BARANOF DREAM

Built
1980
Last inspected
18 March 2026
Documentation
Valid · NVDC file of 10 August 2026
Controls
None recorded without a removal date

Coast Guard record current through 23 August 2026, retrieved 5 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Passenger Ship class in Maury's sources begin in 2016.

Inspection record

Last inspected 18 March 2026
…with no type recorded1
Operational controls None recorded without a removal date
Years with a record 11 calendar years (2016–2026)
Every line above is a count of records the US Coast Guard wrote, or a date it recorded. A blank resolution means none was recorded in this data; it does not establish that a deficiency is outstanding. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Identity

WDG8058
Flag
UNITED STATES
Maury page id
psix-52041

Documentation record

Registered dimensions (L × B × D)123.5 ft × 28.0 ft × 6.8 ft
Registered tonnagegross 97 / net 84
ITC dimensions (L × B × D)Not recorded
ITC tonnageNot recorded
BuilderBLOUNT MARINE CORP · WARREN, RI, UNITED STATES · built 1980
Hull materialSteel
PropulsionDiesel Reduction
Hull shapeUNSPECIFIED
Hull configurationUNSPECIFIED
Hailing portSITKA, AK
Endorsements, as the file codes themcw_un, reg
DocumentationValid · issued 3 July 2026 · expires 31 July 2027
Service, as the file records itPassenger (Inspected)
Hull formpowered (Maury's inference from propulsion, hull shape, material and length, rule hf-1; not a recorded fact)
Tonnage as PSIX records it97 - Regulatory (Subpart C or D), Gross Ton
84 - Regulatory (Subpart C or D), Net Ton
158 - Displacement, Ton
Every line above is a field of the National Vessel Documentation Center's file as served by NOAA Fisheries, dated 10 August 2026, matched to this hull on its Official Number. Registered and ITC measurements are two systems and are never combined. One snapshot is held so far; documentation history begins with the next.
Professional
The full record for this vessel

Behind this panel: 31 inspections, each with its date, unit and type; 91 deficiencies with the resolution recorded against each; operational controls, none recorded without a removal date; no tow-unit appearances recorded; 1 other recorded name; the documentation record: dimensions, tonnage, builder, hailing port and endorsements. Every line is a record the Coast Guard wrote; the counts above are the same counts as in the summary, and they are free.

Professional is $39 a month or $299 a year, or $19.99 a month locked for life at the founding rate, for the first 200 subscribers. It unlocks every detail section on every vessel page, fleet watch tied to your account, and ownership records on request. Already a subscriber? Sign in.

Maury does not score, rate or grade vessels, at any price.

Vessel history report
Every record for this hull, in one document — $299

Every recorded inspection, 1972 to 2026, in one chronology · every deficiency, with system, dates and resolution · operational controls imposed and removed · every name this hull has been recorded under · the vessels it was inspected alongside, and when · how its record compares with hulls of similar age and size, as a fact about the population and never a judgement about this vessel.

Read one first, in full: a forty-year chronology · a hull that changed operators four times · the sparse case, shown as an example, not for sale.

This report is in development and is not for sale yet. There is no date, and nothing is charged. Leave an email and we will tell you when it exists, once.

