G.L. 10

Built
1978
Last inspected
26 July 2021
Controls
None recorded without a removal date

This record may be incomplete: the most recent inspection recorded for this vessel was 5 years ago. Maury shows what the Coast Guard recorded, not whether the vessel has been inspected since, is still in service, or what condition it is in. Coast Guard record current through 23 August 2026, retrieved 5 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard.

Inspection record

Last inspected 26 July 2021
…with no type recorded6
Operational controls None recorded without a removal date
Years with a record 10 calendar years (1987–2021)
Every line above is a count of records the US Coast Guard wrote, or a date it recorded. A blank resolution means none was recorded in this data; it does not establish that a deficiency is outstanding. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Identity

Flag
UNITED STATES
Tonnage
2601 - Convention (Subpart B), Gross Ton 780 - Convention (Subpart B), Net Ton
Maury page id
psix-49552
Vessel history report
Every record for this hull, in one document — $299

Every recorded inspection, 1972 to 2026, in one chronology · every deficiency, with system, dates and resolution · operational controls imposed and removed · every name this hull has been recorded under · the vessels it was inspected alongside, and when · how its record compares with hulls of similar age and size, as a fact about the population and never a judgement about this vessel.

Read one first, in full: a forty-year chronology · a hull that changed operators four times · the sparse case, shown as an example, not for sale.

This report is in development and is not for sale yet. There is no date, and nothing is charged. Leave an email and we will tell you when it exists, once.

Inspected as a tow unit · 3

The Coast Guard recorded this vessel and the following in the same inspection activity — normally a tug and the barges in its tow. Only barges and towing vessels are in this archive, so any other vessel type in the same activity does not appear here: these lists are a floor, not a complete manifest.

MISS OCIE Towing Vessel · MISLE 71496 · 10 October 1995 · activity 22549CAPT. MARK Towing Vessel · MISLE 74112 · 10 October 1995 · activity 22549RACHAEL Towing Vessel · MISLE 98597 · 10 October 1995 · activity 22549

Inspection history · 20

26 July 2021 Administrative Inspection
Administrative · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 7268570
6 June 2019 Administrative Inspection · Internal Structural Exam · Drydock Exam
Physical examination · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 6705251
10 September 2018 Re-Inspection · Annual Inspection · MARPOL Annex I Examination · Deficiency Check · Plan Review (Other than "T")
Physical examination · Sector Charleston · USCG Southeast District (CGD-SE) · Activity 6537613
8 December 2017 Administrative Inspection
Administrative · Activities Europe · Activity 6320768
4 June 2017 Internal Structural Exam · Drydock Exam
Physical examination · Activities Europe · Activity 6092406
31 May 2017 MARPOL Annex I Examination · COI Inspection · MTSA/ISPS Verification
Physical examination · Activities Europe · Activity 6160980
25 October 2016 Administrative Inspection
Administrative · Activities Europe · Activity 6029028
15 March 2016 MTSA/ISPS Verification · Annual Inspection
Physical examination · Activities Europe · Activity 5833344
10 November 2015 Deficiency Check
Physical examination · Activities Europe · Activity 5760867
27 September 2015 Administrative Inspection · Drydock Exam · Internal Structural Exam
Physical examination · Activities Europe · Activity 5719021
29 June 2015 Deficiency Check · Administrative Inspection
Physical examination · Activities Europe · Activity 5167269
28 April 2015 Internal Structural Exam · Plan Review (Other than "T") · COI Inspection
Physical examination · Activities Europe · Activity 5112190
3 November 1998 Type not recorded
No type recorded · MSO JACKSONVILLE · USCG Southeast District (CGD-SE) · Activity 803603
29 September 1998 Type not recorded
No type recorded · MSO JACKSONVILLE · USCG Southeast District (CGD-SE) · Activity 200857
29 September 1998 Type not recorded
No type recorded · MSO JACKSONVILLE · USCG Southeast District (CGD-SE) · Activity 757436
22 November 1995 Type not recorded
No type recorded · MSO JACKSONVILLE · USCG Southeast District (CGD-SE) · Activity 881480
10 October 1995 Type not recorded
No type recorded · MSO JACKSONVILLE · USCG Southeast District (CGD-SE) · Activity 22549
5 October 1995 Type not recorded
No type recorded · MSO JACKSONVILLE · USCG Southeast District (CGD-SE) · Activity 874173
9 May 1988 Administrative
Administrative · MSO TAMPA · USCG Southeast District (CGD-SE) · Activity 1346250
16 January 1987 Hull Examination · COI Inspection
Physical examination · MSU GALVESTON · USCG Heartland District (CGD-H) · Activity 1015844

