GRAND PRINCESS

GRAND PRINCESS is a 1998 passenger vessel (inspected). The Coast Guard has recorded 156 inspections since 2016, most recently in June 2026, along with 65 deficiencies.

Records from 2016 to 2026. Most recent: inspection, 3 June 2026.

Built
1998
Last inspected
3 June 2026
Documentation
Not in the documentation file of 10 August 2026
Controls
None recorded without a removal date

Identity

9104005
474882
Flag
BERMUDA
Maury page id
psix-474882

Coast Guard record current through 23 August 2026, retrieved 5 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Passenger Ship class in Maury's sources begin in 2016.

Inspections, by type

…with no type recorded62
Years with a record 11 calendar years (2016–2026)
Every line above is a count of records the US Coast Guard wrote, or a date it recorded. The counts in the strip above are the same counts; this table splits the inspections by the kind of activity recorded. A blank resolution means none was recorded in this data; it does not establish that a deficiency is outstanding. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Documentation record

Tonnage as PSIX records it107517 - Convention (Subpart B), Gross Ton
72622 - Convention (Subpart B), Net Ton
8496 - Dead Weight, Ton
54520 - Displacement, Ton
This hull's Official Number is not in the NVDC file dated 10 August 2026 as served by NOAA Fisheries, so no documentation record is shown. Absence from that file is a fact about the file, not about the hull.
Vessel history report

A report is not offered for this hull. Its record holds only 2 of the seven kinds of material a report is built from: inspections, deficiencies, operational controls, tow-unit appearances, casualty records, dimensions and documentation. That is a statement about the record, not about the vessel. What a sparse-record report looks like.