Inspection history · 31

18 March 2026 Administrative Inspection
Administrative · Marine Safety Detachment Sitka · USCG Arctic District (CGD-A) · Activity 8328407
3 November 2025 Vessel Attendance · Examination of Repairs · Hull Examination · Internal Structural Exam
Physical examination · Marine Safety Detachment Sitka · USCG Arctic District (CGD-A) · Activity 8264288
5 May 2025 Annual Inspection · Internal Structural Exam · Deficiency Check
Physical examination · Marine Safety Detachment Sitka · USCG Arctic District (CGD-A) · Activity 8129338
25 June 2024 Administrative Inspection
Administrative · Marine Safety Detachment Sitka · USCG Arctic District (CGD-A) · Activity 7948223
14 May 2024 Deficiency Check · Annual Inspection
Physical examination · Marine Safety Detachment Sitka · USCG Arctic District (CGD-A) · Activity 7912997
17 November 2023 Administrative Inspection · Special Consideration · In-Service Inspection
Physical examination · Marine Safety Detachment Sitka · USCG Arctic District (CGD-A) · Activity 7836746
16 November 2023 Examination of Repairs · Hull Examination · Internal Structural Exam
Physical examination · Marine Safety Detachment Sitka · USCG Arctic District (CGD-A) · Activity 7826827
14 September 2023 Deficiency Check · Examination of Repairs · Administrative Inspection
Physical examination · Marine Safety Detachment Sitka · USCG Arctic District (CGD-A) · Activity 7791799
3 September 2023 Type not recorded
No type recorded · Station Ketchikan · USCG Arctic District (CGD-A) · Activity 7784417
3 September 2023 Damage Survey · Administrative Inspection
Physical examination · Marine Safety Detachment Ketchikan · USCG Arctic District (CGD-A) · Activity 7784637
13 July 2023 Deficiency Check · Damage Survey
Physical examination · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7742800
9 May 2023 Deficiency Check · Annual Inspection
Physical examination · Marine Safety Detachment Sitka · USCG Arctic District (CGD-A) · Activity 7685319
30 May 2022 Deficiency Check · Administrative Inspection · COI Inspection
Physical examination · Marine Safety Detachment Sitka · USCG Arctic District (CGD-A) · Activity 7460718
29 September 2021 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7353783
1 April 2021 Administrative Inspection · Examination of Repairs · Hull Examination · Internal Structural Exam
Physical examination · Marine Safety Detachment Sitka · USCG Arctic District (CGD-A) · Activity 7167244
6 March 2021 In-Service Inspection
Physical examination · Marine Safety Detachment Sitka · USCG Arctic District (CGD-A) · Activity 7151218
28 May 2020 Administrative Inspection
Administrative · Marine Safety Detachment Sitka · USCG Arctic District (CGD-A) · Activity 6962945
7 April 2020 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6936654
1 October 2019 In-Service Inspection
Physical examination · Marine Safety Detachment Sitka · USCG Arctic District (CGD-A) · Activity 6826899
8 May 2019 Deficiency Check
Physical examination · Marine Safety Detachment Sitka · USCG Arctic District (CGD-A) · Activity 6680594
5 April 2019 Annual Inspection
Physical examination · Marine Safety Detachment Sitka · USCG Arctic District (CGD-A) · Activity 6658241
28 March 2019 Deficiency Check
Physical examination · Marine Safety Detachment Sitka · USCG Arctic District (CGD-A) · Activity 6651702
30 January 2019 Hull Examination · Internal Structural Exam · Deficiency Check
Physical examination · Marine Safety Detachment Sitka · USCG Arctic District (CGD-A) · Activity 6618298
9 October 2018 In-Service Inspection
Physical examination · Marine Safety Detachment Sitka · USCG Arctic District (CGD-A) · Activity 6558834
12 April 2018 COI Inspection
Physical examination · Marine Safety Detachment Sitka · USCG Arctic District (CGD-A) · Activity 6392754
11 October 2017 In-Service Inspection
Physical examination · Marine Safety Detachment Sitka · USCG Arctic District (CGD-A) · Activity 6287189
10 July 2017 Deficiency Check
Physical examination · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 6206801
10 April 2017 Deficiency Check · Annual Inspection
Physical examination · Marine Safety Detachment Sitka · USCG Arctic District (CGD-A) · Activity 6121372
24 January 2017 Internal Structural Exam · Hull Examination
Physical examination · Marine Safety Detachment Sitka · USCG Arctic District (CGD-A) · Activity 6077300
11 May 2016 Deficiency Check
Physical examination · Marine Safety Detachment Sitka · USCG Arctic District (CGD-A) · Activity 5875477
2 May 2016 Annual Inspection · DAPI Audit
Physical examination · Marine Safety Detachment Sitka · USCG Arctic District (CGD-A) · Activity 5872507

