DISNEY MAGIC

DISNEY MAGIC is a 1998 passenger vessel (inspected). The Coast Guard has recorded 142 inspections since 1998, most recently in April 2026, along with 65 deficiencies and 19 operational controls.

Records from 1998 to 2026. Most recent: inspection, 3 April 2026.

Built
1998
Last inspected
3 April 2026
Documentation
Not in the documentation file of 10 September 2026
Controls
None recorded without a removal date

Identity

9126807 View on MarineTraffic leaves Maury; a third-party site, nothing from it is stored here
470968
Flag
BELIZE
—
Maury page id
psix-470968

Inspections, by type

…with no type recorded49
Years with a record 28 calendar years (1998–2026)
The 142 inspections in the strip above, split by the kind of activity the US Coast Guard recorded. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Coast Guard record current through 13 September 2026, retrieved 18 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Passenger Ship class in Maury's sources begin in 1977.

Documentation record

Tonnage as PSIX records it83969 - Convention (Subpart B), Gross Ton
59476 - Convention (Subpart B), Net Ton
7411 - Dead Weight, Ton
44438 - Displacement, Ton
This hull's Official Number is not in the NVDC file dated 10 September 2026 as served by NOAA Fisheries, so no documentation record is shown. Absence from that file is a fact about the file, not about the hull.

Radio station licence

No FCC ship-station licence is recorded against this Official Number in the file of 6 September 2026. That is a fact about the licence file, not about the radio.

Inspected as a tow unit · 2

The Coast Guard recorded this vessel and the following in the same inspection activity — normally a tug and the barges in its tow. A recreational or unclassed hull in the same activity is held and not published, so it does not appear here: these lists are a floor, not a complete manifest.

VIRGIN BREEZE Passenger (Inspected) · MISLE 718298 · 2 February 2012 · activity 4239933B-15 Freight Barge · MISLE 53621 · 27 July 2008 · activity 3282259