Inspection history · 156

3 June 2026 Type not recorded
No type recorded · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 8391184
18 May 2026 Deficiency Check
Physical examination · Sector San Juan · USCG Southeast District (CGD-SE) · Activity 8375351
10 April 2026 In-Service Inspection · Deficiency Check
Physical examination · Sector San Juan · USCG Southeast District (CGD-SE) · Activity 8345783
8 February 2026 PSC B · COC-CVE Quarterly
Physical examination · Sector San Juan · USCG Southeast District (CGD-SE) · Activity 8305397
7 August 2025 COC-CVE Annual · PSC A
Physical examination · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 8204959
19 May 2025 Administrative Inspection · Deficiency Check
Physical examination · Marine Safety Detachment Ketchikan · USCG Arctic District (CGD-A) · Activity 8139448
19 May 2025 Type not recorded
No type recorded · Marine Safety Detachment Ketchikan · USCG Arctic District (CGD-A) · Activity 8145284
16 February 2025 COC-CVE Quarterly · PSC B
Physical examination · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 8079774
20 September 2024 PSC B
Physical examination · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 8006578
26 July 2024 Deficiency Check · PSC A · COC-CVE Annual
Physical examination · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7967838
3 May 2024 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7921826
3 May 2024 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7923324
27 April 2024 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7922799
21 April 2024 PSC B · COC-CVE Quarterly
Physical examination · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 7895764
2 April 2024 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7906210
5 March 2024 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7883606
20 February 2024 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7873939
29 December 2023 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7872353
3 October 2023 Bulk Liquid Transfer Monitor
Physical examination · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 7803705
13 September 2023 Administrative Inspection · Deficiency Check
Physical examination · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7791209
6 September 2023 Ballast Water Examination · PSC A · COC-CVE Annual
Physical examination · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7778876
12 July 2023 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7833592
21 June 2023 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7763670
20 June 2023 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7802257
14 June 2023 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7763645
14 June 2023 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7791848
17 May 2023 PSC B · COC-CVE Quarterly · Deficiency Check · Ballast Water Examination
Physical examination · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7689219
17 May 2023 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7742112
17 May 2023 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7744893
10 May 2023 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7734971
9 May 2023 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7738799
28 April 2023 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7726478
26 April 2023 In-Service Inspection
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 7676276
22 April 2023 In-Service Inspection
Physical examination · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 7676401
13 February 2023 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7636159
21 November 2022 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7598178
12 October 2022 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7576303
17 September 2022 Type not recorded
No type recorded · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7565134
11 September 2022 PSC A · Ballast Water Examination · COC-CVE Annual
Physical examination · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7555357
24 August 2022 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7542518
8 August 2022 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7528577
23 June 2022 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7485454
21 June 2022 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7483401
15 June 2022 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7478797
13 June 2022 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7476801
9 April 2022 Type not recorded
No type recorded · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 7428298
4 April 2022 Type not recorded
No type recorded · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7440947
25 March 2022 Deficiency Check
Physical examination · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 7418859
15 March 2022 COC-CVE Quarterly · PSC B
Physical examination · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 7410401
15 March 2022 Bulk Liquid Transfer Monitor
Physical examination · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 7412573
10 March 2022 Type not recorded
No type recorded · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7410465
9 March 2022 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7408985
23 February 2022 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7400894
18 February 2022 Type not recorded
No type recorded · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 7401644
26 January 2022 Type not recorded
No type recorded · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 7388666
18 January 2022 Ballast Water Examination
Physical examination · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 7383927
27 September 2021 Deficiency Check
Physical examination · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 7321806
17 September 2021 COC-CVE Annual
Administrative · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 7316822
29 July 2021 Type not recorded
No type recorded · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7531905
3 April 2020 Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6937678
3 March 2020 Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6935215
28 February 2020 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6917891
6 February 2020 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6904254
28 December 2019 Ballast Water Examination · COC-CVE Annual · ISPS II Exam
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6878261
13 December 2019 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6873473
2 December 2019 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6865780
20 November 2019 Administrative Inspection
Administrative · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 6859252
19 November 2019 Type not recorded
No type recorded · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 6862584
13 November 2019 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6855225
9 November 2019 Type not recorded
No type recorded · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 6865963
4 November 2019 Administrative Inspection
Administrative · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 6849185
4 November 2019 Type not recorded
No type recorded · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 6854381
3 October 2019 Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6831609
3 October 2019 Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6835001
30 September 2019 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6825087
25 September 2019 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6821149
6 September 2019 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6805712
4 September 2019 Type not recorded
No type recorded · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6850842
30 August 2019 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6799222
30 August 2019 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6799229
12 August 2019 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6781229
12 August 2019 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6781236
8 August 2019 Deficiency Check
Physical examination · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6777909
8 August 2019 Type not recorded
No type recorded · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6804178
23 July 2019 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6759607
16 July 2019 Type not recorded
No type recorded · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6752749
15 July 2019 Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6752209
11 July 2019 COC-CVE Quarterly · ISPS III Exam · Ballast Water Examination
Physical examination · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6746028
11 June 2019 Type not recorded
No type recorded · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6745152
10 June 2019 Type not recorded
No type recorded · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6718221
28 May 2019 Type not recorded
No type recorded · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6705099
18 May 2019 Type not recorded
No type recorded · Sector Puget Sound · USCG Northwest District (CGD-NW) · Activity 6752409
24 April 2019 Administrative Inspection
Administrative · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 6668966
15 April 2019 Type not recorded
No type recorded · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 6666349
12 April 2019 Type not recorded
No type recorded · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 6663068
7 April 2019 Administrative Inspection
Administrative · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 6657593
20 March 2019 Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6646375
18 January 2019 Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6613681
29 December 2018 COC-CVE Annual · Ballast Water Examination · ISPS III Exam
Physical examination · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 6602581
29 December 2018 Deficiency Check
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6608545
19 November 2018 Type not recorded
No type recorded · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 6600275
4 September 2018 Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6533394
29 August 2018 Deficiency Check
Physical examination · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6526859
18 August 2018 Type not recorded
No type recorded · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6564571
8 August 2018 In-Service Inspection
Physical examination · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6504880
6 August 2018 Type not recorded
No type recorded · Marine Safety Detachment Ketchikan · USCG Arctic District (CGD-A) · Activity 6557999
6 August 2018 Type not recorded
No type recorded · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6564374
29 June 2018 Type not recorded
No type recorded · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6507580
20 June 2018 Ballast Water Examination · ISPS III Exam · COC-CVE Quarterly
Physical examination · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6450406
10 June 2018 Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6448310
10 June 2018 Type not recorded
No type recorded · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6460093
6 June 2018 Type not recorded
No type recorded · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6445396
17 April 2018 Type not recorded
No type recorded · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 6394402
24 March 2018 Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6387930
27 February 2018 Administrative Inspection
Administrative · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 6362924
4 January 2018 ISPS III Exam · COC-CVE Annual · Ballast Water Examination
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6332409
13 November 2017 Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6307371
29 October 2017 Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6298593
28 October 2017 Administrative Inspection
Administrative · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 6298317
19 September 2017 Deficiency Check
Physical examination · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6270252
18 September 2017 Type not recorded
No type recorded · Marine Safety Detachment Ketchikan · USCG Arctic District (CGD-A) · Activity 6270267
11 September 2017 Type not recorded
No type recorded · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6264491
5 September 2017 Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6260153
10 August 2017 ISPS II Exam · Ballast Water Examination · PII Safety Exam · COC-CVE Quarterly
Physical examination · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6234620
18 May 2017 ISPS III Exam · MARPOL Annex VI Survey · MARPOL Annex I Examination
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6149118
26 April 2017 Type not recorded
No type recorded · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 6136863
14 April 2017 Type not recorded
No type recorded · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 6132702
9 February 2017 Administrative Inspection
Administrative · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 6085537
15 January 2017 Ballast Water Examination · ISPS II Exam · COC-CVE Annual
Physical examination · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 6070223
6 December 2016 Damage Survey · Administrative Inspection
Physical examination · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 6051963
30 November 2016 Type not recorded
No type recorded · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 6057426
26 November 2016 Administrative Inspection
Administrative · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 6047798
29 October 2016 PI Safety Exam · Damage Survey
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6031620
15 October 2016 Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6044155
18 September 2016 Random ISPS/MTSA-No PSC
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6002200
13 September 2016 Type not recorded
No type recorded · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6031508
8 September 2016 Random ISPS/MTSA-No PSC
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 5995101
29 August 2016 Random ISPS/MTSA-No PSC
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 5986228
28 July 2016 COC-CVE Quarterly · Deficiency Check · Ballast Water Examination · ISPS II Exam · PII Safety Exam
Physical examination · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 5955788
20 July 2016 Random ISPS/MTSA-No PSC
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 5946799
20 July 2016 Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 5948031
10 July 2016 Random ISPS/MTSA-No PSC
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 5935375
10 June 2016 Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 5906502
31 May 2016 Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 5894984
11 May 2016 Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 5887825
24 April 2016 Administrative Inspection
Administrative · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 5860988
19 April 2016 Type not recorded
No type recorded · Marine Safety Detachment Santa Barbara · USCG Southwest District (CGD-SW) · Activity 5858601
14 April 2016 Type not recorded
No type recorded · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 5854378
6 April 2016 Type not recorded
No type recorded · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 5855314
2 April 2016 Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 5865036
8 March 2016 Type not recorded
No type recorded · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 5857791
26 February 2016 Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 5824958
22 February 2016 Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 5822991
12 February 2016 Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 5816122
25 January 2016 COC-CVE Annual · ISPS II Exam · Ballast Water Examination · COE-Administrative
Physical examination · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 5802135
24 January 2016 Type not recorded
No type recorded · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 5822322

