02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 20 August 2025
Resolved
New installations of electrical equipment and material, and the repair or replacement of wire and cable, on an existing vessel, which are completed to the satisfaction of the cognizant Officer in Charge, Marine Inspection (OCMI) on or after March 11, 1996, must comply with this part. Newly installed bilge/fire pump was not listed on the recently approved one line electrical diagram. It was located in panel 17, slot 14 which is listed as "flow meter". Additionally, the fire pump located in the engine room was not listed on the one line diagram. Update electrical one line diagram and submit to MSC for approval.
46 CFR 120.115
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 September 2025
Resolved 22 December 2025
Resolution: MI verified fire/bilge pump installation & operation, approved one line electrical diagram Rev C and proper labeling of associated equipment on correct electrical panel.
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 14 May 2025
Resolved
SOLAS 1974 II-2 Regulation 21
Currently, All the crew berthing areas (below the bulkhead deck) have two means of escape. However, the second means of escape are in crewmember berthing rooms above the top bunks. Furthermore, the two means of escape for each berthing area lead to a common space (i.e. Lounge/lounges) above the crew berthing areas. Using the forward crew berth as an example: If a fire were to break out in the forward bar (located in the forward lounge) the crew below would have no escape route. The same scenario for the large aft crew berths under the Galley and main passenger lounge.
* Submit plans to Coast Guard Marine Safety Center to correct the deficient means of escape from all three crew berths prior to sailing foreign.
Until the means of escape meet SOLAS 1974 II-2 Regulations 21, the vessel is restricted to domestic voyages only.
Condition: Placed in Improper Service
Action required: 702 - Prior to embarking on international voyage
Due 31 August 2025
Resolved 8 October 2025
Resolution: 08Oct2025, In accordance with 46 C.F.R. § 1.03-15(j), CVC issued an appeal response letter rescinding this requirement. The response letter (ser # 3279) was uploaded into vessel documents.
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 14 May 2025
Resolved
Taking into consideration the means of escape requirements of SOLAS 1974 II-2 Reg 21), SASH requirements found in 46 USC 3106 (Key Control). On October 19, 2024, and ISM Audit was completed with a Nonconformity issued for SASH policies and Key Control implementation. The Corrective actions were implemented on the vessel; however, the implementation of the key control measures directly conflicts with the two means of escape requirements in SOLAS.
Prior to embarking passengers on a foreign voyage, you are required to remove the locks on all three berthing area doors that lead to the second means of escape from the three crew berths below the bulkhead deck.
To conform with the SASH requirements, you are required to reassign the crew members from the rooms with the escape hatches to another appropriate berth.
Condition: Placed in Improper Service
Action required: 702 - Prior to embarking on international voyage
Due 31 August 2025
Resolved 21 November 2025
Resolution: Received email from [name withheld] - Director of Compliance stating The door locks have been removed from the cabins with secondary egress routes, thus restoring a secondary
means of egress.
15 - Safety Management Systems (ISM) › N/A - No Subsystem › Other (ISM)
Issued 14 May 2025
Resolved
ISM CODE 1.2.2 Safety management objectives of the Company should, inter alia: Provide for safe practices in ship operation and a safe working environment, assess all identified risks to its ships, personnel and the environment and establish appropriate safeguards; and continuously improve safety management skills of personnel ashore and aboard ships, including preparing for emergencies related both to safety and environmental protection.
Currently the means of escape routes on the vessel do not meet SOLAS 1974 II-2 Regulation 21 and present a hazard to the crew. If a fire or other emergency were to compromise the lounge areas above the crew quarters, crew members would find themselves without a safe and independent alternative route for egress. This configuration does not provide segregated escape paths for the crew, thereby placing them at increased risk in emergency situations.
* Conduct a Risk Assessment covering the emergency response procedures for a fire outbreak in the passenger lounges above the crew quarters. Consider the impact on crew escape routes, and the resultant effects on vessel operations, including firefighting and abandonment of the vessel and its passengers - with special consideration for conducting these operations with a reduced crew.
