07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 28 March 2023
Resolved
Vessels described by 46 CFR 175.110(c) must have an interconnected fire detection system in compliance with § 181.450 installed in all enclosed areas where passengers and crew have routine access, including accommodation spaces and machinery spaces. An interconnected fire detection system has not been installed on-board the vessel. Install a interconnected fire detection system and prove proper operation to the satisfaction of the attending Marine Inspector.
46 CFR 181.450(a)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 April 2023
Resolved 9 May 2023
Resolution: Received, reviewed, and accepted documentation and photos showing install of approved interconnected fire detection system.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 28 March 2023
Resolved
Marine inspector shall examine all accessible parts of the exterior and interior of the hull, watertight bulkheads, and weather deck. Cracked weld found on the base of the vertical beam within the lazarrette supporting the upper longitudinal. Grind and renew.
46 CFR 176.25-5(a)(1)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 April 2023
Resolved 24 April 2023
Resolution: Receive, reviewed, and accepted photo showing new weld completed on the vertical beam supporting the upper longitudinal.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 28 March 2023
Resolved
Marine inspector shall examine all accessible parts of the exterior and interior of the hull, watertight bulkheads, and weather deck. Pinholes found in outer pilothouse shell plating. Plug pinholes.
46 CFR 176.25-5(a)(1)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 April 2023
Resolved 24 April 2023
Resolution: Received, reviewed, and accepted photo showing adequate plugging of pinholes.
10 - Safety of Navigation › N/A - No Subsystem › Lights, shapes, sound-signals
Issued 28 March 2023
Resolved
On vessels of less than 20 meters in length, the sidelights, if necessary to meet the requirements of § 84.15, shall be fitted with matt black inboard screens. Navigation light screens found missing black background. Paint screens.
33 CFR 84.05(a)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 April 2023
Resolved 24 April 2023
Resolution: Received, reviewed, and accepted photo showing correct black background behind navigation lights.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 28 March 2023
Resolved
A vessel not required to have a power driven fire pump by § 181.300 must have at least three 9.5 liter (2 1/2 gallon) buckets, with an attached lanyard satisfactory to the cognizant OCMI, placed so as to be easily available during an emergency. The words “FIRE BUCKET” must be stenciled in a contrasting color on each bucket.
0ne of three fire buckets found with a hole. Replace or repair fire bucket.
46 CFR 181.610
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 April 2023
Resolved 24 April 2023
Resolution: Received, reviewed, and accepted photo showing two new fire buckets provided for vessel with proper markings.
01 - Certificates & Documentation › 011 - Ships Certificates › Certificate of Inspection (COI)
Issued 28 March 2023
Resolved
The certification of inspection shall, in general, be framed under glass or other transparent material and posted in a conspicuous place. Certification of Inspection, Certificate of Documentation, and Stability Letter were not properly posted. Properly post documents.
46 CFR 176.01-40(a)
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 April 2023
Resolved 24 April 2023
Resolution: Received, reviewed, and accepted photo showing the proper posting of all required documents onboard.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 28 March 2023
Resolved
Gages to indicate engine cooling water discharge temperature and lubricating oil pressure shall be provided for all propulsion engines. Gages for lubricating oil pressure found not operating correctly. Replace or repair.
46 CFR 182.20-5
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 April 2023
Resolved 27 April 2023
Resolution: Received, reviewed, and accepted photos showing install and operation of new gages at operating station.
11 - Life Saving Appliances › N/A - No Subsystem › Other (life saving)
Issued 28 March 2023
Resolved
All life floats and buoyant apparatus shall be of approved type. The subparts in Subchapter Q contain the specifications for lifefloats to meet approval series 160.027. Vessel to replace lifefloat to meet the specification standards listed in 46 CFR 160.027, Subchapter Q for lifefloats to include drop down net. Vessel's passenger count reduced to 24 POB until the installation of a CG approved lifefloat that meets 46 CFR 160.027 standards.
46 CFR 180.10-1
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 April 2023
Resolved 27 April 2023
Resolution: Received, reviewed, and accepted photos showing installation of new CG approved lifefloat.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 28 March 2023
Resolved
Marine inspector shall examine all accessible parts of the exterior and interior of the hull, watertight bulkheads, and weather deck. Crack identified in deck longitudinal near starboard stuffing box. Grind and renew.
46 CFR 176.25-5(a)(1)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 April 2023
Resolved 24 April 2023
Resolution: Received, reviewed, and accepted photo showing new weld where crack was ID'd in the deck longitudinal near starboard stuffing box.