Inspection history · 142

3 April 2026 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 8341657
6 March 2026 COC-CVE Annual · PSC A
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 8314348
27 December 2025 Type not recorded
No type recorded · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 8287632
24 October 2025 Deficiency Check
Physical examination · Sector San Juan · USCG Southeast District (CGD-SE) · Activity 8258137
14 September 2025 PSC A · COC-CVE Annual
Physical examination · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 8233112
4 June 2025 In-Service Inspection
Physical examination · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 8151673
10 March 2025 COC-CVE Quarterly · PSC B
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 8091362
26 November 2024 Deficiency Check
Physical examination · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 8040320
12 October 2024 In-Service Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 8018188
20 September 2024 PSC A · COC-CVE Annual
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 8004847
25 March 2024 COC-CVE Quarterly · PSC B
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 7882871
12 January 2024 Bulk Liquid Transfer Monitor
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 7848861
25 September 2023 COC-CVE Annual · PSC A
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 7796397
26 July 2023 Exemption · Administrative Inspection
Administrative · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 7775290
20 May 2023 COC-CVE Quarterly · Ballast Water Examination · PSC B
Physical examination · Sector San Juan · USCG Southeast District (CGD-SE) · Activity 7691528
17 March 2023 Damage Survey
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 7652457
16 October 2022 PSC A · COC-CVE Annual
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 7577242
5 October 2022 Type not recorded
No type recorded · Sector New York · USCG Northeast District (CGD-NE) · Activity 7572990
11 April 2022 COC-CVE Quarterly · Ballast Water Examination · PSC B
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 7427268
10 March 2022 Administrative Inspection
Administrative · Sector Miami · USCG Southeast District (CGD-SE) · Activity 7409969
8 November 2021 Administrative Inspection
Administrative · Sector Miami · USCG Southeast District (CGD-SE) · Activity 7347225
16 October 2021 PSC A · In-Service Inspection · COC-CVE Annual
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 7332356
6 April 2020 In-Service Inspection
Physical examination · USCG Southeast District (dp) · USCG Southeast District (CGD-SE) · Activity 6935899
2 October 2019 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6832019
30 September 2019 ISPS II Exam · COC-CVE Annual · Ballast Water Examination
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 6824173
28 March 2019 Type not recorded
No type recorded · Sector Key West · USCG Southeast District (CGD-SE) · Activity 6673623
26 March 2019 COC-CVE Quarterly · Ballast Water Examination · ISPS III Exam
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 6649747
31 January 2019 Type not recorded
No type recorded · Sector Miami · USCG Southeast District (CGD-SE) · Activity 6617825
7 November 2018 In-Service Inspection
Physical examination · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 6577491
4 October 2018 ISPS II Exam · Ballast Water Examination · COC-CVE Annual
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 6550481
11 April 2018 Type not recorded
No type recorded · Sector Miami · USCG Southeast District (CGD-SE) · Activity 6389622
14 March 2018 Ballast Water Examination · Deficiency Check · COC-CVE Quarterly · ISPS III Exam
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 6370398
30 December 2017 Type not recorded
No type recorded · Sector Key West · USCG Southeast District (CGD-SE) · Activity 6370969
6 December 2017 Administrative Inspection
Administrative · Sector Key West · USCG Southeast District (CGD-SE) · Activity 6321126
2 October 2017 COC-CVE Annual · Ballast Water Examination · ISPS II Exam
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 6278114
4 April 2017 COC-CVE Quarterly · Ballast Water Examination · ISPS II Exam
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 6117537
17 March 2017 Deficiency Check · In-Service Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 6106436
10 January 2017 Type not recorded
No type recorded · Sector Miami · USCG Southeast District (CGD-SE) · Activity 6068579
20 December 2016 Type not recorded
No type recorded · Sector Miami · USCG Southeast District (CGD-SE) · Activity 6060532
4 December 2016 Administrative Inspection
Administrative · Sector Key West · USCG Southeast District (CGD-SE) · Activity 6052500
16 November 2016 In-Service Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 6042061
2 October 2016 ISPS II Exam · Ballast Water Examination · COC-CVE Annual
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 6013035
10 May 2016 Deficiency Check
Physical examination · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 5873629
10 April 2016 Ballast Water Examination · COC-CVE Quarterly · ISPS III Exam
Physical examination · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 5850169
5 April 2016 Type not recorded
No type recorded · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 5847854
22 February 2016 Deficiency Check
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 5819727
24 January 2016 Type not recorded
No type recorded · Sector Miami · USCG Southeast District (CGD-SE) · Activity 5805061
27 December 2015 Deficiency Check
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 5787458
9 December 2015 In-Service Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 5778826
20 November 2015 In-Service Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 5774647
23 October 2015 Deficiency Check
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 5749628
4 October 2015 ISPS II Exam · COC-CVE Annual · Ballast Water Examination
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 5733768
6 October 2014 ISPS II Exam · COC-CVE Annual
Physical examination · Sector San Juan · USCG Southeast District (CGD-SE) · Activity 4999997
14 March 2014 COC-CVE Quarterly · ISPS III Exam · Deficiency Check · Ballast Water Examination
Physical examination · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 4815390
2 February 2012 Type not recorded
No type recorded · Marine Safety Unit Saint Thomas · USCG Southeast District (CGD-SE) · Activity 4239933
25 February 2011 Type not recorded
No type recorded · Sector Key West · USCG Southeast District (CGD-SE) · Activity 3965957
11 February 2011 Type not recorded
No type recorded · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 3943725
10 February 2011 Type not recorded
No type recorded · Sector Key West · USCG Southeast District (CGD-SE) · Activity 3943454
28 October 2010 Deficiency Check
Physical examination · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 3879710
27 October 2010 Ballast Water Examination · COC-CVE Quarterly · ISPS II Exam
Physical examination · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 3879333
30 March 2010 ISPS III Exam · Ballast Water Examination · COC-CVE Annual
Physical examination · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 3705747
21 March 2010 Type not recorded
No type recorded · Sector Key West · USCG Southeast District (CGD-SE) · Activity 3699828
3 February 2010 Deficiency Check
Physical examination · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 3674863
27 July 2009 Administrative Inspection
Administrative · Sector San Juan · USCG Southeast District (CGD-SE) · Activity 3547729
7 July 2009 In-Service Inspection
Physical examination · Sector Key West · USCG Southeast District (CGD-SE) · Activity 3526506
25 March 2009 Type not recorded
No type recorded · Sector Jacksonville · USCG Southeast District (CGD-SE) · Activity 3440107
12 February 2009 Type not recorded
No type recorded · Sector Jacksonville · USCG Southeast District (CGD-SE) · Activity 3416644
5 February 2009 Type not recorded
No type recorded · Resident Inspection Office St. Croix · USCG Southeast District (CGD-SE) · Activity 3412906
28 January 2009 Type not recorded
No type recorded · Sector Jacksonville · USCG Southeast District (CGD-SE) · Activity 3401662
16 January 2009 COC-CVE Quarterly
Type not classified · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 3395150
24 September 2008 In-Service Inspection
Physical examination · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 3331771
27 July 2008 ISPS II Exam · COC-CVE Annual
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 3281092
27 July 2008 Type not recorded
No type recorded · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 3282259
13 July 2008 Type not recorded