Condition: Improper/Lack of Maintenance
Action required: 702 - Prior to embarking on international voyage
Due 14 May 2025
Resolved 8 October 2025
Resolution: 08Oct2025, In accordance with 46 C.F.R. § 1.03-15(j), CVC issued an appeal response letter rescinding this requirement. The response letter (ser # 3279) was uploaded into vessel documents.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 1 May 2025
Resolved
Ships shall be provided with an efficient bilge pumping plant capable of pumping from and draining any watertight compartment under all practicable conditions after a casualty whether the ship is upright or listed. Ships shall have at least three power pumps connected to the bilge main piping system. Where the criterion numeral is 30 or more, one additional independent power pump shall be provided. Plan review by MSC determined NATIONAL GEOGRAPHIC SEA LION has a criterion numeral greater than 30 requiring one additional independent power pump be provided. Provide plans to MSC for approval for one additional independent power pump. Provide one additional independent power pump on vessel. Vessel restricted from international voyage until plans approved and one additional pump installed and tested in accordance with approved plans.
SOLAS (1974) II-1 Reg. 18(b)(i)
Action required: 702 - Prior to embarking on international voyage
Due 1 May 2025
Resolved 20 August 2025
Resolution: Additional pump was installed and tested sat.
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 13 April 2025
Resolved
46 CFR 115.830 (a) At each inspection for certification and at every other vessel inspection all observed unsafe practices, fire hazards, and other hazardous situations must be corrected and all required guards and protective devices must be in satisfactory condition.
Currently there are multiple flammable, explosive and hazardous items being stored in the engine room and not in an approved flammable materials locker.
* You are required to install a flammable material locker for the storage of these materials.
Condition: Improper/Lack of Maintenance
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Due 16 May 2025
Resolved 30 April 2025
Resolution: All flammable and hazardous materials were moved to the aft main deck lockers on the weather deck that are constructed of steel IAW 46 CFR 116.405.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 13 April 2025
Resolved
46 CFR 115.804 (c) Inspection of all machinery essential to the routine operations of the vessel including generators and cooling systems. (d) External inspection of fuel tanks and inspection of tanks vents, piping and pipe fittings.
There was a small fuel leak dripping from the supply hose going to the emergency generator.
* Make proper repairs to fix the fuel leak.
Condition: Improper/Lack of Maintenance
Action required: 15 - Rectify deficiencies by next port
Due 30 April 2025
Resolved 23 April 2025
Resolution: Engineers replaced the leaking fitting on the generator fuel supply hose.
15 - Safety Management Systems (ISM) › N/A - No Subsystem › Maintenance of the ship and equipment
Issued 19 March 2025
Resolved
The company should establish procedures to ensure that the ship is maintained in accordance with the provisions of the relevant rules and regulations established by the company. The technical and/or operational nature of the deficiencies noted above provide objective evidence of a serious failure of the implementation of the ISM Code. A safety management audit satisfactory to the OCMI must be
submitted prior to the clearance of this deficiency.
SOLAS IX, ISM Code A/10
Action required: 30 - Ship detained
Resolved 24 March 2025
Resolution: Audit conducted by class (DNV). 01 non-conformity issued.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 18 March 2025
Resolved
The emergency generator was found to have clear/plastic fuel hose on the fuel return line and a grease fitting with single hose clamp terminating at the fuel tank. Provide emergency generator fuel return with CG approved fuel hose, proper termination fittings, and double hose clamps.
46 CFR 176.25-10(5)
Action required: 30 - Ship detained
Resolved 24 March 2025
Resolution: Approved fuel line installed.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 18 March 2025
Resolved
While testing newly installed bilge/fire pumps #2 and #3, both motor controller overload tripping mechanisms were tripping the circuit and securing the bilge/fire pump. Provide safe electrical overload protection.
46 CFR 177.10-5; 46 111.70-1
Action required: 30 - Ship detained
Resolved 24 March 2025
Resolution: New motors provided.
09 - Working and Living Conditions › 092 - Working Conditions › Protection machinery
Issued 18 March 2025
Resolved
Newly installed bilge/fire pumps #2 and #3 were found with unprotected motor to pump couplings. Provide couplings with machinery guard to prevent personnel injury.
46 CFR 182.10-5
Action required: 30 - Ship detained
Resolved 24 March 2025
Resolution: Guard provided for rotating machinery.
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 18 March 2025
Resolved
Structural fire protection in the engine room overhead (stbd/forward) was found to missing. Restore structural fire protection to A-60 standard.
46 CFR 177.10-5
Action required: 30 - Ship detained
Resolved 24 March 2025
Resolution: SFP provided in engine room overhead.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Operation of machinery
Issued 18 March 2025
Resolved
The aft generator fuel supply piping was found to be missing a support bracket, allowing pipe to move freely and causing a vibration hazard. Repair fuel supply piping bracket.