09 - Working and Living Conditions › 092 - Working Conditions › Machinery
Issued 28 March 2023
Resolved
Protective gratings shall be provided at such locations where persons or gear might come in contact with the exhaust pipe. Starboard main engine found with missing lagging around engine turbos. Replace or renew.
46 CFR 182.15-20(g)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 April 2023
Resolved 24 April 2023
Resolution: Received, reviewed, and accepted photo showing install of new lagging around engine turbos.
09 - Working and Living Conditions › 092 - Working Conditions › Anchoring devices
Issued 28 March 2023
Resolved
All vessels shall be fitted with such ground tackle and hawsers as deemed necessary by the Officer in Charge, Marine Inspection. Vessel unable to provide adequate anchor onboard. Provide anchor that satisfies vessel's route and size.
46 CFR 184.10-1(a)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 April 2023
Resolved 24 April 2023
Resolution: Received, reviewed, and accepted photo showing adequate anchor provided onboard.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 11 May 2022
Resolved
01 life jacket was found not to be serviceable. Reduce passenger count to 37 until life jacket is replaced.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 9 June 2022
Resolution: 38 Lifejackets found to be in satisfactory condition.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 11 May 2022
Resolved
Water intrusion was observed in the pilot house overhead were electrical switches are installed.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 9 June 2022
Resolution: Resolved water intrusion in pilothouse.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 11 May 2022
Resolved
Bonding wire not installed.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 9 June 2022
Resolution: Installed bonding wire on fuel tank in lazerette.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 11 May 2022
Resolved
Lanyard is frayed and breaking apart. Replace lanyard.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 9 June 2022
Resolution: Replaced lanyard on lifebuoy.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 11 May 2022
Resolved
Light in the lazarette missing bulb and guard. Dead end wires were found behind operator console on the bridge. Install guards on light fixture and secure dead end wires.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 9 June 2022
Resolution: Installed guard on light and secured wires.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 11 May 2022
Resolved
Exhaust hose was cut the length of hose. Silicone was used to rejoin the two ends. Replace hose to the satisfaction of the marine inspector.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 9 June 2022
Resolution: Replaced and double clamped hose on exhaust piping.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 11 May 2022
Resolved
Placard was not available for all types of life jackets carried on board.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 9 June 2022
Resolution: Installed placard for both types of lifejacket donning.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Gauges, thermometers, etc
Issued 11 May 2022
Resolved
Connection for Lube Oil gauge is leaking behind operating station.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 9 June 2022
Resolution: Secured leak behind steering console.
04 - Emergency Systems › N/A - No Subsystem › Emergency, lighting, batteries and switches
Issued 11 May 2022
Resolved
Portable Light on the bridge is extinguished.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 9 June 2022
Resolution: Replaced batteries in portable light in wheelhouse.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Machinery space openings
Issued 30 March 2021
Resolved
It shall be the duty of the master of any vessel to assure that all exposed hatches are properly secured before getting underway for a voyage on other than protected waters.
Engine room hatches are not fitted with latches that allow them to be secured for sea.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 29 April 2021
Resolved 22 April 2021
Resolution: Installed latches on engine room hatches
09 - Working and Living Conditions › 092 - Working Conditions › Warning notices
Issued 30 March 2021
Resolved
Remote fuel shutoff stations must be marked in clearly legible letters at least 25 millimeters (1 inch) high indicating purpose of the valve and direction of operation.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 19 April 2021
Resolved 22 April 2021
Resolution: Marked emergency fuel shutoff location
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 30 March 2021
Resolved
Generators and motors for use in machinery spaces shall generally be designed for an ambient temperature of 50 degrees C.
Observed nameplate data stated that ambient temperature rating was for 40 degrees C. Either provide updated nameplate with a 50 degree C rating, or derate generator to 80%.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 29 April 2021
Resolved 22 April 2021
Resolution: New nameplate provided with 50 degree C ambient temp rating
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 30 March 2021
Resolved
Acid batteries shall be located in a tray of lead or other suitable material resistant to deteriorating action by the electrolyte.
Observed several holes in both battery boxes allowing for the electrolyte to spill directly to the bilge.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 29 April 2021
Resolved 22 April 2021
Resolution: replaced both main battery boxes and placed generator battery in plastic box.