Deficiency record · 65

15 - Safety Management Systems (ISM) › N/A - No Subsystem › Shipboard operations
Issued 10 April 2026 Resolved
THE COMPANY SHOULD ISSUE PROCEDURES TO ENSURE THAT THE SHIP IS MAINTAINED IN CONFORMITY WITH THE PROVISIONS OF THE RELEVANT RULES AND REGULATIONS AND WITH ANY ADDITIONAL REQUIREMENTS WHICH MAY BE ESTABLISHED BY THE COMPANY. THE VESSEL DID NOT HAVE SUFFICIENT FUEL ONBOARD TO MAKE THE NECESSARY VOYAGE INTENDED. AN INTERNAL ISM AUDIT AND RECORD OF CORRECTIVE ACTIONS, INCLUDING ACTIONS TO PREVENT RECURRENCE IAW ISM 9, IS REQUIRED. 74 SOLAS (20) IX/3.1 ISM CODE 10.1
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 April 2026
Resolved 18 May 2026
Resolution: ISM audit conducted, see attached report.
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 10 April 2026 Resolved
TIMES FOR SUBMITTING NOTICE OF ARRIVALS ARE AS FOLLOWS: IF YOUR VOYAGE TIME IS LESS THAN 96 HOURS, BEFORE DEPARTURE BUT AT LEAST 24 HOURS BEFORE ARRIVING AT THE PORT OR PLACE OF DESTINATION. THE VESSEL DID NOT SUBMIT AN NOA IN THE REQUIRED TIME FRAME. 33 CFR 160.212 (a)(4)(ii)
Action required: 10 - Deficiency Rectified
Due 13 April 2026
Resolved 13 April 2026
Resolution: NOA submitted.
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 8 February 2026 Resolved
Where the contents and use of a space are such that there is a doubt as to its classification for the purpose of this regulation, it shall be treated as a space within the relevant category having the most stringent boundary requirements. PSCO found combustible materials being stored in A/C station 8735 (ire door 08.7.07) in a room without fire suppression system. 74SOLAS97II-2/26/2.2. 16ac.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 22 February 2026
Resolved 10 April 2026
Resolution: All combustible materials have been removed.
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 8 February 2026 Resolved
The marking must enable passengers to identify all the routes of escape and readily identify escape exits. All escape route signs and fire equipment location markings shall be of photoluminescent material or marked by lighting. PSCO Observed that the Main Office Front Desk Reception in deck 4, leading to Back Office through a stairways to deck e below lacks of adequate emergency escape signage. Also, there are combustible materials stored under the stairways. 74SOLAS97II-2/28.1.10 16ac.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 22 February 2026
Resolved 10 April 2026
Resolution: Combustible material under starways removed, and signage posted.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 8 February 2026 Resolved
The construction of all doors and door frames in ``A'' class divisions, with the means of securing them when closed, shall provide resistance to fire as well as to the passage of smoke and flame, as far as practicable, equivalent to that of the bulkheads in which the doors are situated. Such doors and door frames shall be constructed of steel or other equivalent material. PSCO observed fire door FSD 06.7.07 not closing, its hose port not closing due to damage spring. 74SOLAS97II-2/30.2 16ac.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 22 February 2026
Resolved 8 February 2026
Resolution: Corrected on the spot.
07 - Fire Safety › N/A - No Subsystem › Operation of Fire protection systems
Issued 8 February 2026 Resolved
Fire protection systems and fire-fighting systems and appliances shall be maintained ready for use. Fire hose cabinet and portable fire extinguisher, and emergency exit door were being blocked by boxes with supplies in deck 4, adjacent to FSD 4.7.20. 74SOLAS20 II-2/14.1.1 10C.
Action required: 10 - Deficiency Rectified
Resolved 8 February 2026
Resolution: Items removed, corrected on the spot.
11 - Life Saving Appliances › N/A - No Subsystem › Lifeboats
Issued 14 August 2025 Resolved
All life-saving appliances and arrangements shall comply with the applicable requirements of the Code. The propeller shafting shall be so arranged that the propeller can be disengaged from the engine. Provision shall be made for ahead and astern propulsion of the lifeboat. PSCO observed lifeboat number 11 without astern propulsion.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 14 August 2025
Resolution: Rectified
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 14 August 2025 Resolved
All "A" class doors located in stairways, public spaces and main vertical zone bulkheads in escape routes shall be equipped with self-closing hose port of material, construction and fire resistance which is equivalent to the door into which it is fitted, and shall be inset into the lower edge of the door, opposite the door hinges or, in the case of sliding doors, nearest the opening. PSCO observed FSD 15.3.01 not fully closing.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 15 August 2025
Resolution: Rectified
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Operation of machinery
Issued 19 May 2025 Resolved
The capacity of these generating sets shall be such that in the event of any one generating set being stopped it will still be possible to supply those services necessary to provide normal operational conditions of propulsion and safety. On May 19th 2025, the GRAND PRINCESS experienced a loss of propulsion while operating on two diesel generators. When DG #1 experienced a cooling water pump failure and shutdown. DG #6 was unable to provide operational propulsion, and the vessel was without propulsion for approximately 9 minutes. [name withheld] stated the vessel routinely operated with only 2 generators. SOLAS 74 (2004) II-1/41.1.2
Condition: Invalid
Action required: 16 - Rectify deficiencies w/in 14 days
Due 2 June 2025
Resolved 25 May 2025
Resolution: Witnessed satisfactory simulation of event with no loss of propulsion
14 - Pollution Prevention › 145 - MARPOL Annex V › Garbage management plan
Issued 17 August 2024 Resolved
Every ship of 100 gross tonnage and above, and every ship which is certified to carry 15 or more persons, and fixed or floating platforms shall carry a garbage management plan which the crew shall follow. PSCO observed a 6 ft high pile of unsorted garbage including hard plastic, food waste, paper, and other items in the recycling center. The pile of garbage extended into the recycling center blocking access to the space's fixed foam system activation point. Ship's crew stated that this system was not in accordance with the ship's procedures. In addition, a plastic container of unsorted garbage was found on deck 6, crew stair, forward by the bosun's store- crew stated garbage was collected here during the day. MARPOL 2017 Annex V / 10.2