46 CFR 176.25-10
Action required: 30 - Ship detained
Resolved 24 March 2025
Resolution: Fuel line secured.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Doors
Issued 18 March 2025
Resolved
The engine room to lazarette watertight door indicator switch was found to be inoperable. Make repairs and prove proper operation.
74 SOLAS Reg13, (f) (v)
Action required: 30 - Ship detained
Resolved 24 March 2025
Resolution: WTD indicator operational.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 18 March 2025
Resolved
Fire doors must be capable of closing against an inclination opposing closure. Vessel was not able to demonstrate effective closure of fire doors.
74 SOLAS II-2, Reg 23
Action required: 30 - Ship detained
Resolved 24 March 2025
Resolution: FSD's operational.
04 - Emergency Systems › N/A - No Subsystem › Emergency fire pump and its pipes
Issued 18 March 2025
Resolved
Each fire pump motor controller shall have a low-voltage release installed. Prove newly installed fire pump motor controller are equipped with devices.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 April 2025
Resolved 13 April 2025
Resolution: Witnessed succesful operation of low voltage device.
09 - Working and Living Conditions › 092 - Working Conditions › Machinery
Issued 18 March 2025
Resolved
Protective gratings shall be provided at such locations where persons or gear might come in contact with exhaust pipe. Emergency generator exhaust piping was found to be bare piping and uninsulated. Provide lagging or protective gratings to protect crew and passengers from hot surface. Old T – 46 CFR 182.15-20(g)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 April 2025
Resolved 24 March 2025
Resolution: Lagging provided around e-gen.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 18 March 2025
Resolved
At each subsequent inspection the MI shall examine electrical cables to determine they are in a safe condition. Dead-ended cables were found on a junction box centerline in lazarette and in the port side fantail gear locker. Remove dead-ended cables and seal penetrations. Old T – 46 CFR 176.25-15
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 April 2025
Resolved 24 March 2025
Resolution: Dead end wires removed.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 18 March 2025
Resolved
Receptacle outlets and attached plugs operating at 100 volts or more must have a grounding pole and conductor in the cable. The galley mixer electrical cord was found without a ground terminal on the plug. Repair or replace mixer plug with a three-prong device.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 April 2025
Resolved 24 March 2025
Resolution: New mixer plug provided.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 18 March 2025
Resolved
Each lighting fixture globe must have a guard. The lighting fixture inside the emergency generator compartment was found to be unmounted, with an open socket, and no globe or guard. Repair light fixture to satisfaction of attending marine inspector.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 April 2025
Resolved 24 March 2025
Resolution: Light fixture repaired.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 18 March 2025
Resolved
At each subsequent inspection the MI shall examine electrical devices to determine they are in a safe condition. The electrical outlet mounted on the day tank outboard the starboard main engine was found to be lose and improperly installed. Repair or replace electrical outlet. Old T – 46 CFR 176.25-15
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 April 2025
Resolved 24 March 2025
Resolution: Outlet properly mounted.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Manholes/flush scuttles
Issued 18 March 2025
Resolved
Each watertight hatch must be attached to the frame by hinges, captive chains, or other devices to prevent its loss. Lazarette escape hatch was found without a retaining device/chain. Prove hatch with retaining device.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 April 2025
Resolved 24 March 2025
Resolution: Hatch provided with keeper chain.
10 - Safety of Navigation › N/A - No Subsystem › Other (navigation)
Issued 14 March 2025
Resolved
In accordance with vessel COI each Zodiac shall have a handheld submersible DSC capable radio. Zodiac's did not have DSC capable feature operational. Make each handheld radio for Zodiac’s DSC capable using each Zodiac name prior to taking passengers.
Action required: 705 - Other - as specified
Resolved 18 March 2025
Resolution: Verified deficiency rectified.
04 - Emergency Systems › N/A - No Subsystem › Emergency, lighting, batteries and switches
Issued 14 March 2025
Resolved
Emergency lighting modifications made in accordance with MSC letter E2-2500735. Emergency lighting in forward lounge, aft lounge, galley, and forward / lower stateroom passageway was found to be inoperable. Prove proper operation of emergency lighting prior to vessel departing San Diego.