Deficiency record · 91

99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 9 May 2025 Resolved
The cognizant OCMI may require that a vessel and its equipment undergo any additional test or inspection deemed reasonable and necessary to determine that the vessel and its equipment are suitable for the service in which they are to be employed. Make ready for inspection and testing the following items: Watchman alarm, interconnected fire detection system, installed liferafts, fire pump and hoses, emergency lighting, fixed fire fighting system shutdowns. 46 CFR 176.840
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 12 May 2025
Resolution: All required items were available for testing and testedx SAT.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 9 May 2025 Resolved
Each length of hose must: (1) Be lined commercial fire hose that conforms to Underwriters' Laboratories, Inc., Standard 19 or Federal Specification ZZ-H-451E. A hose that bears the Label of Underwriters' Laboratories, Inc., as lined fire hose is accepted as conforming to the requirement. Fire station #4 hose had multiple pin holes located at the hydrant connection. 46 CFR 181.15-10 Old T
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 12 May 2025
Resolution: Fire hose was replaced with a brand new one and tested SAT.
09 - Working and Living Conditions › 092 - Working Conditions › Lighting (Working spaces)
Issued 9 May 2025 Resolved
Lighting fixtures shall be constructed in accordance with the requirements of Underwriters' Laboratories, Inc. Standard for Marine Type Electric Lighting Fixtures, Subject 595, or shall bear the proper Underwriters' Laboratories, Inc. "Marine Type" label, or shall be constructed in accordance with the requirements of other recognized testing laboratories. Several deck 02 outdoor lights were missing the protective guard around the globe or were found broken. 46 CFR 183.10-20(I) Old T
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 12 May 2025
Resolution: All identified lighting issues were repaired SAT.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 9 May 2025 Resolved
Vessels described by 46 CFR 175.110(c) must have an interconnected fire detection system in compliance with § 181.450 installed in all enclosed areas where passengers and crew have routine access, including accommodation spaces and machinery spaces. Fire detection sensor in the steering gear room was missing.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 12 May 2025
Resolution: Missing detector was replaced and tested SAT.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 5 May 2025 Resolved
Shutoff valves, installed so as to close against the fuel flow, shall be fitted in the fuel supply lines, one at the tank connection and one at the engine end of the fuel line to stop fuel flow when servicing accessories. fuel flow when servicing accessories. The shutoff valve at the tank shall be operable from outside the tank compartment. Fuel shutoff valves were replaced but the emergency fuel pull cable was not connected to the valves and could not be tested. 46 CFR 182.20-40(3) - Old T
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 9 May 2025
Resolution: Fuel shut off cables were connected and tested SAT.
07 - Fire Safety › N/A - No Subsystem › Ventilation
Issued 5 May 2025 Resolved
Spaces containing machinery shall be fitted with at least two ducts to furnish natural or mechanical supply and exhaust ventilation. Both engine room fans were supplying air to the engine room with no exhaust ventilation. 46 CFR 182.20-45(c) - Old T
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 9 May 2025
Resolution: Ventillation was repaired and provided intake and exhaust.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Covers (hatchway-, portable-, tarpaulins, etc.)
Issued 5 May 2025 Resolved
All enclosed spaces within the vessel shall be properly vented or ventilated. Where such openings would endanger the vessel under adverse weather conditions, means shall be provided to close them. All ventilation pull cables were too short and could not be locked into place properly. 46 CFR 177.20(a) - Old T
Action required: 66 - Prior to drilling or production operations
Resolved 12 May 2025
Resolution: All ventillation were adjusted properly and allowed for proper closure.
10 - Safety of Navigation › N/A - No Subsystem › Lights, shapes, sound-signals
Issued 5 May 2025 Resolved
The lights prescribed by these Rules shall, if carried, also be exhibited from sunrise to sunset in restricted visibility and may be exhibited in all other circumstances when it is deemed necessary. Stern light was inoperable. 33 CFR 83.20
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 9 May 2025
Resolution: Stern light was repaired and tested SAT.
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 5 May 2025 Resolved
Except as otherwise provided in this section, all vessels shall be provided with not less than two avenues of escape from all general areas accessible to the passengers or where the crew may be quartered. Escape ladder from aft crew 100's space was not properly secured at the bottom of the escape ladder. 46 CFR 177.15-1 Old T
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 9 May 2025
Resolution: Ladder was properly secured to the deck.
04 - Emergency Systems › N/A - No Subsystem › Public address system
Issued 5 May 2025 Resolved
On a vessel of more than 19.8 meters (65 feet) in length, the public address system must be a fixed installation and be audible during normal operating conditions throughout the accommodation spaces and all other spaces normally manned by crew members. Public address system speakers were inoperable in the passageway in crew aft 100's. 46 CFR 184.610(b)
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 9 May 2025
Resolution: Passageway speakers were repaired and tested SAT.
09 - Working and Living Conditions › 091 - Living Conditions › Pipes, wires (insulation)
Issued 5 May 2025 Resolved
This part is intended to provide a minimum standard of regulations for electrical installations and equipment that will result in a vessel that is reasonably safe from fire caused by and/or originating in electrical equipment, and reasonably safe from electrical shock. The following electrical issues were identified: - Electrical outlet in crew berthing forward 100's outboard room did not have a cover installed. - 02 florescent lights in crew berthing forward 100's did not have bulbs installed and were missing the covers. - Crew berthing room #107 had a broken electrical switch and broken light cover. - Crew berthing room #115 had a broken electrical plug cover. - Crew berthing room #114 had a missing light cover and missing light bulb. 46 CFR 183.200
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 9 May 2025
Resolution: All identified electrical issues were repaired.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 5 May 2025 Resolved