No type recorded · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 3266241
11 March 2008 Type not recorded
No type recorded · Sector Jacksonville · USCG Southeast District (CGD-SE) · Activity 3162554
1 March 2008 COC-CVE Quarterly
Type not classified · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 3155698
13 February 2008 Type not recorded
No type recorded · Sector Jacksonville · USCG Southeast District (CGD-SE) · Activity 3146664
30 January 2008 Type not recorded
No type recorded · Sector Jacksonville · USCG Southeast District (CGD-SE) · Activity 3139067
9 January 2008 Type not recorded
No type recorded · Sector Jacksonville · USCG Southeast District (CGD-SE) · Activity 3127528
4 January 2008 Type not recorded
No type recorded · Sector Jacksonville · USCG Southeast District (CGD-SE) · Activity 3124784
12 December 2007 Type not recorded
No type recorded · Sector Jacksonville · USCG Southeast District (CGD-SE) · Activity 3114575
23 November 2007 Type not recorded
No type recorded · Sector Jacksonville · USCG Southeast District (CGD-SE) · Activity 3103075
1 September 2007 PII Safety Exam · COC-CVE Annual · MARPOL Annex V Examination · Ballast Water Examination · ISPS II Exam · MARPOL Annex I Examination
Physical examination · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 3042239
11 May 2007 Type not recorded
No type recorded · Sector Jacksonville · USCG Southeast District (CGD-SE) · Activity 2927705
2 May 2007 Type not recorded
No type recorded · Sector Jacksonville · USCG Southeast District (CGD-SE) · Activity 2920792
23 March 2007 Type not recorded
No type recorded · Sector Jacksonville · USCG Southeast District (CGD-SE) · Activity 2893851
16 March 2007 Type not recorded
No type recorded · Sector Jacksonville · USCG Southeast District (CGD-SE) · Activity 2889361
22 October 2006 Type not recorded
No type recorded · Station Key West · USCG Southeast District (CGD-SE) · Activity 2806123
9 August 2006 Type not recorded
No type recorded · Marine Safety Unit Saint Thomas · USCG Southeast District (CGD-SE) · Activity 2741561
8 August 2006 Type not recorded
No type recorded · Marine Safety Unit Saint Thomas · USCG Southeast District (CGD-SE) · Activity 2740434
15 July 2006 Deficiency Check
Physical examination · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 2713458
23 June 2006 ISPS II Exam · COC-CVE Annual
Physical examination · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 2689026
28 April 2006 COC-CVE Annual · MARPOL Annex V Examination · MARPOL Annex I Examination
Physical examination · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 2627222
29 October 2005 MARPOL Annex V Examination · Ballast Water Examination · MARPOL Annex I Examination · COC-CVE Quarterly · ISPS II Exam
Physical examination · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 2541555
30 May 2005 Type not recorded
No type recorded · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 2373033
28 May 2005 Type not recorded
No type recorded · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 2371113
25 May 2005 Type not recorded
No type recorded · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 2368330
11 May 2005 Deficiency Check
Physical examination · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 2355323
30 April 2005 COC-CVE Annual · ISPS II Exam · Ballast Water Examination · MARPOL Annex I Examination · MARPOL Annex V Examination
Physical examination · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 2343130
4 December 2004 COC-CVE Quarterly
Type not classified · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 2253171
11 July 2004 In-Service Inspection
Physical examination · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 2133015
21 June 2004 MTSA/ISPS Verification
Physical examination · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 2105701
29 May 2004 MTSA/ISPS Verification
Physical examination · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 2081635
29 May 2004 Annual Inspection
Physical examination · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 2081646
6 December 2003 In-Service Inspection
Physical examination · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 1959824
8 October 2003 Deficiency Check
Physical examination · MSO HAMPTON ROADS · USCG East District (CGD-E) · Activity 1924060
25 September 2003 Administrative Inspection
Administrative · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 1913001
8 June 2003 Type not recorded
No type recorded · MSD MARATHON · USCG Southeast District (CGD-SE) · Activity 1819086
7 June 2003 Annual Inspection
Physical examination · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 1811842
10 May 2003 Administrative Inspection
Administrative · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 1802818
1 March 2003 Quarterly Examination
Physical examination · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 1751267
14 December 2002 Quarterly Examination
Physical examination · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 1718573
7 September 2002 Quarterly Examination
Physical examination · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 1671795
8 June 2002 Certificate of Compliance · MARPOL Annex V Examination · Ballast Water Examination · MARPOL Annex I Examination
Physical examination · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 1628913
20 May 2002 Type not recorded
No type recorded · MSO JACKSONVILLE · USCG Southeast District (CGD-SE) · Activity 1618694
18 March 2002 Administrative Inspection · Damage Survey
Physical examination · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 1494311
14 March 2002 Type not recorded
No type recorded · MSO JACKSONVILLE · USCG Southeast District (CGD-SE) · Activity 1493663
4 March 2002 Quarterly Examination
Physical examination · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 1490697
8 December 2001 Control Verification
Physical examination · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 773062
8 September 2001 Quarterly Examination
Physical examination · MSO JACKSONVILLE · USCG Southeast District (CGD-SE) · Activity 1453936
9 June 2001 Control Verification
Physical examination · MSO JACKSONVILLE · USCG Southeast District (CGD-SE) · Activity 1072377
9 June 2001 Control Verification
Physical examination · MSO JACKSONVILLE · USCG Southeast District (CGD-SE) · Activity 1445821
10 March 2001 Quarterly Examination
Physical examination · MSO JACKSONVILLE · USCG Southeast District (CGD-SE) · Activity 1462199
9 September 2000 Quarterly Examination
Physical examination · MSO JACKSONVILLE · USCG Southeast District (CGD-SE) · Activity 1450520
9 June 2000 Control Verification
Physical examination · MSO JACKSONVILLE · USCG Southeast District (CGD-SE) · Activity 1050487
20 March 2000 Quarterly Examination
Physical examination · MSO JACKSONVILLE · USCG Southeast District (CGD-SE) · Activity 817213
20 December 1999 Quarterly Examination
Physical examination · MSO JACKSONVILLE · USCG Southeast District (CGD-SE) · Activity 1440238
20 September 1999 Quarterly Examination
Physical examination · MSO JACKSONVILLE · USCG Southeast District (CGD-SE) · Activity 1338510
20 August 1999 Deficiency Check
Physical examination · MSO JACKSONVILLE · USCG Southeast District (CGD-SE) · Activity 779353
21 June 1999 Control Verification
Physical examination · MSO JACKSONVILLE · USCG Southeast District (CGD-SE) · Activity 1424778
5 April 1999 Quarterly Examination
Physical examination · MSO JACKSONVILLE · USCG Southeast District (CGD-SE) · Activity 788222
15 March 1999 Deficiency Check
Physical examination · MSO JACKSONVILLE · USCG Southeast District (CGD-SE) · Activity 805877
22 January 1999 Type not recorded
No type recorded · MSO JACKSONVILLE · USCG Southeast District (CGD-SE) · Activity 120950
7 January 1999 Type not recorded
No type recorded · MSO JACKSONVILLE · USCG Southeast District (CGD-SE) · Activity 165220
7 January 1999 Type not recorded
No type recorded · MSO JACKSONVILLE · USCG Southeast District (CGD-SE) · Activity 177764
21 December 1998 Quarterly Examination
Physical examination · MSO JACKSONVILLE · USCG Southeast District (CGD-SE) · Activity 808533
21 September 1998 Quarterly Examination
Physical examination · MSO JACKSONVILLE · USCG Southeast District (CGD-SE) · Activity 801371
14 August 1998 Type not recorded
No type recorded · Marine Safety Unit Port Canaveral · USCG Southeast District (CGD-SE) · Activity 437661
7 August 1998 Type not recorded
No type recorded · MSO JACKSONVILLE · USCG Southeast District (CGD-SE) · Activity 798638
16 July 1998 Type not recorded
No type recorded · MSO JACKSONVILLE · USCG Southeast District (CGD-SE) · Activity 110485
15 July 1998 Control Verification
Physical examination · MSO JACKSONVILLE · USCG Southeast District (CGD-SE) · Activity 1471355
19 June 1998 Type not recorded
No type recorded · Activities Europe · Activity 1368783