09 - Working and Living Conditions › 092 - Working Conditions › Warning notices
Issued 30 March 2021
Resolved
When operating a vessel on a body of water where the discharge of untreated sewage is prohibited by the Environmental Protection Agency under 40 CFR 140.3, the operator must secure each Type III device in a manner which prevents discharge of sewage. Acceptable methods of securing the device include—
(1) Closing each valve leading to an overboard discharge and removing the handle;
(2) Padlocking each valve leading to an overboard discharge in the closed position; or
(3) Using a non-releasable wire-tie to hold each valve leading to an overboard discharge in the closed position.
Observed that there was no way to ensure that overboard discharge valve would be secured in the closed position.
Action required: 60 - Rectify deficiencies prior to movement
Due 13 April 2021
Resolved 22 April 2021
Resolution: Installed chain and lock on sewage overboard discharge valve.
09 - Working and Living Conditions › 092 - Working Conditions › Other (accident prevention)
Issued 30 March 2021
Resolved
Doors on a cooking appliance must be provided with hinges and locking devices to prevent accidental opening in heavy seas.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 29 April 2021
Resolved 22 April 2021
Resolution: installed latches on refrigerator.
11 - Life Saving Appliances › N/A - No Subsystem › Means of rescue
Issued 30 March 2021
Resolved
At each inittial and subsequent inspection for certification of a vessel, the owner or manging operator shall be prepared to conduct tests and have the vessel ready for inspection of life saving equipment and systems.
Rescue platform for recovering man overboard could not be located.
Action required: 701 - Prior to carriage of passengers/cargo
Due 13 April 2021
Resolved 22 April 2021
Resolution: returned jacobs ladder to vessel
09 - Working and Living Conditions › 092 - Working Conditions › Ropes and wires
Issued 30 March 2021
Resolved
Rails or equivalent protection must be installed near the periphery of all decks of a vessel accessible to passengers or crew.
There are no rails on the stern deck of the vsl. Either install new rails or place a sign at the exit of the cabin stating that no passengers are permitted on deck while transiting.
Action required: 701 - Prior to carriage of passengers/cargo
Due 13 April 2021
Resolved 22 April 2021
Resolution: installed signage limiting back decks while underway
Fire Fighting › Portable Foam Applicators › General
Issued 27 February 2018
Resolved
Found ONE BI Fire extinguisher in pilot house and ONE BI in engine room. Only TWO BII in accomodation spaces. COI requires ONE BI and FOUR BII. Add additional BII and upgrade type to meet number required by COI.
Condition: Improper Installation
Action required: 60 - Rectify deficiencies prior to movement
Due 27 February 2018
Resolved 27 February 2018
Resolution: Resolved all descrepancies by procuring and stocking entire compliement of fire extinguishers required by COI.
Operations/Management › Drug and Alcohol Testing › Proof of Enrollment
Issued 27 February 2018
Resolved
No Drug & Alcohol Program policy nor MIS reports available for inspection.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 27 February 2018
Resolved 2 March 2018
Resolution: Recieved email from Buds Boat Rentals showing proof of DAPI enrollment.
Accommodation/Occupational Safety › Medical/First Aid › Medicine Chest
Issued 27 February 2018
Resolved
Medicines in First Aid Kit Expired. Stock vessel with complete First Aid Kit.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 27 February 2018
Resolved 27 February 2018
Resolution: Purchased and stocked brand new First Aid Kit.
Fire Fighting › Portable CO2 Fire Extinguisher › Service
Issued 16 March 2017
Resolved
Portable fire extinguisher in engine room was last serviced in FEB 2016. Provide proper inspection records from third party.
Action required: 705 - Other - as specified
Due 23 March 2017
Resolved 16 March 2017
Resolution: Replaced extinguisher with one in compliance. Same type.
Construction/Loadline › Markings › Draft Marks/Indicating System
Issued 2 March 2017
Resolved
Owner or operator must repaint fore and aft draft marks in contrasting color.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 9 March 2017
Resolved 6 March 2017
Resolution: Owner re-painted draft marks.
Lifesaving › Buoyant Apparatus › Approval
Issued 2 March 2017
Resolved
Starboard life float is missing approval plaque attesting to Coast Guard compliance. Provide plaque and documentation attesting to approval prior to carrying greater than 12 passengers. Vessel is restricted to carrying 12 or less passengers until requirements have been met & approved by CG Marine Inspector. 46CFR180.200(a)(2)
Condition: Invalid
Action required: 705 - Other - as specified
Due 23 March 2017
Resolved 22 March 2017
Resolution: Ordered new life float and replaced in-kind. provide documentation attesting to CG approval.