46 CFR 120.432
Action required: 60 - Rectify deficiencies prior to movement
Resolved 18 March 2025
Resolution: Verified deficiency rectified.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 14 March 2025
Resolved
Bilge and Firemain system modifications made in accordance with MSC letter E1-2500482. Vessel’s bilge piping system is not yet complete. Prove proper operation of new bilge pumps and associated piping.
Vessel restricted from international voyage.
46 CFR 119.510
Action required: 705 - Other - as specified
Resolved 13 April 2025
Resolution: Witnesses sat operation of bilge and fire pumps.
04 - Emergency Systems › N/A - No Subsystem › Emergency, lighting, batteries and switches
Issued 14 March 2025
Resolved
Emergency lighting modifications made in accordance with MSC letter E2-2500735. 50 amp feed breaker was installed for the new inverter panel and the approved plan states 60 amp. Make installation match approved plans or resubmit revised plans to MSC.
46 CFR 120.432
Action required: 60 - Rectify deficiencies prior to movement
Resolved 18 March 2025
Resolution: Verified Deficiency Rectified
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 14 March 2025
Resolved
Shutoff valves, installed so as to close against the fuel flow, must be fitted in the fuel supply lines, one at the tank connection and one at the engine end of the fuel line to stop fuel flow when servicing accessories. Port and STBD shut off valves are not functioning as designed. Make valves operator as designed.
46 CFR 119.455(b)(3)
Action required: 30 - Ship detained
Resolved 24 March 2025
Resolution: Shutoff valves operational.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 14 March 2025
Resolved
A self-propelled vessel must meet the applicable requirements for main and auxiliary steering apparatus in subchapters F (Marine Engineering) and J (Electrical Engineering) of this chapter. Aft steering/local rudder indicator off more than 5 degrees. Test system to
determine which indicator is correct and ensure both indicators indicators are reading the same.
46 CFR 176.25-50
Action required: 30 - Ship detained
Resolved 24 March 2025
Resolution: Steering test completed.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 14 March 2025
Resolved
At each inspection for certification the bilges and other spaces may be examined to see that there is no excessive accumulation of oil, trash, debris, or other matter that might create a fire hazard, clog bilge pumping systems, or block emergency escapes. Observed over 1’ of hydraulic oil in FWD ER bilge. Remove oil from bilge and clean bilge.
46 CFR 115.830(b)
Action required: 60 - Rectify deficiencies prior to movement
Resolved 18 March 2025
Resolution: Verified Deficiency Rectified
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 14 March 2025
Resolved
At each inspection for certification all observed unsafe practices, fire hazards, and other hazardous situations must be corrected. Forward generator PTO hydraulic PMP hoses were chaffed and top layer ripped. Provide new hoses and tag out system until new hoses are provided.
46 CFR 115.830(a)
Action required: 60 - Rectify deficiencies prior to movement
Resolved 18 March 2025
Resolution: Verified Deficiency Rectified.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 14 March 2025
Resolved
Batteries must be mounted in trays lined with, or constructed of, a material that is resistant to damage by the electrolyte and secured to protect against shifting with the roll and pitch of the vessel. Inverter batteries not secured and not in box. Provide box and secure inverter batteries.
46 CFR 120.350(b) and (e)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 April 2025
Resolved 13 April 2025
Resolution: Battery boxes and bateries are secured.
04 - Emergency Systems › N/A - No Subsystem › Damage control plan
Issued 14 March 2025
Resolved
The owner or managing operator shall prepare an evacuation plan that must:
(a) Identify possible casualties involving fires or flooding, including a fire in the largest capacity passenger space in each main vertical zone;
(b) Provide procedures for evacuating all affected spaces for each casualty identified as required by paragraph (a) of this section without abandoning the vessel, including—
(1) Identify readily accessible areas of refuge for the maximum number of persons allowed aboard the vessel. The capacity for an area of refuge may not exceed the number of persons specified in § 116.438(n)(2) of this part, except that one person may be permitted for each 0.28 square meters (3 square feet) of deck area; and
(2) Identify at least two means of escape complying with § 114.400 from the space being evacuated; and
(c) Include procedures to evacuate passengers from the vessel using an abandon ship plan, considering the number of passengers and the vessel’s route. The abandon ship plan must identify at least one escape route from each area of refuge to each embarkation station required by § 116.510 of this part.
-Provide emergency evacuation plan and identify areas of refuge for all persons on board with 3 sq ft deck space (no furnishings) per Pearson. Evacuation plan must be updated to meet regulation.