Deficiency record · 65

11 - Life Saving Appliances › N/A - No Subsystem › Operational readiness of lifesaving appliances
Issued 6 March 2026 Resolved
Before the ship leaves port and at all times during the voyage, all life-saving appliances shall be in working order and ready for immediate use. PSCO observed port side rescue boat with intermittent gear lever engagement when selecting forward gear. 74 SOLAS 20 III/20.2 action code 17c def code 11129
Condition: Damaged By Earlier Event
Action required: 17 - Rectify deficiencies prior to departure
Due 10 March 2026
Resolved 6 March 2026
Resolution: Crew troubleshot and identified loose throttle cable connection. Rectified and retested sat.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 6 March 2026 Resolved
The construction of all doors and door frames in ``A'' class divisions, with the means of securing them when closed, shall provide resistance to fire as well as to the passage of smoke and flame, as far as practicable, equivalent to that of the bulkheads in which the doors are situated. Such doors and door frames shall be constructed of steel or other equivalent material. PSCO observed 12 fire doors, including those in main vertical zone boundaries stairway enclosures, unable to close properly. 74 SOLAS 97 II-2/30.2 Action code 17c Def Code 07105
Condition: Design Flaw
Action required: 17 - Rectify deficiencies prior to departure
Due 10 March 2026
Resolved 6 March 2026
Resolution: Crew rectified each identified door prior to completion of exam
03 - Water/Weathertight Conditions › N/A - No Subsystem › Doors
Issued 6 March 2026 Resolved
Each power-operated sliding watertight door, shall be provided with an audible alarm, distinct from any other alarm in the area, which will sound whenever the door is closed remotely by power and which shall sound for at least 5 s but nounit. PSCO observed approximatley half of the sliding watertight doors in machinery spaces with inoperable visual signals 74 SOLAS 04 II-1/15.7.1.6 Action Code 16c Def code 03107
Condition: Design Flaw
Action required: 16 - Rectify deficiencies w/in 14 days
Due 10 March 2026
Resolved 6 March 2026
Resolution: Crew replaced bulbs and retetested
11 - Life Saving Appliances › N/A - No Subsystem › Operational readiness of lifesaving appliances
Issued 6 March 2026 Resolved
Before the ship leaves port and at all times during the voyage, all life-saving appliances shall be in working order and ready for immediate use. PSCO observed several lifeboats with emergency steering tillers incapable of steering the lifeboat to starboard. 74 SOLAS 20 III/20.2 Action code 50c Def code 11129
Condition: Design Flaw
Action required: 50 - Rectify deficiencies w/in 30 days
Due 6 April 2026
Resolved 15 March 2026
Resolution: Class report attesting to satisfactory resolution provided, uploaded to documents.
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 6 March 2026 Resolved
Where the contents and use of a space are such that there is a doubt as to its classification for the purpose of this regulation, it shall be treated as a space within the relevant category having the most stringent boundary requirements. PSCO observed A/C machinery space on deck 7 converted into workshop, including storage of combustibles. 74 SOLAS 97 II-2/26.2.2 action code 50c def code 07101
Condition: Design Flaw
Action required: 50 - Rectify deficiencies w/in 30 days
Due 6 April 2026
Resolved 6 March 2026
Resolution: Crew removed all items stowed in A/C machinery space prior to completion of exam.
07 - Fire Safety › N/A - No Subsystem › Operation of Fire protection systems
Issued 6 March 2026 Resolved
Fire-fighting systems and appliances shall be kept in good working order and readily available for immediate use. Portable extinguishers which have been discharged shall be immediately recharged or replaced with an equivalent unit. PSCO observed stowed items blocking sprinkler system nozzles on aft mooring deck. 74 SOLAS 20 II-2/14.2.1.2 action code 16c def code 07123
Condition: Damaged By Earlier Event
Action required: 16 - Rectify deficiencies w/in 14 days
Due 20 March 2026
Resolved 6 March 2026
Resolution: Crew removed stowed gear prior to completion of exam.
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 6 March 2026 Resolved
Where the contents and use of a space are such that there is a doubt as to its classification for the purpose of this regulation, it shall be treated as a space within the relevant category having the most stringent boundary requirements. PSCO observed several technical spaces behind linings being used for storage, including combustibles. 74 SOLAS 97 II-2/26.2.2 action code 16c def code 0701
Condition: Design Flaw
Action required: 16 - Rectify deficiencies w/in 14 days
Due 20 March 2026
Resolved 6 March 2026
Resolution: Crew removed items prior to completion of exam.
07 - Fire Safety › N/A - No Subsystem › Remote Means of control (opening,pumps,ventilation,etc.) Machinery spaces
Issued 6 March 2026 Resolved
Means of control shall be provided for opening and closure of skylights, closure of openings in funnels which normally allow exhaust ventilation, and closure of ventilation dampers. PSCO observed ventilation dampers 9304 and 04301 not close when activated. 74 SOLAS 97 II-2/11.4.1 action code 16c def code 07114
Condition: Design Flaw
Action required: 16 - Rectify deficiencies w/in 14 days
Due 20 March 2026
Resolved 6 March 2026
Resolution: Crew troubleshot and demonstrated satisfactory operation of dampers prior to completion of exam.
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 6 March 2026 Resolved
Doorways, cooridors, and intermediate landings included in means of escape shall be sized in the same manner as stairways. PSCO observed secondary means of escape door form category one observation center was smaller than 800 millimeters. 74 SOLAS 97 II-2/28.1.5.3 action code 50c def code 07120
Condition: Design Flaw
Action required: 50 - Rectify deficiencies w/in 30 days
Due 30 April 2026
Resolved 15 March 2026