On a vessel of at least 7.9 meters (26 feet) in length, a visual and audible alarm must be provided at the operating station to indicate a high water level in each normally unmanned space. Forepeak high water alarm was inoperable. 46 CFR 182.530
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 9 May 2025
Resolution: Bilge high water alarm was replaced and tested SAT.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 5 May 2025 Resolved
A vessel is inspected for compliance with the standards required by this subchapter. Machinery, equipment, materials, and arrangements not covered by standards in this subchapter may be inspected in accordance with standards acceptable to the cognizant OCMI as good marine practice. Reefer and freezer were not properly secured in aft food storage space.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 12 May 2025
Resolution: Equipment was properly secured.
04 - Emergency Systems › N/A - No Subsystem › Muster list
Issued 5 May 2025 Resolved
On vessels described by 46 CFR 175.110(d) of this chapter, a passenger safety bill must be posted by the master in each cabin or stateroom, and in passenger accommodation spaces. Several passenger staterooms were missing passenger safety bills as required. 46 CFR 185.515
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 9 May 2025
Resolution: All missing passenger safety bills were replaced.
04 - Emergency Systems › N/A - No Subsystem › Muster list
Issued 5 May 2025 Resolved
The station bill must be posted at the operating station and in a conspicuous location in each crew accommodation space. Crew accommodation spaces were missing the required station bill. 46 CFR 185.514
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 12 May 2025
Resolution: Station bills were properly placed in the crew berthing passageway with bunk cards placed in each berthing.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 14 May 2024 Resolved
Each item of lifesaving equipment determined by the marine inspector to not be in serviceable condition must be repaired or replaced. 03 life rings onboard were found with severe UV damage and cracking. 46 CFR 176.808(d)
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 15 May 2024
Resolution: All ring life buoys have been replaced.
05 - Radio Communications › N/A - No Subsystem › Satellite EPIRB 406MHz/1.6GHz
Issued 14 May 2024 Resolved
Each disposable hydrostatic release unit must be marked with an expiration date of two years after the date on which the unit is installed. EPIRB hydrostatic release unit was found expired. 46 CFR 185.740(b)
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 15 May 2024
Resolution: Hydrostatic release unit was replaced.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 14 May 2024 Resolved
At each initial and subsequent inspection for certification, the owner or managing operator must be prepared to conduct tests and have the vessel ready for inspection of its fire protection equipment. 02 fire extinguishers were found past due on its inspection. 46 CFR 176.810(a)(1)
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 15 May 2024
Resolution: Fire extinguishers were serviced.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 14 May 2024 Resolved
Electrical equipment on a vessel must be installed and maintained to: Protect passengers, crew, other persons, and the vessel from electrical hazards, including fire, caused by or originating in electrical equipment, and electrical shock. Starboard air conditioning space electrical enclosure was missing the cover and wires were found exposed. 46 CFR 183.200
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 15 May 2024
Resolution: Electrical enclosure cover was installed properly.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 14 May 2024 Resolved
On a vessel of at least 7.9 meters (26 feet) in length, a visual and audible alarm must be provided at the operating station to indicate a high water level in each of the following normally unmanned spaces. Aft engine room bilge alarm float switch was found broken. 46 CFR 182.530(a)(12)
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 17 May 2024
07 - Fire Safety › N/A - No Subsystem › Fire pumps and its pipes
Issued 14 May 2024 Resolved
At each initial and subsequent inspection for certification, the owner or managing operator must be prepared to conduct tests and have the vessel ready for inspection of its fire protection equipment Including the following: Inspection of piping, controls, and valves. Fire main branch valve in engine room was leaking excessively at the bonnet. 46 CFR 176.810
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 15 May 2024
Resolution: Leaky fire main branch valve was replaced in kind. Additional testing sat.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 14 May 2024 Resolved
In systems and applications where flexible hoses are permitted to be clamped Double hose clamping is required where practicable. Multiple vital systems on port MDE had single hose clamps. 46 CFR 182.410(d)
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 15 May 2024
Resolution: All vital system non metallic hoses were double clamped.
09 - Working and Living Conditions › 092 - Working Conditions › Lighting (Working spaces)
Issued 14 May 2024 Resolved
Each lighting fixture globe, lens, or diffuser must have a guard or be made of high strength material, except in an accommodation space, radio room, galley, or similar space where it is not subject to damage. Shower light fixture in room 111 was missing the globe. 46 CFR 183.410
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 17 May 2024
Resolution: Missing globe was replaced.
09 - Working and Living Conditions › 092 - Working Conditions › Ventilation (Working spaces)
Issued 14 May 2024 Resolved
Combustibles and other foreign materials are not allowed within ventilation ducts. Galley griddle exhaust ventilation had excessive build up of grease. 46 CFR 176.830
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 17 May 2024
Resolution: Galley hood fans and ventilation duct was degreased.
04 - Emergency Systems › N/A - No Subsystem › Public address system
Issued 14 May 2024 Resolved
A vessel with more than one passenger deck and a vessel with overnight accommodations must have the public address system operable from the operating station. All weather deck public address speakers were inoperable. 46 CFR 184.610(c)
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 17 May 2024
Resolution: All weather deck public address system speakers were retested sat.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 14 May 2024 Resolved
Electrical equipment on a vessel must be installed and maintained to protect passengers, crew, other persons, and the vessel from electrical hazards. GFCI outlets were not installed next to the sink in "TEBENKOF" and WRANGEL" passenger accommodation spaces. 46 CFR 183.200(b)