46 CFR 116.520
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 April 2025
Resolved 24 March 2025
Resolution: Fire control plan updated.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 14 March 2025
Resolved
Approved modifications are in progress to the vessel’s bilge system, discrepancies identified between installation and plans are: pumps 2 and 3 share a strainer, overboard check valve and cut-off valve not accurate, cross-connect valve to raw water system incorrectly installed. Make installation match approved plans or resubmit revised plans to MSC.
46 CFR 119.510
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 April 2025
Resolved 13 April 2025
Resolution: Received MSC Approval and verified operation of the bilge and fire fighting systems.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 14 March 2025
Resolved
Each distribution panel or switchboard must be totally enclosed. Electrical panels (#8 and 15) have openings. Install non-conductive cover/blanks in open spaces.
46 CFR 120.330
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 April 2025
Resolved 24 March 2025
Resolution: Blanks provided for open panels.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 14 March 2025
Resolved
At each inspection for certification the marine inspector shall require that all observed unsafe practices and hazardous situations be corrected. AC raw water piping has 4 temporary pipe repairs. Tag out system and make permanent repairs.
46 CFR 176.25-50
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 April 2025
Resolved 24 March 2025
Resolution: Temp patches are class approved clamps.
11 - Life Saving Appliances › N/A - No Subsystem › Rescue boats
Issued 14 March 2025
Resolved
On a vessel of more than 19.8 meters operating on exposed or partially protected waters, a rescue boat approved under approval series 160.156 is acceptable in meeting the intent of this section. Rescue boat was not found in a list of approved rescue boats. Provide approved rescue boat.
46 CFR 117.210(c)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 April 2025
Resolved 21 January 2026
Resolution: Received CVC Appeal determination on deficiency. Rescue boat can remain installed.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 14 March 2025
Resolved
Master key control system. Vessel needs to meet master key program in accordance with 46 USC 3106. Vessel had some documentation of a master key program in the SMS however, it was not implemented or in practice yet.
46 USC 3106
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 April 2025
Resolved 24 March 2025
Resolution: Master key program implemented.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 14 March 2025
Resolved
Requirement to report sexual offenses. Ensure all applicable safer seas act requirements are implemented in the SMS and annual training is completed.
46 USC 10104
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 April 2025
Resolved 24 March 2025
Resolution: Safer seas act implemented.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 14 March 2025
Resolved
In accordance with the COI, the vessel can carry a maximum of 10 - 6-gallon plastic gasoline containers. 14 were found on the lido deck. Remove 04 6-gallon plastic gasoline containers.
Conditions of COI
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 April 2025
Resolved 24 March 2025
Resolution: 04 gas containers removed.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 14 March 2025
Resolved
Life jacket placards must be posted in each passenger cabin or stateroom on a vessel of more than 65 feet in length with overnight accommodations for more than 49 passengers. Vessel did not have an instruction placard for the type 1 lifejackets that were in the staterooms. Either change the lifejackets or updates the instructions. Provide instructions and post placard for every type of lifejacket in all staterooms.
46 CFR 122.516
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 April 2025
Resolved 24 March 2025
Resolution: Life jacket placard provided.
14 - Pollution Prevention › 141 - MARPOL Annex I › Oil filtering equipment
Issued 14 March 2025
Resolved
A ship must have a "Discharge of Oil Prohibited" placard of at least 5 by 8 inches, made of durable material fixed in a conspicuous place in each machinery space. Placard for “Discharge of Oil Prohibited…” required in OWS space. Also provide line diagram for OWS system.
33 CFR 155.450
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 April 2025
Resolved 24 March 2025
Resolution: Discharge of oil sign provided.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 14 March 2025
Resolved
Tubular gauge glasses, if fitted to diesel fuel tanks must be of heat-resistant materials, adequately and protected from mechanical damage. Gauging tubes at port F/O were not of heat-resistant materials. Provide heat-resistant gauge tubes.
46 CFR 119.440(a)(7)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 April 2025
Resolved 24 March 2025
Resolution: Heat-resistant gauge tubes provided.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 14 March 2025
Resolved
Each ring life buoy on a vessel must be approved in accordance with 46 CFR 160.050. Ring buoy top deck portside line frayed, repair or replace.
46 CFR 117.70
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 April 2025
Resolved 24 March 2025
Resolution: Ring buoy line repaired.
