2003
Resolved 5 September 2003
Resolution: corrected sat
Lifesaving › Lifejacket/PFD (Type I)
Issued 29 March 2002
Resolved
Properly replace fifty-one adult PFD's. LEGACY COMPONENT DESC: Condition
Action required: 705 - Other - as specified
Due 2 April 2002
Resolved 2 April 2002
Resolution: Owner purchased fifty-one new PFD''''s with proper lableing and retro.
Construction/Loadline › Hull
Issued 29 March 2002
Resolved
Properly repair starboard forward pontoon in way of outer shell and bend. LEGACY COMPONENT DESC: Bottom Plating
Action required: 705 - Other - as specified
Due 2 April 2002
Resolved 2 April 2002
Resolution: Owner properly conducted proper repair and scarfed in a 9" x 9" firberglass patch.
Engineering
Issued 14 March 2000
Resolved
Unknown Component - Unknown Cause/Condition
Condition: Unknown
Due 1 April 2000
Resolved 29 March 2000
Engineering
Issued 14 March 2000
Resolved
Unknown Component - Unknown Cause/Condition
Condition: Unknown
Due 1 April 2000
Resolved 29 March 2000
Documentation
Issued 12 April 1999
Resolved
Obtain CPR/First Aid certification for at least 50 percent of crew
Condition: Unknown
Due 19 April 1999
Resolved 21 April 1999
Documentation
Issued 12 April 1999
Resolved
Obtain current copies of Tide Tables, Coast Pilot O/B.
Condition: Unknown
Due 19 April 1999
Resolved 21 April 1999