Condition: Placed in Improper Service
Action required: 17 - Rectify deficiencies prior to departure
Due 17 August 2024
Resolved 17 August 2024
Resolution: Rectified
07 - Fire Safety › N/A - No Subsystem › Operation of Fire protection systems
Issued 17 August 2024 Resolved
Fire protection systems and fire-fighting systems and appliances shall be maintained ready for use. PSCO observed a 6 ft high pile of unsorted garbage including hard plastic, food waste, paper, and other items in the recycling center. The pile of garbage extended into the recycling center blocking access to the space's fixed foam system activation point. Ship's crew stated that this system was not in accordance with the ship's procedures. 74 SOLAS 20 II-2/14.1.1
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 17 August 2024
Resolved 17 August 2024
Resolution: Resolved
09 - Working and Living Conditions › 092 - Working Conditions › Other (working space ILO)
Issued 17 August 2024 Resolved
Cylinders must always be secured and, when not in use, they must be stowed in a rack in an upright position, with the valve protection cap in place. PSCO observed eight full oxygen cylinders without protective caps on full cylinders. 46 CFR 147.60 b.
Condition: Placed in Improper Service
Action required: 17 - Rectify deficiencies prior to departure
Due 17 August 2024
Resolved 17 August 2024
Resolution: Rectified
07 - Fire Safety › N/A - No Subsystem › Operation of Fire protection systems
Issued 17 August 2024 Resolved
Fire protection systems and fire-fighting systems and appliances shall be maintained ready for use. PSCO observed fire suppression system in forward purifier room did not operate upon remote activation. The crew discovered the solenoid connector was loose at the valve. SOLAS 20 II-2/14.1.1
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 17 August 2024
Resolved 17 August 2024
Resolution: Rectified
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 17 August 2024 Resolved
Fire doors in main vertical zone bulkheads and stairway enclosures shall be self-closing and shall have an approximately uniform rate of closure of no more than 40 s and no less than 10 s. PSCO observed fire screen doors 01.05.05 and 5.03.03 did not close when tested. SOLAS 97 II-2/30.4.1 17 c
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 17 August 2024
Resolved 17 August 2024
Resolution: Rectified
11 - Life Saving Appliances › N/A - No Subsystem › Rescue boat inventory
Issued 17 August 2024 Resolved
All life-saving appliances and arrangements shall comply 74 with the applicable requirements of the Code. Except as otherwise stated, the normal equipment of every rescue boat shall consist of a searchlight with a horizontal and vertical sector of at least 6° and a measured luminous intensity of 2,500 cd which can work continuously for not less than 3 h. PSCO observed port side rescue boat searchlight inoperative. SOLAS 20 III/34 LSA Code 5.1.2.2.11 17 ac
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 17 August 2024
Resolved 17 August 2024
Resolution: Rectified
04 - Emergency Systems › N/A - No Subsystem › Abandon ship drills
Issued 17 August 2024 Resolved
Every crew member with assigned emergency duties shall be familiar with these duties before the voyage begins. Starboard midship life raft launching crew were not familiar with procedures for launching life raft as witnessed by PSCO during launching of the training life raft during abandon ship drill. 74 SOLAS 20 III/19.2.1
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 17 August 2024
Resolved 17 August 2024
Resolution: Rectified
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 17 August 2024 Resolved
All waste-receptacles shall be constructed of non-combustible materials with no openings in the sides or bottom. PSCO observed plastic waste-receptacles used with combustible materials in multiple galley spaces, and the ventilation officer office. 74 SOLAS 97 II-2/18.5
Condition: Placed in Improper Service
Action required: 16 - Rectify deficiencies w/in 14 days
Due 31 August 2024
Resolved 21 August 2024
Resolution: Ship provided proof that plastic garbage cans had been removed.
15 - Safety Management Systems (ISM) › N/A - No Subsystem › Maintenance of the ship and equipment
Issued 17 August 2024 Resolved
The company should establish procedures to ensure that the ship is maintained in conformity with the provisions of the relevant rules and regulations and with any additional requirements which may be established by the company. Following onboard procedures were not maintained in accordance with the vessels safety management system (SMS): 1. Garbage management plan, section 4.2.3 (Garbage assortment) - Garbage was left unassorted in recycling center and crew stairway. 2. SOLAS training manual, Section 4.11 (Instructions for Life Raft Preparation Party - Life raft deployment team displayed lack of familiarity during life raft deployment evolution. Crew needed assistance from shoreside safety management team to identify safety hazards and proper deployment procedures. 3. ), MED-4004 Medical Guide. Section 2.2 (Storage of Medical Gases) - Crew in charge of verifying storage of more that a dozen 100lbs pressurized storage tanks were unaware that they were stored incorrectly. Full oxygen tanks were stored without valve protection caps. Per staff, shoreside training did not provide accurate instructions on how to properly store the pressurized tanks. Due to multiple areas of the SMS system being affected, an external audit is required. 74 SOLAS 20 IX/3.1 ISM Code A.10.1
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 18 September 2024
Resolved 10 September 2024
Resolution: Received and review Flag state audit.
07 - Fire Safety › N/A - No Subsystem › Fire control plan
Issued 17 August 2024 Resolved