02 - Structural Conditions › N/A - No Subsystem › Stability/strength/loading information and instruments
Issued 14 March 2025
Resolved
Each vessel contracted for before March 11, 1996 may be constructed in accordance with the regulations in effect at the time. However, any alterations or repairs must be done in accordance with § 170.005. Vessel completed dry-dock and made several modifications to the hull. Submit weight added/removed to MSC for review and approval.
46 CFR 170.001(b)/MTN 04-95, CH-2
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 April 2025
Resolved 7 May 2025
Resolution: Vessel rep submitted weight change details to MSC for approval.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 14 March 2025
Resolved
Unless otherwise provided by this subpart, each vessel required to have a Certificate of Inspection is subject to the annual vessel inspection fee listed in table 2.10-101 for its vessel category. Vessel has five inspected inflatable rafts used to transfer passengers during excursions. COI inspections were recently completed without proof of annual inspection fees paid. Provide proof of annual user fees for all five inflatable rafts.
46 CFR 2.10-101
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 April 2025
Resolved 24 March 2025
Resolution: User fee reciepts provided.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 14 March 2025
Resolved
In a passenger ship the required fire pumps shall be capable of delivering for fire-fighting purposes a quantity of water, at the appropriate pressure prescribed below, not less than two-thirds of the quantity required to be dealt with by the bilge pumps when employed for bilge pumping Relief valves shall be provided in conjunction with all fire pumps if the pumps are capable of developing a pressure exceeding the design pressure of the water service pipes, hydrants or hoses. Could not find pressure of system in plans or during testing to verify pressures or to know if relief valves are necessary. Provide calculations to MSC and update plan to show pressure and if relief valves are needed.
SOLAS 74 Ch. II-2 Reg 5(a)(i) and 5(b)(iii).
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 April 2025
Resolved 13 April 2025
Resolution: PER MSC plan review, pressure relief valves are not required. Performed operation tests of the fire pump and associated hydrants - all sat.
02 - Structural Conditions › N/A - No Subsystem › Decks - cracking
Issued 14 March 2025
Resolved
A-Class decks must be made intact with the main structure of the vessel. They must be so constructed that, if subjected to the standard fire test, they are capable of preventing the passage of smoke and flame for 1 hour. New inverter power cable penetrate the main deck to lazarette with air gap showing. Provide A-class boundary where inverter cable penetrates deck.
46 CFR 116.415
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 April 2025
Resolved 13 April 2025
Resolution: Resolved to the satisfaction of the attending MI.
04 - Emergency Systems › N/A - No Subsystem › Damage control plan
Issued 14 March 2025
Resolved
A fire control plan must be posted on the vessel in a location that is accessible and visible to all passengers. The plan must show escape routes, areas of refuge. With changes to emergency evacuation plan, Area of refuge shall be updated on the fire control plan.
46 CFR 116.530
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 April 2025
Resolved 24 March 2025
Resolution: Fire control plan updated.
04 - Emergency Systems › N/A - No Subsystem › Emergency source of power - Emergency generator
Issued 14 March 2025
Resolved
There shall be above the bulkhead deck and outside the machinery casings a self-contained emergency source of electrical power. Emergency generator is not operational. Provide emergency source of power that complies with regulation SOLAS 74 Ch. II-1 Reg 25.
Repair prior to sailing foreign.
Action required: 705 - Other - as specified
Resolved 13 April 2025
Resolution: Emergency generator was witnessed as operational
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 14 March 2025
Resolved
The owner or managing operator shall submit drawings, sketches, or written specifications describing the details of any proposed alterations to the cognizant [name withheld] have been made to the electrical system. New motors for bilge/firefighting installed. Provide updated electrical plans to the MSC for approval.
46 CFR 115.700(b)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 24 April 2025
Resolved 6 June 2025
Resolution: Received objective evidence attesting to submission of diagrams to MSC
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 14 March 2025
Resolved
The owner shall, prior to receiving a Certificate of Inspection, submit for approval to the Marine Safety Center, three copies of the following plans: Ventilation diagrams engine exhaust diagram. Vessel did not have ventilation diagram. Provide diagram for vessel and submit to MSC for review.