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 17 May 2024
Resolution: GFCI outlets were installed next to sink.
01 - Certificates & Documentation › 011 - Ships Certificates › Cargo Ship Safety Radio (including exemption)
Issued 9 May 2023 Resolved
The Bridge-to-Bridge Act and the regulations of this part apply to the following vessels in the navigable waters of the United States: (a) very power-driven vessel of 20 meters or over in length while navigating. Vessels Bridge to Bridge Radio Certificate was expired. 47 CFR 80.1001
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 10 May 2023
Resolution: FCC inspection was completed and cetificate posted on the bridge.
05 - Radio Communications › N/A - No Subsystem › Main installation
Issued 9 May 2023 Resolved
Except as noted in paragraph (c) of this section, stations in the maritime service must be licensed by the FCC either individually or by fleet. Vessels FCC station license was expired. 47CFR 80.13
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 10 May 2023
Resolution: Station license was renewed and posted on the vessel.
05 - Radio Communications › N/A - No Subsystem › Main installation
Issued 9 May 2023 Resolved
A certification that the ship has passed an inspection must be entered into the ship's log by the inspecting technician. Vessels FCC Safety Radiotelephony Certificate was expired. 47 CFR 80.59(a)(2)
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 10 May 2023
Resolution: FCC inspection was completed and certificate was posted.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 9 May 2023 Resolved
Complete but simple instructions for the operation of a fixed gas fire extinguishing system must be located in a conspicuous place at or near each pull box and stop valve control and in the space where the extinguishing agent cylinders are stored. If the storage cylinders are separate from the protected space, the instructions must also include a schematic diagram of the system and instructions detailing alternate methods of releasing the extinguishing agent should the local manual release or stop valve controls fail to operate. Installed CO2 system did not have the required instructions or schematic of the system. 46 CFR 185.612(a)
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 10 May 2023
Resolution: Simple instructions and diagram were placed at the pull station and at the location of the bottles in the lazarette.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 9 May 2023 Resolved
Electrical equipment on a vessel must be installed and maintained to Protect passengers, crew, other persons, and the vessel from electrical hazards, including fire, caused by or originating in electrical equipment, and electrical shock. Electrical enclosure in the AC room was missing the cover and had exposed wiring. 46 CFR 183.200(b)
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 10 May 2023
Resolution: Missing cover was installed.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 9 May 2023 Resolved
A vessel of more than 19.8 meters (65 feet) in length must have at least one fire axe located in or adjacent to the primary operating station. A fire ax was not located in or adjacent to the operating station. 46 CFR 181.600
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 10 May 2023
Resolution: A fire ax was placed at the operating station.
10 - Safety of Navigation › N/A - No Subsystem › Nautical publications
Issued 9 May 2023 Resolved
As appropriate for the intended voyage, a vessel must carry adequate and up-to-date Coast Pilot [name withheld], Tides and Currents. Vessels nautical publications were not updated. 46 CFR 184.420
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 10 May 2023
Resolution: All required navigational publications were updated on the bridge computer.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 21 June 2022 Resolved
Nonconducting mats or grating must be provided on the deck in front of each switchboard and, if accessible from the rear, on the deck in the rear of the switchboard. Nonconductive matting was missing in front of main switchboard. 46 CFR 183.330(f)
Action required: 10 - Deficiency Rectified
Resolved 21 June 2022
Resolution: Non conductive matting was added in front of switchboard.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 21 June 2022 Resolved
All electrical installations shall be to the satisfaction of the Officer in Charge, Marine Inspection. Light fixture in lazarette overhead was secured with electrical tape. 46 CFR 183.01-15 OLD T
Action required: 10 - Deficiency Rectified
Resolved 21 June 2022
Resolution: Light fixture was properly secured.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 21 June 2022 Resolved
All electrical installations shall be to the satisfaction of the Officer in Charge, Marine Inspection. Electrical junction box in lazarette overhead was missing cover plate. 46 CFR 183.01-15 OLD T
Action required: 10 - Deficiency Rectified
Resolved 21 June 2022
Resolution: Cover plate installed on junction box.
11 - Life Saving Appliances › N/A - No Subsystem › Launching arrangements for survival craft
Issued 21 June 2022 Resolved
Each survival craft must be stowed so that when the vessel sinks the survival craft floats free and, if inflatable, inflates automatically. Hydrostatic release units for both life rafts were improperly installed preventing a float free arrangement.
Action required: 10 - Deficiency Rectified
Resolved 21 June 2022
Resolution: HRU's were properly installed.
02 - Structural Conditions › N/A - No Subsystem › Decks - cracking
Issued 21 June 2022 Resolved
At each inspection for certification and at every other vessel inspection all observed unsafe practices, fire hazards, and other hazardous situations must be corrected and all required guards and protective devices must be in satisfactory condition. Starboard quarter 2nd deck had 02 cracked vertical stancions at the acocomodation access door.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 23 June 2022
Resolution: Welds were repaired SAT.
04 - Emergency Systems › N/A - No Subsystem › Fire drills
Issued 16 June 2022 Resolved
All escape hatches and other emergency exits shall be marked on both sides using at least 1-inch letters: "Emergency Exit, Keep Clear", unless such markings are deemed unnecessary by the Officer in Charge, Marine Inspection. Emergency escape was not properly marked. 46 CFR 185.30-15 OLD T
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 21 June 2022
Resolution: Emergency escape was properly marked.
10 - Safety of Navigation › N/A - No Subsystem › Lights, shapes, sound-signals
Issued 16 June 2022 Resolved
The Rules concerning lights (§§ 83.20 through 83.31) shall be complied with from sunset to sunrise, and during such times no other lights shall be exhibited. All navigation light lenses were cracked and discolored preventing the intensity of the lights from achieving the required 2NM range. Vessel is restricted to daylight operations and periods of unrestricted visibility. 33 CFR 83.20(b)