General arrangement plans shall be permanently exhibited for the guidance of the ship's officers, showing clearly for each deck the control stations, the various fire sections enclosed by "A" class divisions, the sections enclosed by "B" class divisions together with particulars of the fire detection and fire alarm systems the sprinkler installation, the fire-extinguishing appliances, means of access to different compartments, decks, etc., and the ventilating system, including particulars of the fan control positions, the position of dampers and identification numbers of the ventilating fans serving each section. PSCO observed a storage closet containing combustible materials in the crew office on deck 4 MVZ 5. The space was not outlined on the fire control plan with categorization nor did the space contain fire suppression or detection. 74 SOLAS 20 II-2/15.2.4.1
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 18 September 2024
Resolved 7 October 2024
Resolution: Class and flag approved changes to the ship's crew HR office closet to meet SOLAS. Fire Plan was amended.
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 17 August 2024 Resolved
Within the perimeter of such stairway enclosures, only public toilets, lockers of non-combustible material providing storage for non-hazardous safety equipment and open information counters are permitted. On deck 6,forward, by the bosun's store, PSCO observed plastic bins storing plastic bags of unsorted garbage. 74 SOLAS 97 II-2/29.2.
Condition: Placed in Improper Service
Action required: 10 - Deficiency Rectified
Due 17 August 2024
Resolved 17 August 2024
Resolution: Rectified
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 17 August 2024 Resolved
Cabin doors in ``B'' class divisions shall be of a self-closing type. Hold-backs are not permitted. PSCO observed cabin 3342 door unable to lock in the closed position. 74 SOLAS 97 II-2/31.1.2
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 17 August 2024
Resolved 17 August 2024
Resolution: Rectified
07 - Fire Safety › N/A - No Subsystem › Operation of Fire protection systems
Issued 6 September 2023 Resolved
Fire protection systems and fire-fighting systems and appliances shall be maintained ready for use. Fire extinguishers 1.IV.01 and 1.IV.07 were observed to be blocked in the engine control room. Additionally, fire station in the gym on deck 15 would not open due to handle falling off. Fire station on deck 14 zone 4 port side, near the pool and women's restroom was unable to open, the surrounding frame blocked fire station door from opening. 74 SOLAS 20 II-2/14.1.1 10c
Condition: Design Flaw
Action required: 10 - Deficiency Rectified
Due 6 September 2023
Resolved 6 September 2023
Resolution: Materials blocking fire extinguishers removed. Handle for fire station door in gym on deck 15 was replaced, allowing door to open. Lip to frame that blocked fire screen door was secured to frame, allowing fire station door to open.
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 6 September 2023 Resolved
The means of escape, including stairways and exits, shall be marked by lighting or photoluminescent strip indicators placed not more than 300 mm above the deck at all points of the escape route, including angles and intersections. Low location lighting was being blocked by insulation in the vicinity of FSD 08.1.04. In addition, low location lighting in the vicinity of semi-portable fire extinguisher 5.VI.11 on deck 5, was extinguished. 74 SOLAS 01 II-2/41-2.4.7 16ac
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 20 September 2023
Resolved 13 September 2023
Resolution: Received Flag Report and pictures attesting to repairs.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 6 September 2023 Resolved
Fire doors in main vertical zone bulkheads and stairway enclosures, remote-controlled sliding or power-operated doors shall be equipped with an alarm that sounds at least 5 s but no more than 10 s before the door begins to move and continues sounding until the door is completely closed. Numerous sliding doors including FSD 15/III/09, FSD 10/VII/05 & FSD 10.7.04 did not alarm for at least 5 s but no more than 10 s before the doors began to move. 74 SOLAS 97 II-2/30.4.2 16ac
Condition: Design Flaw
Action required: 16 - Rectify deficiencies w/in 14 days
Due 20 September 2023
Resolved 11 September 2023
Resolution: Received report attesting to repair of doors.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Operation of machinery
Issued 6 September 2023 Resolved
The machinery, boilers and other pressure vessels, associated piping systems and fittings shall be of a design and construction adequate for the service for which they are intended and shall be so installed and protected as to reduce to a minimum any danger to persons on board, due regard being paid to moving parts, hot surfaces and other hazards. PSCO observed soft patch on jacket water plate cooler salt water discharge lin. 74 SOLAS 04 II-1/26.1 16ac
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 20 September 2023
Resolved 13 September 2023
Resolution: Received Flag Report and images attesting to repairs.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 6 September 2023 Resolved
It shall be possible for each door to be opened and closed from each side of the bulkhead by one person only. FSD 15/III/09, FSD 10/VII/05 & FSD 10.7.04 would not close when manual release was activated. Additionally, FSD 15/III/09 & FSD 10/7/04 would not open once closed while the manual release was activated. 74 SOLAS 97 II-2/30.3 40ac
Condition: Improper/Lack of Maintenance
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 13 September 2023
Resolution: Received report attesting to repair of doors.
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 6 September 2023 Resolved
Additionally, escape route signs and fire equipment location markings shall be of photoluminescent material or marked by lighting. Emergency escape signage IVO lifeboat 19 was extinguished. 74 SOLAS 01 II-2/41-2.4.7 10c
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 6 September 2023
Resolved 6 September 2023
Resolution: Sign was repaired so it illuminated.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 6 September 2023 Resolved
All "A" class doors located in stairways, public spaces and main vertical zone bulkheads in escape routes shall be equipped with a self-closing hose port of material, construction and fire resistance which is equivalent to the door into which it is fitted. Hose port in FSD 06.2.06 was not self-closing and remained open when the door was closed. 74 SOLAS 97 II-2/30.7 10c
Action required: 10 - Deficiency Rectified