Resolution: Class report attesting to satisfactory resolution provided, uploaded to documents.
07 - Fire Safety › N/A - No Subsystem › Remote Means of control (opening,pumps,ventilation,etc.) Machinery spaces
Issued 6 March 2026 Resolved
Means of control shall be provided for opening and closure of skylights, closure of openings in funnels which normally allow exhaust ventilation, and closure of ventilator dampers. PSCO observed labelling for fire damper control system to be inaccurate. 74 SOLAS 97 II-2/11.4.1 action code 50c def code 07114
Condition: Design Flaw
Action required: 50 - Rectify deficiencies w/in 30 days
Due 6 April 2026
Resolved 6 March 2026
Resolution: Crew corrected inaccurate labelling on damper. System remains inaccurate, however NCOE stated that this was acceptable.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 14 September 2025 Resolved
07105 Fire doors in main vertical zone bulkheads and stairway enclosures shall be self-closing. PSCO observed Firedoor# 03/3/02, 4-2-05, and 3.6.20 not able to close. 74 SOLAS 97 II-2/30.4.1 10c
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 14 September 2025
Resolved 14 September 2025
Resolution: Doors were restored to proper fucntionality and operation.
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 14 September 2025 Resolved
07120 In addition to the emergency lighting, the means of escape, including stairways and exits, shall be marked by lighting of photoluminescent strip indicators placed not more than 0.3m (300mm) above the deck at all points of the escape route including angles and intersections. The marking must enable passengers to identify all the routes of escape and readily identify escape exits. Escape route located in Luminere restaurant had escape route signage that was not visible. 74 SOLAS 97 II-2/28.1.10 10c
Condition: Improper Installation
Action required: 10 - Deficiency Rectified
Due 14 September 2025
Resolved 14 September 2025
Resolution: Signage was installed above the escape route.
01 - Certificates & Documentation › 011 - Ships Certificates › Cargo Ship Safety Construction (including exempt.)
Issued 12 October 2024 Resolved
The condition of the ship and its equipment shall be maintained to conform with the provisions of the present regulations to ensure that the ship in all respects will remain fit to proceed to sea without danger to the ship or persons. PSCOs were informed that Diesel Generator #3 had a governor malfunction, causing the diesel generator to be non-operational. 74 SOLAS (20) Ch I / Reg 11(a)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 26 October 2024
Resolved 26 November 2024
Resolution: Vessel submitted documenation showing Diesel Generator #3 and to find it in good working order.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 20 September 2024 Resolved
Except for hatches between cargo, special category, store, and baggage spaces, and between such spaces and the weather decks, all openings shall be provided with permanently attached means of closing which shall be at least as effective for resisting fires as the divisions in which they are fitted. FSD 01/3/03 and 03/7/14 failed to securely latch upon closing. 74SOLAS97 II-2/30.1
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 20 September 2024
Resolved 20 September 2024
04 - Emergency Systems › N/A - No Subsystem › Low level lighting in corridors
Issued 16 October 2022 Resolved
Means of escape shall be marked by lighting or photoluminescent strip indicators placed...at all points of the escape route, including angles and intersections. Secondary exit leading from Fathoms lacks low location lighting.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 16 November 2022
Resolved 14 November 2022
Resolution: LLL was installed and documentation to support submitted.
04 - Emergency Systems › N/A - No Subsystem › Abandon ship drills
Issued 16 October 2022 Resolved
Every crew member with assigned emergency duties shall be familiar with these duties before the voyage begins. Crew unfamiliar with operation of liferaft davit. Davit was entended to the degree that wire rope was causing limit switch to be activated preventing raft from being lifted into embarkation position. Additionally, crew did not arrange the liferaft in an postition suitable for embarkation.
Condition: Placed in Improper Service
Action required: 10 - Deficiency Rectified
Resolved 16 October 2022
Fire Fighting › Means of Escape › Escape Route Signs
Issued 14 March 2018 Resolved
0915 - signs indications - Additional aids for escape shall be provided as necessary to ensure accessibility, clear marking, and adequate design for emergency situations. Signage in numerous locations throughout the ship are missing and others are not in accordance with the fire control plan. - 74SOLAS(2014 cons.)II-2/13.1.3
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 28 March 2018
Resolved 28 March 2018
Resolution: Vessel submitted class report attesting to the correction of def. Vessel installed and replaced exit and emergency exit signage throughout the ship IAW the fire control plan.
Operations/Management › Port and Waterways Safety › Notice of Arrival, General
Issued 6 December 2017 Resolved
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 4 February 2018
Resolved 1 February 2018
Resolution: USCG Issued NOV
Fire Fighting › Structural - A Class Divisions › Aux Spaces (little/no fire risk)
Issued 2 October 2017 Resolved
A category 10 space is a space where the storage of combustibles is prohibited. Port and starboard fan rooms FWD Deck 6 (space 6.6) had excessive air filters stored in there.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 2 October 2017
Engineering › Sea-water System (primary cooling) › Piping
Issued 17 March 2017 Resolved
The condition of the ship and its equipment shall be maintained to conform with the condition of the present regs. Vessel suffered a reduction of propulsion due to decrease of cooling liquid for port shaft.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 17 March 2017
Resolved 17 March 2017