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 21 June 2022
Resolution: NAV Light lenses were cleaned and intensity of light has increased. O/O has placed a purchase for new lenses to be installed upon receipt.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 16 June 2022 Resolved
All electrical installations shall be to the satisfaction of the Officer in Charge, Marine Inspection. Forward storage space passageway and space has several overhead lights without protective covers installed.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 21 June 2022
Resolution: Protective covers have been installed.
09 - Working and Living Conditions › 092 - Working Conditions › Other (accident prevention)
Issued 16 June 2022 Resolved
For items not covered by standards in this subchapter, inspection shall be in accordance with standards acceptable to the Officer in Charge, Marine Inspectionsm as good marine practice. Forward lounge bar had several CO2 beverage bottles not properly secured. 46 CFR 176.25-1 OLD T
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 21 June 2022
Resolution: CO2 beverage bottles have been properly secured.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 16 June 2022 Resolved
All cable and wire must Be installed with metal supports spaced not more than 610 millimeters (24 inches) apart, and in such a manner as to avoid chafing and other damage. Wire run is not properly supported in forward storage space overhead. 46 CFR 183.340(b)(4)
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 21 June 2022
Resolution: Wire run has been properly supported.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 16 June 2022 Resolved
All electrical installations shall be to the satisfaction of the Officer in Charge, Marine Inspection. Electrical outlet in forward storage space does not have a cover plate attached. 46 CFR 183.01-15 OLD T
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 21 June 2022
Resolution: Cover plate has been installed.
04 - Emergency Systems › N/A - No Subsystem › Public address system
Issued 16 June 2022 Resolved
On a vessel of more than 19.8 meters (65 feet) in length, the public address system must be a fixed installation and be audible during normal operating conditions throughout the accommodation spaces and all other spaces normally manned by crew members. Forward 100's passageway PA system speakers were inoperable. 46 CFR 184.610(b)
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 21 June 2022
Resolution: PA system has was tested SAT. All speakers are functional.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 16 June 2022 Resolved
All electrical installations shall be to the satisfaction of the Officer in Charge, Marine Inspection. Main dining room aft overhead light switches were missing covers. 46 CFR 183.01-15 OLD T
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 21 June 2022
Resolution: Covers have been installed.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 16 June 2022 Resolved
All electrical installations shall be to the satisfaction of the Officer in Charge, Marine Inspection. Gen Board Bus 2 Panel 3 had an open slot requiring a blank. 46 CFR 183.01-15 OLD T
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 21 June 2022
Resolution: Blank installed.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 16 June 2022 Resolved
Remote fuel shutoff stations shall be marked in at least 1-inch letters indicating purpose of the valve and direction of operation. Fuel shutoff handles were not properly marked.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 21 June 2022
Resolution: Fuel shutoffs have been properly marked.
09 - Working and Living Conditions › 092 - Working Conditions › Other (accident prevention)
Issued 16 June 2022 Resolved
For items not covered by standards in this subchapter, inspection shall be in accordance with standards acceptable to the Officer in Charge, Marine Inspections as good marine practice. Ice machine located outside the galley is not properly secured. 46 CFR 176.25-1 OLD T
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 21 June 2022
Resolution: Ice machine has been properly secured.
09 - Working and Living Conditions › 092 - Working Conditions › Other (accident prevention)
Issued 16 June 2022 Resolved
At each inspection for certification and reinspection the marine inspector shall examine the bilges and other spaces to see that there is no accumulation of oil or other matter. Lazzarette had excessive hydraulic fluid in the bilge from recent maintenance. 46 CFR 176.25-50 OLD T
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 21 June 2022
Resolution: Space has been properly cleaned.
07 - Fire Safety › N/A - No Subsystem › Ventilation
Issued 16 June 2022 Resolved
All enclosed spaces within the vessel shall be properly vented or ventilated. Means shall be provided to close them. Port and starboard side ventilation closures require gaskets due to large gap when closed. 46 CFR 177.20-1 OLD T
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 21 June 2022
Resolution: Gaskets have been installed on the ventilation closures.
02 - Structural Conditions › N/A - No Subsystem › Hull - corrosion
Issued 9 June 2021 Resolved
Extensive wastage to longitudal framing below room 103 shower. Crop and renew to original condition.
Action required: 705 - Other - as specified
Resolved 30 June 2021
Resolution: NDT Conducted - air lance/vac box sat.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 6 March 2021 Resolved
Prove proper operation of engine room fixed extinguishing system machinery shut-downs.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 21 June 2022
Resolution: Engine room ventilation pressure switch tested SAT.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 6 March 2021 Resolved
Identify and make permanent repairs to all exhaust leaks in engine room.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 21 June 2022
Resolution: All exhaust leaks repaired SAT.
01 - Certificates & Documentation › 012 - Crew Certificates › Certificates for master and officers
Issued 7 April 2020 Resolved
While the vessel is engaged in towing the vessel must be controlled by a licensed Master or Mate of towing. Vessel has until April 1st 2022 to man vessel with licensed Master and Mate of towing.
Action required: 705 - Other - as specified
Due 1 April 2022
Resolved 2 November 2021
Resolution: Cleared. SEC JUN made determination that vessel not engaged in the service of towing commercially.
01 - Certificates & Documentation › 013 - Documents › Stability Information Booklet
Issued 7 April 2020 Resolved
Vessel must provide updated stability calculations to include towing to Coast Guard Marine Safety Center to update vessels stability letter by April 1st 2022