Due 6 September 2023
Resolved 6 September 2023
Resolution: Hose port was repaired so that it would close.
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 6 September 2023 Resolved
The arrangements for the storage, distribution and utilization of oil used shall be such as to ensure the safety of the ship and persons onboard. PSCO observed oiil accumulation below main engine #1. 74 SOLAS 97 II-2/15.2 10c
Action required: 10 - Deficiency Rectified
Due 6 September 2023
Resolved 6 September 2023
Resolution: Oil was removed beneath main engine #1.
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 17 May 2023 Resolved
The means of escape, including stairways and exits shall be marked by lighting or photoluminescent strop indicators...at all points of the escape route including angles and intersections. Low location lighting on deck 7, aft IVO the atrium and mid passenger stair tower was extinguished. 74 SOLAS 97 II-2/28.1.10
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 21 June 2023
Resolution: Photos received of energized LLL.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 17 May 2023 Resolved
Crew members shall be trained to be familiar with the arrangements of the ship as well as the location and operation of any fire-fighting systems and appliances that they may be called upon to use. Two crewmembers in the dishwashing area deck 14, aft were unfamiliar with shipboard procedures in the event of a fire. In addition , during the fire drill, two crewmember in the cabins directly outside of the crew laundry (deck 4, fwd) were unfamiliar with shipboard procedures in the event of a fire. Furthermore, in the main laundry room, one crewmember was unfamiliar with the operation of firefighting appliances. 74 SOLAS 20 II-2/15.2.2.1
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 21 June 2023
Resolution: Training completed.
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 17 May 2023 Resolved
All escape route signs...shall be of photoluminescent material or marked by lighting. Backstage Princess Theater exit signage was not visible. In addition, emergency exit sign in the backstage area of the Vista Lounge was extinguished. 74 SOLAS 97 II-2/28.1.10
Action required: 10 - Deficiency Rectified
Resolved 17 May 2023
11 - Life Saving Appliances › N/A - No Subsystem › Embarkation arrangement survival craft
Issued 17 May 2023 Resolved
Muster and embarkation stations shall be adequately illuminated by lighting supplied from the emergency source of electrical power. Two embarkation lights on the port side were extinguished. 74 SOLAS 97 III/11.4
Action required: 10 - Deficiency Rectified
Resolved 17 May 2023
11 - Life Saving Appliances › N/A - No Subsystem › Lifeboats
Issued 11 September 2022 Resolved
Lifeboats should demonstrate that the gearbox and gearbox train are engaging satisfactorily. Lifeboat #12 would not engage in reverse while testing propulsion with vessel in the cradle. SOLAS 97 III/19
Action required: 10 - Deficiency Rectified
Resolved 11 September 2022
Resolution: Lubricated and re-tested.
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 11 September 2022 Resolved
The addition to the emergency lighting required...The marking must enable passengers to identify all the routes of escape and readily identify the escape exits. The men's and women's changing areas in the spa had no escape signage. SOLAS 97 II-2/28
Action required: 10 - Deficiency Rectified
Resolved 11 September 2022
Resolution: Signage added.
07 - Fire Safety › N/A - No Subsystem › Ready availability of fire fighting equipment
Issued 11 September 2022 Resolved
Fire-fighting systems and appliances shall be kept in good working order and readily available for immediate use. Aftmost fire station on the 17th deck, starboard side was inaccessible due to a seized latch on the access door. SOLAS 20 II-2/14.2.1.2
Action required: 10 - Deficiency Rectified
Resolved 11 September 2022
Resolution: Latch repaired.
11 - Life Saving Appliances › N/A - No Subsystem › Operation of Life Saving Appliances
Issued 11 September 2022 Resolved
Every crew member with assigned emergency duties shall be familiar with these duties before the voyage begins. The life boat #8 commander was not familiar with the starting procedures for life boat engine. SOLAS 20 III/19.2.1
Action required: 10 - Deficiency Rectified
Resolved 11 September 2022
Resolution: Crew member instructed on how to start lifeboat.
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 11 September 2022 Resolved
Above the bulkhead deck there shall be at least two means of escape from each main vertical zone or similarly restricted space. The pantry adjacent to the Oasis bar on the 17th deck was blocked at both exit locations. SOLAS 97 II-2/28
Action required: 10 - Deficiency Rectified
Resolved 11 September 2022
Resolution: Removed stored items from space.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 15 March 2022 Resolved
All electrical apparatus shall be so constructed and so installed as not to cause injury when handled or touched in the normal manner. Light in the male sauna lacking protective cover. 74SOLAS(04)II-1/45
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 15 April 2022
Resolved 25 March 2022
Resolution: Received Class report attesting to satisfactory repairs.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 15 March 2022 Resolved
All electrical apparatus shall be so constructed and so installed as not to cause injury when handled or touched in the normal manner. Dead end wires found on the lighting mount in fan room next to CO2 space. 74SOLAS(04)II-1/45
Action required: 50 - Rectify deficiencies w/in 30 days
Due 15 April 2022
Resolved 25 March 2022
Resolution: Received Class report attesting to satisfactory repairs.
07 - Fire Safety › N/A - No Subsystem › Ready availability of fire fighting equipment
Issued 15 March 2022 Resolved
Fire-fighting systems and appliances shall be kept in good working order and readily available for immediate use. Portable extinguishers which have been discharged shall be immediately recharged or replaced with an equivalent unit. CO2 door unopenable due to corroded locking mechanism. 74SOLAS(20) II-2/14.2.1.2
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 15 March 2022
Resolved 15 March 2022
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 15 March 2022 Resolved