Resolution: Received Class report from LR attesting to adequate repair of cooling piping. Def rectified.
Operations/Management › Port and Waterways Safety › Notice of Arrival, General
Issued 4 December 2016 Resolved
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 4 December 2016
Resolved 5 December 2016
Resolution: ISSUED NOV
Fire Fighting › Structural - A Class Divisions › Fire Doors
Issued 10 April 2016 Resolved
0750-Fire Prevention- The construction of all doors in "A" class divisions with the means of serving shall provide resistance to fire. Fire door 11/02/01 needs to be replaced due to it's inoperability and fire screen door 3/04/05 is not capable of full closure at the bottom. SOLAS 74 (97 con.) chap II-2 Reg 30 (2).
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 10 May 2016
Resolved 10 May 2016
Resolution: MSD Port Canaveral received Class Report from Lloyd's Register surveyor attesting to repair and satisfactory operation of both Fire Screen Doors.
Fire Fighting › Structural - A Class Divisions › Special Category Spaces
Issued 10 April 2016 Resolved
0750-Fire Prevention- The minimum fire fire integrity of bulkheads shall be as prescribed in the table 26.1 A-0 bulkhead on deck deck 11 between 1Ft space & pyrotechnics space does not meet A-0 requirements due to new ventilation trunk with no damper. SOLAS 74 (97 Con Ed.) Chap.II-2 Reg 26.1
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 10 May 2016
Resolved 10 May 2016
Resolution: MSD Port Canaveral received Class Report from Lloyd's Register surveyor stating that ventilation fan and associated trunking have been removed and A-0 bulkhead integrity reinstated to the Surveyor's satisfaction.
Engineering › Compressed Air System (start air) › Compressor
Issued 9 December 2015 Resolved
1430 - A second source of energy shall be provided for an additional three starts. The secondary means of starting the EDG (air) is inoperable. 74 SOLAS (97), Ch. II-I / 44.2.
Condition: Invalid
Action required: 705 - Other - as specified
Due 23 December 2015
Resolved 27 December 2015
Resolution: PSC Miami received class surveyor report. PSCO witnessed the secondary means (air) of starting of the EDG successfully.
Lifesaving › Launching Appliances › Release Mechanism
Issued 4 October 2015 Resolved
0610 - Every lifeboat to be launched by falls shall be fitted with a release mechanism. Lifeboat #20 port side release mechanism was inoperable/detached. 74 SOLAS (97) III/1.4 LSA Code Ch. IV/4.4.7.6
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 4 October 2015
Resolved 4 October 2015
Resolution: Release mechanism was re-attached and deficiency was cleared on the spot.
Communications › Public Address System › Loudspeaker
Issued 4 October 2015 Resolved
0676 - A public address system or other effective means of communication shall be available throughout the accommodation and service spaces. Public address system should be clearly audible above ambient noise in all spaces. PA system not able to be heard in engine room spaces. 74 SOLAS (97) II-2/40.5
Condition: Design Flaw
Action required: 705 - Other - as specified
Due 4 October 2015
Resolved 4 October 2015
Resolution: Deficiency was rectified.
Fire Fighting › Means of Escape › Emergency Lighting
Issued 4 October 2015 Resolved
0915 - Means of escape shall be marked by lighting or photo luminescent strip indicators at all points of escape routes. Various sections of low location lighting along escape routes are extinguished. 74 SOLAS (97) II-2/28.1.10
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 18 October 2015
Resolved 23 October 2015
Resolution: New low locating lighting has been installed.
Fire Fighting › Structural - A Class Divisions › Fire Doors
Issued 4 October 2015 Resolved
0750 - Doors and door frames in "A" class divisions shall provide resistance to fire as well as passage of smoke and flame. Numerous fire doors did not fully close as designed, including: 01/4/15, 03/3/03, 05/3/02, 05/4/02, 10/6/03, 8/2/08, 7/6/12, 3/4/16, 03/1/10 and 01/3/27. 74 SOLAS (97) II-2/30.2
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 18 October 2015
Resolved 23 October 2015
Resolution: Doors have been repaired and fully close now.
Fire Fighting › Structural - A Class Divisions › Windows
Issued 4 October 2015 Resolved
0750 - Windows facing embarkation and muster areas and open decks used for escape routes shall have fire integrity as required by Reg. 26. A-0 windows on embarkation deck are no longer protected by dedicated sprinklers as designed due to installation of second glass pane. 74 SOLAS (97) II-2/33.3
Condition: Design Flaw
Action required: 705 - Other - as specified
Due 6 November 2015
Resolved 23 October 2015
Resolution: Shelfs were permanently removed, leaving only one vertical piece which will not interfere with the adequate cooling of the windows by the sprinkler system if activated.
Fire Fighting › Structural - A Class Divisions › Sanitary Spaces
Issued 4 October 2015 Resolved
0750 - For determining appropriate fire integrity standards to be applied to divisions between adjacent spaces, spaces are categorized according to their fire risk as shown in categories (1) to (11). Previous sanitary space adjoining broadcast room is being used as a category 13 storage space but is classified as a category 9 on the vsl plans. Also, multiple lifts are cat. as 8 but should be a 2
Condition: Design Flaw
Action required: 705 - Other - as specified
Due 26 February 2017
Resolved 22 February 2016
Resolution: Received Class Report from LR attesting to adequate designation on fire plans of Cat. 13 (previous Cat. 9) space. Space was veriefied to have been changed to a storage room on inspection conducted on 23OCT16.
Fire Fighting › Combustible Materials › Insulation
Issued 4 October 2015 Resolved
0750 - The minimum fire integrity of all bulkheads and decks shall be prescribed in tables 26.1 & 26.2. Overhead separating concierge large and storeroom on deck 10 does not have proper insulation to ensure A-30 boundary. Additionally, glass bulkhead separating category 3 elevator and category 8 radio studio is not A-15 boundary as required. 74 SOLAS (97) II-2/26.1