Action required: 705 - Other - as specified
Due 1 April 2022
Resolved 2 November 2021
Resolution: Cleared. SEC JUN made determination that vessel not engaged in the service of towing commercially.
10 - Safety of Navigation › N/A - No Subsystem › Lights, shapes, sound-signals
Issued 7 April 2020 Resolved
Vessel shall provide correct light and day shape configuration for the tow being conducted prior to towing.
Action required: 705 - Other - as specified
Due 7 April 2020
Resolved 2 November 2021
Resolution: Cleared. SEC JUN made determination that vessel not engaged in the service of towing commercially.
09 - Working and Living Conditions › 092 - Working Conditions › Ropes and wires
Issued 7 April 2020 Resolved
Vessel shall start and maintain records for towline and terminal gear used for towing astern or alongside prior to towing
Action required: 705 - Other - as specified
Due 7 April 2020
Resolved 2 November 2021
Resolution: Cleared. SEC JUN made determination that vessel not engaged in the service of towing commercially.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 1 October 2019 Resolved
Provide an interlock on the electrical distribution panel to prevent generators from being simultaneously connected to the switchboard with shore power.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 21 June 2022
Resolution: Interlock device has been installed.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 1 October 2019 Resolved
Ensure all hot water heaters are properly installed and secured from rolling by straps or other devices.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 21 June 2022
Resolution: How water heaters have been properly secured.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 5 April 2019 Resolved
Engine room fire detection must be registered visibly and audibly in the pilothouse; system failed to provide an audible alarm.
Action required: 17 - Rectify deficiencies prior to departure
Due 1 May 2019
Resolved 8 May 2019
Resolution: Witnessed a satisfactory operational test of the engine room heat detection.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 5 April 2019 Resolved
A vessel must be provided with a bilge dewatering system; an operational test of the system failed and one remote operated bilge valve could not be exercised.
Action required: 17 - Rectify deficiencies prior to departure
Due 1 May 2019
Resolved 8 May 2019
Resolution: Witnessed a satisfactory test of the bilge dewatering system and verified the malfunctioning valve had been serviced and operated properly.
09 - Working and Living Conditions › 092 - Working Conditions › Protection machinery
Issued 5 April 2019 Resolved
Piping in excess of 150 degrees F must be suitably insulated, exhaust lagging in the starboard steering room and the port generator was not provided.
Action required: 705 - Other - as specified
Due 1 May 2019
Resolved 8 May 2019
Resolution: Each identified location was provided with new lagging.
09 - Working and Living Conditions › 092 - Working Conditions › Warning notices
Issued 5 April 2019 Resolved
An alarm for fixed gas fire extinguishing systems must be clearly and conspicuously marked; the engine room CO2 siren sign was badly faded and inconspicuously placed.
Action required: 705 - Other - as specified
Due 1 May 2019
Resolved 8 May 2019
Resolution: Verified a new sign placard was provided and conspicuously placed.
09 - Working and Living Conditions › 092 - Working Conditions › Protection machinery
Issued 5 April 2019 Resolved
An exposed hazard such as rotating machinery must be properly protected by a cover; the generators and main engines' flywheels were exposed.
Action required: 705 - Other - as specified
Due 1 May 2019
Resolved 8 May 2019
Resolution: Verified flywheel covers were provided.
02 - Structural Conditions › N/A - No Subsystem › Marking of IMO number
Issued 5 April 2019 Resolved
The name and hailing port must be marked on some clearly visible exterior part of the stern; no name or hailing port were provided.
Action required: 705 - Other - as specified
Due 1 May 2019
Resolved 8 May 2019
Resolution: Verified the vessel name and hailing port were provided on the exterior stern.
08 - Alarms › N/A - No Subsystem › Other (alarms)
Issued 5 April 2019 Resolved
A high water alarm must be provided for each space with through hull fittings; the bilge sensor device in the steering room was not properly mounted and inoperable.
Action required: 705 - Other - as specified
Due 1 May 2019
Resolved 8 May 2019
Resolution: Verified that bilge sensor was mounted and witnessed a satisfactory operational test.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 5 April 2019 Resolved
Lighting fixtures must have a guard and wires must be properly terminated in a junction box; both fwd and aft crew's accommodations were missing lighting fixture covers and both had bear wirs protruding through the ceiling.
Action required: 705 - Other - as specified
Due 1 May 2019
Resolved 8 May 2019
Resolution: Verified all identified wiring discrepancies were properly addressed.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 5 April 2019 Resolved
Wires and cables must be properly supported and installed in a manner that does not interfere with moving machinery; lighting cables were interfering with the starboard side rudder bar.
Action required: 705 - Other - as specified
Due 1 May 2019
Resolved 8 May 2019
Resolution: Verified the identified cable was bundled back to prevent interference.
10 - Safety of Navigation › N/A - No Subsystem › Magnetic compass
Issued 5 April 2019 Resolved
Except for vessels limited to daytime operations the compass must be illuminated; the light was inoperable.
Action required: 705 - Other - as specified
Due 1 May 2019
Resolved 8 May 2019
Resolution: Verified the installation of a new compass light.
04 - Emergency Systems › N/A - No Subsystem › Fire drills
Issued 5 April 2019 Resolved
Conduct drills prior to seasonal operations.
Action required: 705 - Other - as specified
Due 1 May 2019
Resolved 8 May 2019
Resolution: Witnessed underway drills
Engineering › Reduction Gearing/Clutches › Gear
Issued 10 July 2017 Resolved
[name withheld] reported failure of #2 Engine propulsion, likely in the reduction gear. Master instructed to repair proper function of #2 shaft for forward and reverse operation.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 12 July 2017
Resolution: [name withheld] attended vessel in Auke Bay to verify proper operation of propulsion on #2 engine.
Engineering › Lubricating Oil Service System › Gauge
Issued 10 April 2017 Resolved
Gauges to indicate L/O pressure shall be provided for propulsion equipment. Repair or renew the port main engine L/O pressure gauge at the operating station.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 10 May 2017
Resolved 10 May 2017
Resolution: Verified gauge was operating properly.
Communications › Radio Communications › EPIRB
Issued 10 April 2017 Resolved