Openings in "A" class divisions. Fire door 14.501 could not close due to the kick plate getting caught. 74SOLAS(97)II-2/30
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 15 March 2022
Resolved 15 March 2022
14 - Pollution Prevention › 148 - Ballast Water › Ballast water report
Issued 24 January 2022 Resolved
For any vessel that is equipped with ballast water tanks and bound for ports or places in the United States and not addressed in paragraph (b)(1) and (2) of this section submit a ballast water report no later than 6 hours after arrival at the port or place of destination, whichever is earlier. NBIC report not submitted for separate port calls within Honolulu COTP zone.
Condition: Design Flaw
Action required: 10 - Deficiency Rectified
Due 24 January 2022
Resolved 24 January 2022
Resolution: Safety Officer submitted ballast water report to NBIC for each port in Hawaii.
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 17 September 2021 Resolved
Materials used in the ships' structure shall ensure that the structural integrity is not degraded due to fire. Structural fire protection insulation found damaged in space with sprinkler section valve 20.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 17 October 2021
Resolved 27 September 2021
Resolution: Damaged insulation was replaced with new insulation material. Repairs were examined by class and found satisfactory.
04 - Emergency Systems › N/A - No Subsystem › Low level lighting in corridors
Issued 17 September 2021 Resolved
The means of escape, including stairways and exits, shall be marked by lighting or photoluminescent strip indicators placed not more than 300 mm above the deck at all points of the escape route, including angles and intersections. A section of low location lights in deck 5, zone 1, port side, near the crew cabins were inoperable.
Action required: 10 - Deficiency Rectified
Resolved 17 September 2021
Resolution: Vessel replaced the low location light strip.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 17 September 2021 Resolved
Detection and alarm. Non operational heat detector in the sauna space.
Action required: 10 - Deficiency Rectified
Resolved 17 September 2021
Resolution: Heat detector was replaced with a new heat detector.
07 - Fire Safety › N/A - No Subsystem › Fire pumps and its pipes
Issued 21 July 2019 Resolved
Relief valves shall be provided in conjuction with all fire pumps if the pumps are capable of developing a pressure exceeding the design pressure. Pumps 02 and 03 are not equipped with relief valves. SOLAS(1997) II-2 / 4.3.5
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 20 August 2019
Resolved 8 August 2019
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 21 July 2019 Resolved
Means shall be provided to control leaks of flammable liquids. The after starboard engine space bilges had substantial amounts of oil in the bilge. SOLAS(2014) II-2 / 4.1.1
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 4 August 2019
Resolved 9 August 2019
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 21 July 2019 Resolved
The construction of floors and doorframes in "A" class divisions, with the means of securing them when closed, shall provide resistance to fire as well as to the passage of smoke. Fire screen door FS006.1.08 failed to latch. SOLAS(2014) II-2/4.1.1.2
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 21 July 2019
Resolved 21 July 2019
07 - Fire Safety › N/A - No Subsystem › Division - decks, bulkheads and penetrations
Issued 21 July 2019 Resolved
The minimum fire integrity of all bulkheads and decks shall be prescribed in tables 23.1 to 23.4. Combustible material has been impermissably stored in category 10 and category 3 spaces, changing their categorization. SOLAS(1997) II-2 / 26.2
Condition: Placed in Improper Service
Action required: 10 - Deficiency Rectified
Due 21 July 2019
Resolved 21 July 2019
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 21 July 2019 Resolved
The means of escape, including stairways and exits, shall be marked by lighting or photoluminescent step indicators. Multiple escape routes are missing low locating lighting. SOLAS(1997)II-2/28.1.10
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 21 July 2019
Resolved 21 July 2019
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 21 July 2019 Resolved
All waste receptacles shall be constructed of non-combustable materials with no openings in the sides or bottom. A paper waste receptacle is present in the international cafe pantry.
Condition: Placed in Improper Service
Action required: 10 - Deficiency Rectified
Due 21 July 2019
Resolved 21 July 2019
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 21 July 2019 Resolved
Each notice of arrival must contain all of the information items specified in table 160.206, uncluding the name and 24-hour contact information for the Company Security Officer. The vesse's NOA listed the Vessel Security Officer in lieu of the CSO.
Condition: Placed in Improper Service
Action required: 10 - Deficiency Rectified
Due 21 July 2019
Resolved 21 July 2019
11 - Life Saving Appliances › N/A - No Subsystem › Operational readiness of lifesaving appliances
Issued 29 December 2018 Resolved
Before the ship leaves port and at all times during the voyage, all life-saving appliances shall be in working order and ready for immediate use. Found an inoperable davit for lifeboat number 14 on the port side. The crew is unable to launch or recover lifeboat number 14. The Administration may permit the substitution of lifeboats by liferafts of equivalent total capacity provided that there shall never be less than sufficient lifeboats on each side of the ship to accommodate 37.5% of the total number of persons on board in accordance with SOLAS 1997 cons. Ch. III Reg 20. Total number of persons on board equals 3893 persons.
Action required: 10 - Deficiency Rectified
Due 29 December 2018
Resolved 29 December 2018
Resolution: Crew performed maintenance. Lowered lifeboat to water and maneuvered. Retrieved lifeboat.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 29 December 2018 Resolved
The construction of all doors and door frames in "A" class divisions, with the means of securing them when closed, shall provide resistance to fire as well as to the passage of smoke and flame, as far as practicable, equivalent to that of the bulkheads in which the doors are situated. Crew members were unable to latch the incinerator space fire door, 4-6-45, closed after multiple attempts and maintenance.