Condition: Design Flaw
Action required: 705 - Other - as specified
Due 18 October 2015
Resolved 23 October 2015
Resolution: Adequate insulation has been installed.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Piping
Issued 14 March 2014 Resolved
0725 Containers for the storage of fire-extinguishing medium and associated pressure components shall be designed to pressure components shall be designed to pressure to codes of practice to the satisfaction of the admin. Flexible hose loops on CO2 bottles on Bank1 and Bank10 to be kinked as to cause improper installation. SOLAS(97) II-2/5.1.12 - 16ab.
Due 28 March 2014
Resolved 19 March 2014
Resolution: Vessel provided report from class and photos showing that flexible hose loops are now properly installed.
Fire Fighting › Structural - A Class Divisions › Machinery Spaces
Issued 14 March 2014 Resolved
0799 In passenger ships carrying more than 36 passengers the boundary bulkheads and decks of special category spaces shall be insulated to A-60 class. Port and starboard bunker stations and bulkhead forward of emergency generator room were found to be missing SFP SOLAS(97) II-2/5.1.12 - 16ab.
Condition: Improper/Lack of Maintenance
Due 28 March 2014
Resolved 19 March 2014
Resolution: Vessel provided a report from class stating that the SFP has been reinstalled.
Engineering › Freshwater System (jacketwater cooling) › Piping
Issued 14 March 2014 Resolved
0430 The condition of the ship and its equipment shall be maintained to conform with the provisions of the present regulation to ensure the ship in all respects will remain fit to proceed to sea. Inlet and outlet water piping on lube oil cooler #1 and technical water piping in stbd bunker station found with temporary pipe patches and improper repairs SOLAS(09) I/11 - 16ab.
Condition: Improper/Lack of Maintenance
Due 28 March 2014
Resolved 19 March 2014
Resolution: Vessel provided report from class stating that a temporary repair by welded patches was installed. Also a Mechanical Condition of Class was imposed that requires the vessel to renew piping.
Construction/Loadline › Structures › Transverse Bulkhead
Issued 13 March 2014 Resolved
0987 Ships shall be designed, constructed and maintained in compliance with the structural requirements of a classification society. Bulkhead located in fan space, deck 8, stbd side, across from cabin 8528 was found to be cracked and adjacent overhead had a temporary repair SOLAS (04) II-1/3-1 - 16ab.
Condition: Damaged By Earlier Event
Due 28 March 2014
Resolved 17 March 2014
Resolution: Received class report attesting that all areas are been inspected and fire protection reinstated.
Fire Fighting › Means of Escape › Blocked
Issued 3 April 2010 Resolved
Access to emergency escape, fire fighting equipment, and water tight doors are blocked or hindered on C deck. All blocked areas are to be cleared and allow free access to water tight doors, fire fighting equipment and emergency escape.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 3 April 2010
Resolution: All areas were cleaned to allow free access to watertight doors, fire fighting equipment, and emergency escape. DCL Staff Captain provided email that areas were cleared and the ship departed as scheduled.
Electrical › Lighting (service) › Lighting Fixture
Issued 3 April 2010 Resolved
Spool piece in A/C room in vicinity of FSD 08/5/05 leaks onto light.
Action required: 705 - Other - as specified
Due 3 May 2010
Resolved 28 October 2010
Resolution: Reviewed photgraph of satisfactory correction to spool piece.
Operations/Management › Port and Waterways Safety › Notice of Arrival, General
Issued 8 August 2006 Resolved
M/V DISNEY MAGIC failed to provide an ANOA 24 hours prior to entering US Waters.
Action required: 705 - Other - as specified
Due 8 August 2006
Resolved 9 August 2006
Resolution: ANOA submitted at 1702 08Aug2006. Vsl allowed to enter St Thomas at 0630 09Aug2006.
Electrical › Electrical Distribution System (service) › Cable
Issued 28 April 2006 Resolved
Remove dead end wire from OWS space.
Due 13 May 2006
Resolved 15 July 2006
Resolution: Completed/Inspected by [name withheld], [name withheld].
Engineering › Diesel Engine (auxiliary) › Piping (exhaust)
Issued 30 April 2005 Resolved
Repairs are to be made to the emergency generator required by SOLAS 74, Chapter II-1, Regulation 42 IWO exhaust piping leaks.
Condition: Unknown
Action required: 705 - Other - as specified
Due 7 May 2005
Resolved 11 May 2005
Resolution: Received LR Class report attesting to repairs to the emergency generator exhaust leak.
Engineering › Steering Gear System › Rudder Angle Indicator
Issued 30 April 2005 Resolved
Vessel is to make repairs to the starboard steering gear system required by SOLAS 74, Chapter II-1, Regulation 29 IWO misalignment between bridge and aft steering.
Condition: Unknown
Action required: 705 - Other - as specified
Due 7 May 2005
Resolved 11 May 2005
Resolution: Received LR Class report attesting to repairs and proper operation of the steering system.
Construction/Loadline › Hull › Weld
Issued 29 May 2004 Resolved
Provide Class attestation as to the proper repairs to a cracked weld in the starboard steering room overhead located on a frame stiffener that runs between two longitudinal frames. The crack is approx 12 inches long and does not appear to follow through to the longitudinal frame. LEGACY COMPONENT DESC: Stiffener
Condition: Unknown
Due 16 June 2004
Resolved 11 July 2004
Fire Fighting › Miscellaneous Items
Issued 7 June 2003 Resolved
Replace missing IMO stickers on fire stations between Preludes and Animator's Palate. LEGACY COMPONENT DESC: IMO stickers
Condition: Unknown
Due 7 July 2003
Resolved 8 October 2003
Resolution: RECEIVED CERTIFICATE OF CLASS ATTESTING THE DISNEY MAGIC WAS "FOUND IN COMPLIANCE WITH THE RULES AND REGULATIONS FOR THE CLASSIFICATION OF SHIPS, THE AFORESAID SHIP HAS BEEN ASSIGNED CLASS."