Each vessel that operates on the high seas mush have Cat 1 EPIRB. Provide and properly install EPIRB.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 10 May 2017
Resolved 10 May 2017
Resolution: Verified EPIRB was aboard and installed properly.
Accommodation/Occupational Safety › Medical/First Aid › Medicine Chest
Issued 10 April 2017 Resolved
A vessel must carry and approved or equivalent first aid kit and instructions. Provide an appropriate first aid kit for the vessel.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 10 May 2017
Resolved 10 May 2017
Resolution: Verified appropriate first kit was aboard.
Lifesaving › Lifejacket/PFD (General) › Storage
Issued 10 April 2017 Resolved
Properly distribute life preservers and mark life preserver stowage in the crew’s accommodations.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 10 May 2017
Resolved 10 May 2017
Resolution: Verified PFD's were properly distrubuted and storage locations were marked.
Electrical › Lighting (emergency) › Lighting Fixture
Issued 10 April 2017 Resolved
Each vessel must have adequate emergency lighting fitted along the line of escape to the main deck for passengers and crew. Correct E-light discrepancies and make available for reinspection.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 10 May 2017
Resolved 10 May 2017
Resolution: Verfied emergency lighting instalations were sat.
Accommodation/Occupational Safety › Occupational Safety › Guards for Exposed Hazards
Issued 10 April 2017 Resolved
Suitable covers, guards, or rails shall be installed in way of all exposed hazards. Provide cover for ventilation opening for the Engine Room supply fan.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 10 May 2017
Resolved 10 May 2017
Resolution: Verified instalation of expanded metal to close off ventalation opening.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Servicing
Issued 10 April 2017 Resolved
Complete servicing and maintenance of the engine rooms fixed fire extinguishing system.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 10 May 2017
Resolved 10 May 2017
Resolution: Verified fixed fire extinguishing system maintenance was completed and system was intact.
Engineering › Fuel Oil Service System › Valve
Issued 10 April 2017 Resolved
Shutoff valve shall be installed at the engine end of the fuel line. Provide shutoff valve for the port main engine.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 10 May 2017
Resolved 10 May 2017
Resolution: Port MDE shutoff valves provided by primary fuel filter valves.
Engineering › Sea-water System (primary cooling) › Piping
Issued 10 April 2017 Resolved
Each flexible hose designed for use with hose clamps shall utilize two clamps at both ends. Provide an additional clamps for both generator's sea-water piping.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 10 May 2017
Resolved 10 May 2017
Resolution: Verified generator sea water piping was properly fastened.
Electrical › Electrical Distribution System (service) › Cable
Issued 24 January 2017 Resolved
Vessel owners shall minimize accidental personnel contact with energized circuits. Remove the two dead-ended cables in the FWD 100's void, reconnect and protect identified cable next to hatch in aft 100's, and properly terminate large cable in ovhd of aft steering.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 May 2017
Resolved 10 May 2017
Resolution: Verified cables were removed.
Electrical › Electrical Distribution System (service) › Cable
Issued 24 January 2017 Resolved
Each conductor shall be with metal supports not more than 24" apart. Properly run and support cable providing powering to aft corridor outlet in the FWD 100's.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 May 2017
Resolved 10 May 2017
Resolution: Verfied cable was removed.
Engineering › Freshwater System (jacketwater cooling) › Hose
Issued 24 January 2017 Resolved
Each flexible hose designed for use with hose clamps shall utilize two clamps at both ends. Provide an additional clamp for the port main engine jacket water cooler connection.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 May 2017
Resolved 10 April 2017
Resolution: Verified installation of additional hose clamp.
Stability › Watertight Integrity › Watertight Subdivision Standard
Issued 24 January 2017 Resolved
Penetrations in watertight bulkheads must have means to make them watertight. Properly secure open ended piping penetrations in the steering compartment fwd bulkhead stbd of centerline.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 May 2017
Resolved 3 April 2017
Resolution: 3 decomissioned piping penetrations were capped and 1 wiring penetration was properly sealed.
Accommodation/Occupational Safety › Occupational Safety › Rubbish/Waste Materials
Issued 24 January 2017 Resolved
Bilges shall be free of excessive accumulation of oil, trash, debris, or other matter that may clog bilge pumping systems. Remove or more appropriately store lagging, tarps, and construction materials in the steering compartment.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 May 2017
Resolved 10 April 2017
Resolution: Verified aft steering compartment bilge rubbish had been removed.
Lifesaving › Inflatable Buoyant Apparatus › Stowage
Issued 2 May 2016 Resolved
Provide proper number of IBAs for persons on board. 46CFR180.200
Condition: Improper Installation
Action required: 701 - Prior to carriage of passengers/cargo
Due 12 May 2016
Resolved 10 May 2016
Fire Fighting › Ventilation Systems › Ventilation Fire Dampers
Issued 2 May 2016 Resolved
Prove proper closing of exterior galley ventilation.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 12 May 2016
Resolved 11 May 2016
Lifesaving › Lifejacket/PFD (General) › Marking
Issued 2 May 2016 Resolved
Provide vessel name on child life jackets. 46CFR180.71
Condition: Improper Installation
Action required: 701 - Prior to carriage of passengers/cargo
Due 12 May 2016
Resolved 11 May 2016
Construction/Loadline › Structures › Manhole
Issued 2 May 2016 Resolved
Prove proper operation of lounge escape hatch.
Condition: Improper Installation
Action required: 701 - Prior to carriage of passengers/cargo
Due 12 May 2016
Resolved 11 May 2016
Communications › Alarms/Indicators › Fire Alarm
Issued 2 May 2016 Resolved
Prove proper operation of audible alarm on bridge alarm panel.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 12 May 2016
Resolved 11 May 2016

Recorded names · 1

SPIRIT OF ALASKA (2005–2008). Names as the Coast Guard recorded them in incident records, with the years they appear; some are renames and some are spelling variants.

Ownership record

The Coast Guard's documentation record for this hull -- the Abstract of Title, with its owners and liens as filed -- is not in PSIX. Ask, and Maury buys it from the National Vessel Documentation Center, files it here with its date, and every reader of this page gets it.