Action required: 10 - Deficiency Rectified
Due 29 December 2018
Resolved 29 December 2018
Resolution: The crew performed maintenance and proved operation of the fire door.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 29 December 2018 Resolved
Each separate circuit shall be protected against short circuit or overload. Multi-outlet adapters (power strips) found connected to other adapters (“daisy-chained”), or otherwise used in a manner that could overload the capacity of a receptacle on Deck 6 in the computer officer room, 6227.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 12 January 2019
Resolved 7 January 2019
Resolution: The multi-outlet power strips have now been connected individually to single outlets thereby preventing overload of the receptables within the Computer Officer Room 6227 and found to be satisfactory.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 29 December 2018 Resolved
Cables and wiring shall be installed and supported in such a manner as to avoid chafing or other damage. The mounting bracket for the port side rescue boat shore power electrical outlet was found wasted/corroded. Further corrosion damage to the mounting bracket may result in damage to the shore power electrical outlet.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 29 January 2019
Resolved 7 January 2019
Resolution: The mounting brackets and the shore power electrical outlet have now been renewed and were found to be secure and satisfactory.
07 - Fire Safety › N/A - No Subsystem › Division - decks, bulkheads and penetrations
Issued 8 August 2018 Resolved
07103- Division - bulkheads - Bulkheads forming fire boundaries between category (13) storerooms and category (8) public spaces shall be of "A-15" rating. The boundary between the disco and the pantry storeroom on deck 15, port, frames 38-43 is indicated on the SFP plan as being of "A-0" rating. - 74 SOLAS (97) II-2/26.1 - 50ac
Action required: 50 - Rectify deficiencies w/in 30 days
Due 8 September 2018
Resolved 29 August 2018
Resolution: MSC receievd satisfactory drawings indicating correct SFP arrangement.
Lifesaving › Lifeboat › Propulsion Starting System
Issued 20 June 2018 Resolved
0610: Before the ship leaves port and at all times during the voyage, all life-saving appliances shall be in working order and ready for immediate use. Lifeboat 4 was not capable of starting during the lifeboat drill. 74 SOLAS 2014 Ch. III 20.2
Action required: 10 - Deficiency Rectified
Due 20 June 2018
Resolved 20 June 2018
Resolution: Vessel replaced starter. tested all sat.
Fire Fighting › Structural - A Class Divisions › Fire Doors
Issued 10 August 2017 Resolved
0710 - Sliding fire doors in main vertical zone bulkheads and stairway enclosures designed to re-open upon contacting an object in its path shall re-open sufficiently to allow a clear passage of at least 0.75 m but no more than 1 m. FSD 07\II\10 & 11 are sliding doors which opens more than 1m when contacting an object in its path. - 74 SOLAS (97) Ch. II-2 Reg. 30.4.2 - 50abc
Action required: 705 - Other - as specified
Due 19 September 2017
Resolved 19 September 2017
Resolution: Sliding fire door fixed by techs and tested to Class and CG satisfaction.
Fire Fighting › Structural - A Class Divisions › Fire Doors
Issued 10 August 2017 Resolved
0710 - Fire doors in main vertical zone bulkheads and stairway enclosures shall be self-closing and double-leaf doors equipped with a latch necessary to their fire integrity shall have a latch that is automatically activated by the operation of the doors when released by the system. FSD 11.4.06, 14.7.07, 04.3.05 & 06.7.05 did not self close. - 10c - 74 SOLAS (97) Ch. II-2 Reg. 30.4.1,5
Action required: 705 - Other - as specified
Resolved 10 August 2017
Resolution: Corrected on the spot.
Construction/Loadline › Hull › Hull Plating
Issued 6 December 2016 Resolved
Found the tender platform located starboard side, between frames 156 and 164, hanging from hinges. Found upon internal examination located aft laundry store space in way of the centre hinge a hole approximately 10cm that was temporarily plugged to stop water ingress
Due 6 December 2016
Resolved 7 December 2016
Resolution: Recieved class statement attesting to satisfactory repairs.
Operations/Management › Drills/Instruction › Safety Orientation
Issued 3 August 2016 Resolved
0900 - Safety in General - On-board training and instructions in the use of life saving appliances...and fire extinguishing appliances shall be given as soon as possible. 2nd boat commanders unable to demonstrate competence in operating life boat systems, including emergency steering, bilge pumps and turning on engines. Cooks were unable to demonstrate usage of installed firefighting systems.
Action required: 705 - Other - as specified
Due 17 August 2016
Resolved 12 August 2016
Resolution: Attended vessels and verified crew training by randomly questioning the galley and lifeboat crews, all sat.
Fire Fighting › Structural Fire Protection - General › Cooking Area
Issued 3 August 2016 Resolved
0710 - Fire Prevention - The condition of the ship shall be maintained to conform with the provisions of the regulations to ensure that the ship in all respects will remain fit to proceed to sea...main galley, deck 5, Chef's Office window covered, reducing communicable openings to below 30%. SOLAS 74 (1997 Cons) Ch I Reg 11. 10c.
Action required: 705 - Other - as specified
Due 3 August 2016
Resolved 3 August 2016
Resolution: Vessel removed items that were obstructing communicable openings.
Engineering › Thrusters › Piping
Issued 24 April 2016 Resolved
2050:Machinery, bilers, and other pressure vessels, associated piping systems and fittings shall be of a design and construction for the service for which they are intended. Vessel's bow thruster #2 has an internal hydraulic oil leak and is inoperable. 74 SOLAS (14) 11-1/26.1
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 23 May 2016
Resolved 12 May 2016
Resolution: Class Survey was provided.

Ownership record

The Coast Guard's documentation record for this hull -- the Abstract of Title, with its owners and liens as filed -- is not in PSIX. Ask, and Maury buys it from the National Vessel Documentation Center, files it here with its date, and every reader of this page gets it.