46 CFR 116.202(b)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 April 2025
Resolved 6 June 2025
Resolution: Received objective evidence attesting to submission of diagrams to MSC
02 - Structural Conditions › N/A - No Subsystem › Beams, frames, floors-corrosion
Issued 16 January 2025
Resolved
Stiffeners in the sewage tank were found corroded and pulled away from the deck. Submit repair proposal to repair structural integrity.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 28 February 2025
Resolution: Observed fit-up, all SAT
02 - Structural Conditions › N/A - No Subsystem › Hull damage impairing seaworthiness
Issued 5 December 2024
Resolved
Area identified on starboard bow in crew berthing area, needle gun to good material and re gauge.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 18 February 2025
Resolution: Cropped and renewed 18"X30", all SAT
02 - Structural Conditions › N/A - No Subsystem › Decks - corrosion
Issued 5 December 2024
Resolved
Remove deck plates in engine room and ensure bilges are
clean, dry and ready for inspection.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 13 January 2025
Resolution: Completed Inspection
02 - Structural Conditions › N/A - No Subsystem › Bulkhead -corrosion
Issued 5 December 2024
Resolved
Area with a symmetrical crack identified in a 2x3 foot section on port bow that is inaccessible internally. Remove paint to uncover steel and evaluate condition.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 20 January 2025
Resolution: Area cropped, renewed and NDT'd
03 - Water/Weathertight Conditions › N/A - No Subsystem › Machinery space openings
Issued 5 December 2024
Resolved
Three valves were found wasted and require replacement, ensure proper replacement in kind on #'s 20, 25, and 41. Inspect all others prior to re installation. Make available for inspection after cleaning and renewing #31 & 33 or replace in kind.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 18 February 2025
Resolution: Observed and tested valve number 31 and 33, all SAT
03 - Water/Weathertight Conditions › N/A - No Subsystem › Cargo & other hatchways
Issued 5 December 2024
Resolved
When tanks and void spaces not otherwise inspected are made available, coordinate inspection by USCG and ensure spaces are cleaned, dried and gas freed by a marine chemist in previous 24 hours.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 20 January 2025
Resolution: Tanks made available for inspection
02 - Structural Conditions › N/A - No Subsystem › Hull damage impairing seaworthiness
Issued 5 December 2024
Resolved
Once a repair proposal is approved, carry out crop and renews in accordance with the repair proposal and ensure fit up, back gouge and final weld NDT is witnessed by OCMI unless otherwise discussed.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 28 February 2025
Resolution: Repairs completed, all SAT
02 - Structural Conditions › N/A - No Subsystem › Decks - corrosion
Issued 5 December 2024
Resolved
Gauge area in A/C room from cropped area up to waterline, forward to bulkhead and aft to the previously installed new insert. Submit repair proposal with gauge report.
Action required: 705 - Other - as specified
Resolved 28 February 2025
Resolution: Observed repairs (28" X 43"), all SAT
02 - Structural Conditions › N/A - No Subsystem › Ballast, fuel and other tanks
Issued 5 December 2024
Resolved
Holes found in the A1 tank, needlegun area to determine extent of damage and submit repair proposal.
Action required: 705 - Other - as specified
Resolved 28 February 2025
Resolution: Repairs completed, all SAT
02 - Structural Conditions › N/A - No Subsystem › Ballast, fuel and other tanks
Issued 5 December 2024
Resolved
Pit / hole found in starboard day tank, submit repair proposal.
Action required: 705 - Other - as specified
Resolved 18 February 2025
Resolution: Observed repairs (18" X 30") , all SAT
02 - Structural Conditions › N/A - No Subsystem › Bulkhead -corrosion
Issued 5 December 2024
Resolved
Questionable areas were found along the side shell. adjacent to the day tank. Conduct gauging in exposed area and forward and aft until good metal is found.
Submit repair proposal as necessary.
Vessel plans to complete at next drydock.
Action required: 705 - Other - as specified
Due 11 February 2025
Resolved 11 February 2025
Resolution: Vessel plans to complete at next drydock.
09 - Working and Living Conditions › 092 - Working Conditions › Pipes, wires (insulation)
Issued 5 December 2024
Resolved
Test substance near day tank for asbestos and take appropriate measures during repairs.
Action required: 705 - Other - as specified
Resolved 12 February 2025
Resolution: Received insulation/asbestos report, all SAT
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 23 July 2024
Resolved
Propulsion machinery must be suitable in type and design for propulsion requirements of the hull in which it is installed and capable of operating at constant marine load under such requirements without exceeding its designed limitations. Vessel suffered failure to the port main diesel engine turbo. Upon further inspection, coolant was identified in the exhaust manifold. Technician onboard is continuing to diagnose further damage to port main diesel engine. Make repairs to the port MDE and complete satisfactory power trials to the satisfaction of attending Coast Guard Marine Inspector prior to the carriage of passengers.