Accommodation/Occupational Safety › Occupational Safety
Issued 7 June 2003 Resolved
Replace missing key at A/C station 1201. LEGACY COMPONENT DESC: A/C station key
Condition: Unknown
Due 7 July 2003
Resolved 1 October 2003
Resolution: RECEIVED CERTIFICATE OF CLASS ATTESTING THE DISNEY MAGIC WAS "FOUND IN COMPLIANCE WITH THE RULES AND REGULATIONS FOR THE CLASSIFICATION OF SHIPS, THE AFORESAID SHIP HAS BEEN ASSIGNED CLASS."
Construction/Loadline › Hull
Issued 10 May 2003 Resolved
hull WASTAGE between frames 84 and 87 and 79-81on stbd side in way of the engine room-SECOND OCCURENCE SAME AREA. DISNEY RESEARCHING AND TESTING TO DETERMINE IF BAD STEEL EXISTS AND TO WHAT EXTENT. FULL REPAIRS TO MADE AT DRYDOCK SEP 2003. LEGACY COMPONENT DESC: Hull Plating
Due 30 September 2003
Resolved 8 October 2003
Resolution: RECEIVED CERTIFICATE OF CLASS STATING DISNEY MAGIC WAS "FOUND IN COMPLIANCE WITH THE RULES AND REGULATIONS FOR THE CLASSIFICATION OF SHIPS, THE AFORESAID SHIP HAS BEEN ASSIGNED THE CLASS" (LLOYDS REGISTER)
Accommodation/Occupational Safety › Other Accommodation Spaces › Laundry
Issued 7 September 2002 Resolved
Insulation on several pipes in main laundry missing. Safety Officer taking proper action.
Condition: Improper/Lack of Maintenance
Due 7 September 2002
Resolved 7 September 2002
Resolution: Safety Officer taking proper action.
Accommodation/Occupational Safety › Other Accommodation Spaces
Issued 7 September 2002 Resolved
Luggage in storage space in guest area. Corrected on the spot.
Condition: Unknown
Due 7 September 2002
Resolved 7 September 2002
Resolution: Luggage was removed from storage area.
Accommodation/Occupational Safety › Other Accommodation Spaces › Laundry
Issued 7 September 2002 Resolved
Heat exhaust for dryer in guest launderette cut open, not operational. Corrected on the spot.
Condition: Improper/Lack of Maintenance
Due 7 September 2002
Resolved 7 September 2002
Resolution: Exhaust pipe was repaired.
Fire Fighting › Combustible Materials
Issued 10 June 2002 Resolved
Remove flammables from carpenters shop and cover open containers in the paint locker. LEGACY COMPONENT DESC: Paints/Varnishes/Other Finishes
Due 15 June 2002
Resolved 24 June 2002
Fire Fighting › Structural Fire Protection - General
Issued 10 June 2002 Resolved
repair bottom of Fire Screen door frame Deck 7 Launderette to allow door to properly close. LEGACY COMPONENT DESC: Accommodation Space Protection
Due 15 June 2002
Resolved 24 June 2002
Electrical › Electrical Distribution System (service)
Issued 18 March 2002 Resolved
ALL ELECTRICAL WIRING, RECEPTICLES, OUTLETS AND LIGHTING FIXTURES IN AFT FUNNEL DESTROYED BY FIRE. REPAIR PROPOSAL AND REPAIRS MUST COMPLETED TO THE SATISFACTION OF CLASS. LEGACY COMPONENT DESC: Cable
Condition: Damaged By Earlier Event
Due 18 April 2002
Resolved 1 May 2002
Construction/Loadline › Structures
Issued 18 March 2002 Resolved
EXTERIOR AFT FUNNEL AND UPPER DECK DESTROYED/DEFORMED BY FIRE. STRUCTURE TO REPAIRED/REPLACED TO THE SATISFACTION OF CLASS. LEGACY COMPONENT DESC: Superstructure
Condition: Damaged By Earlier Event
Due 18 April 2002
Resolved 1 May 2002
Fire Fighting
Issued 20 March 2000 Resolved
Extend smoke detection coverage in technical stores in way of reefer flats._x001C_ _x001C_ _x001C_
Condition: Unknown
Due 20 March 2000
Resolved 20 March 2000
Fire Fighting
Issued 20 March 2000 Resolved
Repair F/D's FD/ES 03-1-01.A1 in crew galley; Fs/VS 0A.1.01 at stores aft; FD 11-02-06B/2 and relabel overhead in main galley.
Condition: Unknown
Due 20 March 2000
Resolved 20 March 2000
Fire Fighting
Issued 21 June 1999 Resolved
Correct problems with FSD mimic board and electrical switches on doors 01/02/33, 08/04/104, 09/04/01.
Condition: Unknown
Due 21 June 1999
Resolved 21 June 1999
Accommodation/Occupational Safety
Issued 21 June 1999 Resolved
Provide LLL placards for Maunal fire alarm pull boxes.
Condition: Unknown
Due 21 June 1999
Resolved 21 June 1999
Fire Fighting
Issued 21 June 1999 Resolved
Provide adequate number of spare heads for installed fire detection system(smoke, heat and flame). ***NOTE: Lloyds to determine "adequate."
Condition: Unknown
Due 21 June 1999
Resolved 21 June 1999
Engineering
Issued 5 April 1999 Resolved
[withheld — contains personal information; the deficiency system, dates, and resolution status are shown above]
Condition: Unknown
Due 5 April 1999
Resolved 5 April 1999
Fire Fighting
Issued 21 December 1998 Resolved
REPAIR AND PROVE OPERATION OF FOLLOWING SPLASH DOORS: 3/5/05, 3/5/06, 1/2/21, 1/2/24, 1/4/20.
Condition: Unknown
Due 21 December 1998
Resolved 21 December 1998
Fire Fighting
Issued 21 December 1998 Resolved
FOLLOWING SCREEN DOORS FOUND NOT IN COMPLIANCE: 3/1/03, 1/1/05, 3/3/10, 8/3/23, 9/3/15, 5/3/11, 4/3/12, 1/3/11, 1/3/01, 2/3/05, 2/3/04, 3/3/32, 3/4/10, 3/4/4, 4/3/12, 2/3/04, 7/3/15, 4/2/11, 10/3/4, 1/3/1, 1/3/35. DOORSFOUND AJAR DUE TO IMPROPER LATCH, TIED OPEN, MISALIGNED.
Condition: Unknown
Due 21 December 1998
Resolved 21 December 1998
Fire Fighting
Issued 21 December 1998 Resolved
REPAIR AND PROVE PROPER OPERATION OF SPRINKLER STATION #32 REMOTE INDICATOR.
Condition: Unknown
Due 21 December 1998
Resolved 21 December 1998
Fire Fighting
Issued 21 December 1998 Resolved
MVZ 3 AFT STAIRTOWER FOLLOWING FSD FAILED TO INDICATE CLOSED ON BRIDGE: 7/3/15, 6/3/07, 4/3/16, 4/2/01, 4/2/02, 3/3/06, 3/3/09, 1/3/42, 1/3/54.
Condition: Unknown
Due 21 December 1998
Resolved 21 December 1998
Accommodation/Occupational Safety
Issued 21 September 1998 Resolved
REPAIR AND PROVE PROPER OPERATION OF THE FOLLOWING FIRE SCREEN DOORS: 05/1/01, 04/3/16, 03/3/10, 02/1/02, 04/5/08, 5.15 AT FR 207, B503, A510, 2/3/19, 3/2/03, 4/2/10, 4/1/02, 5/1/1, 7/2/03, 11/2/03, 5/4/4
Condition: Unknown
Due 21 September 1998
Resolved 21 September 1998
Documentation
Issued 21 September 1998 Resolved
PROVIDE TRAINING MANUAL(S) IN ACCORDANCE WITH SOLAS III, REG. 18.2
Condition: Unknown
Due 21 September 1998
Resolved 21 September 1998
Accommodation/Occupational Safety
Issued 21 September 1998 Resolved
COMPLETE PROPER LABELING OF ALL FIRE DAMPERS.