Electrical › Electric Supply System (service) › Cable
Issued 2 March 2017
Resolved
Deteriorating wiring observed on battery cable leading to generator. Repair to satisfaction of CG Marine Inspector.
Action required: 705 - Other - as specified
Due 23 March 2017
Resolved 22 March 2017
Resolution: Replaced wiring in-kind. Provided pictorial proof.
Engineering › Fuel Oil Service System › Piping
Issued 14 April 2016
Resolved
Vessel's generator has a high pressure supply fuel oil line to the #2 injector leaking. Repair to satisfaction of CG Marine Inspector.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 14 May 2016
Resolved 3 May 2016
Construction/Loadline › Structures › Deck Plating
Issued 14 April 2016
Resolved
2 holes found in overhead deck plate for lazarette space. Repair to satisfaction of CG Marine Inspector
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 14 May 2016
Resolved 3 May 2016
Accommodation/Occupational Safety › Other Accommodation Spaces › Open Deck Space
Issued 14 April 2016
Resolved
Port side aft wooden deck above main void space is water-logged. Source of water leak from above deck unidentified. Locate and repair leak(s) and replace deck as needed.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 14 May 2016
Resolved 10 May 2016
Documentation › Certificates/Documents › Certificate of Inspection
Issued 14 April 2016
Resolved
COI not posted on vessel.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 14 May 2016
Resolved 3 May 2016
Accommodation/Occupational Safety › Sleeping Accommodations › Berth
Issued 14 April 2016
Resolved
Remove deep fat fryer from berthing space.
Condition: Invalid
Action required: 705 - Other - as specified
Due 14 May 2016
Resolved 3 May 2016
Documentation › Certificates/Documents › Stability Letter
Issued 14 April 2016
Resolved
Stability letter not posted.
Condition: Invalid
Action required: 705 - Other - as specified
Due 14 May 2016
Resolved 10 May 2016
Documentation › Safety/Response Plans/Programs › Waste Management Plan
Issued 14 April 2016
Resolved
Provide waste management plan.
Condition: Invalid
Action required: 705 - Other - as specified
Due 14 May 2016
Resolved 10 May 2016
Navigation › Collision/Grounding Avoidance › Navigation Lights
Issued 14 April 2016
Resolved
Stern, anchor and searchlights inoperable. Repair.
Condition: Improper/Lack of Maintenance
Action required: 15 - Rectify deficiencies by next port
Due 14 May 2016
Resolved 3 May 2016
Electrical › Electrical Distribution System (service) › Wiring
Issued 14 April 2016
Resolved
Dead end wires found in main and passenger void compartment.
Action required: 705 - Other - as specified
Due 14 May 2016
Resolved 3 May 2016
Electrical › Electric Supply System (service) › Battery Installation
Issued 14 April 2016
Resolved
Clean out battery boxes and protect batteries from dripping.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 14 May 2016
Resolved 3 May 2016
Communications › Alarms/Indicators › Fire Alarm
Issued 14 April 2016
Resolved
Install smoke alarm in berthing area.
Condition: Invalid
Action required: 705 - Other - as specified
Due 14 May 2016
Resolved 10 May 2016
Accommodation/Occupational Safety › Occupational Safety › Portable Electric Equipment/Appliances
Issued 14 April 2016
Resolved
Remove power strip found plugged in inside cabin seating area.
Action required: 705 - Other - as specified
Due 14 May 2016
Resolved 3 May 2016
Documentation › Logs/Records › Logbook (official)
Issued 14 April 2016
Resolved
No EPIRB checks logged for last 3 months.
Action required: 705 - Other - as specified
Due 14 May 2016
Resolved 12 May 2016
Documentation › Logs/Records › Logbook (official)
Issued 14 April 2016
Resolved
Provide weekly, monthly inspections logged for survival craft.
Action required: 705 - Other - as specified
Due 14 May 2016
Resolved 12 May 2016
Documentation › Logs/Records › Logbook (official)
Issued 14 April 2016
Resolved
Provide crew list and safety orientation.
Action required: 705 - Other - as specified
Due 14 May 2016
Resolved 3 May 2016
Navigation › Piloting/Steering › Marine Charts
Issued 14 April 2016
Resolved
Provide chart of sufficient scale for area of operation.
Action required: 705 - Other - as specified
Due 14 May 2016
Resolved 10 May 2016