Deficiency record · 20

Lifesaving › Inflatable Liferafts › Servicing
Issued 25 October 2016 Resolved
Issued 835 extending liferaft servicing date for 5 months or until next scheduled vessel exam whichever comes first as per 46 CFR 199.190(g).
Action required: 705 - Other - as specified
Due 30 April 2017
Resolved 16 July 2017
Resolution: Completed
Fire Fighting › Portable Dry Chemical Fire Extinguisher › Approval
Issued 28 March 2016 Resolved
Remove 3 non CG approved fire extinguishers and replace with CG approved Extinguishers and w/ proper brackets.
Due 28 April 2016
Resolved 4 May 2016
Resolution: Replaced with CG approved extinguishers.
Engineering › Pressure Vessel › Marking and Stamping
Issued 28 March 2016 Resolved
Provide S/N, tank capacity, manufacturer and pressure relief valve setting for all installed air receivers.
Due 28 April 2016
Resolved 4 May 2016
Resolution: Vessel provided all the correct information of air receivers and installed relief valves.
Stability › Watertight Integrity › General
Issued 28 March 2016 Resolved
Ensure all water tight doors below deck are properly labeled and closed while underway.
Due 28 April 2016
Resolved 4 May 2016
Resolution: Labeled all WTD.
Navigation › Collision/Grounding Avoidance › Navigation Lights
Issued 28 March 2016 Resolved
Provide working Nav lights.
Due 28 April 2016
Resolved 4 May 2016
Resolution: Replaced all Nav lights.
Construction/Loadline › Hull › Bottom Plating
Issued 4 October 2015 Resolved
Provide ABS report for all weld testing below the waterline
Action required: 705 - Other - as specified
Due 30 November 2015
Resolved 22 November 2015
Resolution: ABS report received and found satisfactory.
Construction/Loadline › Hull › Weld
Issued 4 October 2015 Resolved
Provide report to USCG of testing of all welding conducted on the deck.
Action required: 705 - Other - as specified
Due 30 November 2015
Resolved 22 November 2015
Resolution: Received satisfactory report from ABS.
Construction/Loadline › Hull › Weld
Issued 4 October 2015 Resolved
Make repairs to wasted bulkheads, frames, and stiffeners in #10 Port Inner, #10 Port Outer, #11 Starboard Inner and #11 Starboard Outer.
Action required: 705 - Other - as specified
Due 30 November 2015
Resolved 22 November 2015
Resolution: All required steel replacement completed.
Construction/Loadline › Structures › Longitudinal Bulkhead
Issued 28 April 2015 Resolved
08 A trusses installed in the tanks below the accommodation modules are not installed IAW approved plans. Ensure fit-up, installation & fabrication are in accordance with approved weld procedures & installation plans. Complete to satisfaction of attending inspector or class society. Current installation not accepted due to poor fit-up, "jet rodding," slag inclusion, & bad welding technique. Approv
Action required: 705 - Other - as specified
Due 24 July 2015
Resolved 4 July 2015
Resolution: ABS reported that welding was inspected and meets ABS standards.
Construction/Loadline › Hull › Hull Plating
Issued 28 April 2015 Resolved
Blast and remove excess rust in all tanks from 09 forward; tanks include 09, 10 & 11 (port & STBD- inner and outer)
Action required: 705 - Other - as specified
Due 19 May 2016
Resolved 3 October 2015
Resolution: Areas have been blasted revealing numerous area to crop and renew in 4 voids.
Construction/Loadline › Structures › Trunk
Issued 28 April 2015 Resolved
Replace void access ladders indicated during internal exam. Ladders with steel wastage beyond 25% shall be replaced to the satisfaction of the attending MI. Note; 9, 10 & 11 port/STBD-inner and outer.
Action required: 705 - Other - as specified
Due 16 May 2016
Resolved 22 November 2015
Resolution: Void access ladders were replaced.
Construction/Loadline › Hull › Hull Plating
Issued 28 April 2015 Resolved
Conduct complete gauging of the barge.
Action required: 705 - Other - as specified
Due 16 May 2016
Resolved 22 November 2015
Resolution: Gauging report recieved and found satisfactory
Accommodation/Occupational Safety › Sleeping Accommodations › Berth
Issued 28 April 2015 Resolved
Secure catwalk to the accomodations.
Action required: 705 - Other - as specified
Due 27 June 2015
Resolved 19 June 2015
Documentation › Safety/Response Plans/Programs › Fire Control Plans
Issued 28 April 2015 Resolved
Update and submit FCP for approval…include life jacket storage boxes and firefighting suit/berthing apparatus. Place update fire plans in accommodation modules.
Action required: 705 - Other - as specified
Due 27 June 2015
Resolved 26 June 2015
Resolution: Received updated Fire and Safety Plan
Accommodation/Occupational Safety › Sleeping Accommodations › Berth
Issued 28 April 2015 Resolved
Remove all exit signs and bar locks from disable doors in accommodation modules. Ensure doors are not mistaken for actual exits in an emergency.
Action required: 705 - Other - as specified
Due 3 June 2015
Resolved 31 May 2015
Fire Fighting › Structural Fire Protection - General › Accommodation Space Protection
Issued 28 April 2015 Resolved
Fire control panel: as per operational manual, "the fire alarm devices shall operate in line with panel configuration as per the manufacture installation and testing manual."
Action required: 705 - Other - as specified
Due 27 June 2015
Resolved 31 May 2015
Electrical › Electric Generation Source (emergency) › Panelboard
Issued 28 April 2015 Resolved
Label all emergency lighting in accommodation modules with "E"
Action required: 705 - Other - as specified
Due 27 June 2015
Resolved 31 May 2015
Electrical › Electric Generation Source (emergency) › Circuit Breaker
Issued 28 April 2015 Resolved
Label all emergency shut down on the outside of each accommodation module.
Action required: 705 - Other - as specified
Due 3 June 2015
Resolved 31 May 2015
Electrical › Electrical Distribution System (service) › Cable
Issued 28 April 2015 Resolved
Ensure the stuffing tube boundary IWO electrical cable penetration through A-60 boundary to accommodation module meets A-6 requirements.
Action required: 705 - Other - as specified
Due 27 June 2015
Resolved 31 May 2015
Electrical › Electric Generation Source (service) › Panelboard
Issued 28 April 2015 Resolved
Label electrical pabnel for accommodation modules.
Action required: 705 - Other - as specified
Due 27 June 2015
Resolved 31 May 2015