Action required: 701 - Prior to carriage of passengers/cargo
Due 23 July 2024
Resolved 27 July 2024
Resolution: Tech completed inspection and both turbos on port engine replaced.
07 - Fire Safety › N/A - No Subsystem › Crew alarm
Issued 31 May 2024
Resolved
Vessels described by 46 CFR 114.110(f) must submit plans to the cognizant OCMI, in accordance with 46 CFR 115.700, for the installation and use of monitoring device(s) to ensure the wakefulness of the watchmen required in paragraph (a) of this section.
46 CFR 122.410(b)(2)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 30 June 2024
Resolved 22 December 2025
Resolution: MI verified and tested watchmen monitoring device was installed and operational.
10 - Safety of Navigation › N/A - No Subsystem › Rudder angle indicator
Issued 16 April 2024
Resolved
Each steering-gearing control system must receive its power from the feeder circuit supplying power to its steering-gear power unit. The port and starboard wing controls are inoperable due to a failed circuit board. Make permanent repairs to the satisfaction of the marine inspector prior to carrying passengers.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 17 April 2024
Resolution: Rcvd confirmation from tech of the full operation of controls.
10 - Safety of Navigation › N/A - No Subsystem › Rudder angle indicator
Issued 16 April 2024
Resolved
An audible alarm must activate in the pilothouse upon failure of the electric power to the control system of any steering gear or failure of that power to the power unit of any steering gear. The primary control unit failed to make an audible alarm. Unit was replaced and proved operational.
Action required: 10 - Deficiency Rectified
Resolved 16 April 2024
Resolution: Unit was replaced and fully operational.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 22 December 2023
Resolved
46CFR58.25-10(b)(2)Main/Aux steering gear shall be capable moving the rudder from 35 degrees on either side to 35 degrees at its deepest loaded line draft. #2 steering pump failed to energize. Multiple hours later MI witnessed sat test of #2 steering pump. Root cause was bad fuses. 46CFR119.600
46CFR58.25
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 December 2023
Resolution: Multiple hours later MI witnessed sat test of #2 steering pump. Root cause was bad fuses.
02 - Structural Conditions › N/A - No Subsystem › Ballast, fuel and other tanks
Issued 22 December 2023
Resolved
The construction and arrangement of a vessel must allow the safe operation of the vessel in accordance with the terms of its COI. MI found multiple plexiglass manhole covers throughout the vessel. 46CFR116.100(a)
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 December 2023
Resolution: Original covers installed prior to departing vessel.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 22 December 2023
Resolved
Repairs and Alterations: Newly installed steering system is not approved by the Coast Guard. Owners have 07 days to address comments from MSC letter dated 05 Jan 2023. Provide proof of correspondence with MSC.
Owners have 07 days to submit QFA/DVTPs to MSC for approval as per CG-CVC policy letters 17-07 and 17-08.
Owners have 30 days to test approved DVTPs and to incorporate in preventive maintenance system testing. 46CFR115.700(a)
Action required: 705 - Other - as specified
Due 7 May 2024
Resolved 31 May 2024
Resolution: Completed satisfactory DVTP testing IAW with MSC approved procedures.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 22 December 2023
Resolved
The construction and arrangement of a vessel must allow the safe operation of the vessel in accordance with the terms of its COI. MI found multiple potable water leaks throughout the engine room.46CFR116.100(a)
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 30 December 2023
Resolution: Potable water leaks were repaired by vessels engineering department.
04 - Emergency Systems › N/A - No Subsystem › Means of communication between safety centre and other control stations
Issued 22 December 2023
Resolved
Each vessel must be provided with a sound powered telephone system, complying with subpart 113.30 of this chapter, to communicate between the pilothouse and steering compartment. Sound powered phone from pilothouse to steering compartment is not functioning as designed.46CFR119.600
46CFR58.25-15
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 11 January 2024
Resolution: Received objective evidence from the Master that states the sound powered phones are operating as designed.
11 - Life Saving Appliances › N/A - No Subsystem › Rescue boats
Issued 22 December 2023
Resolved
Weekly maintenance and inspections: Each rescue boat must be visually inspected, engine must be run ahead and stern for not less than 3 min, and each battery for rescue boat engine starting must be brought up to full charge at least once each week. MI noted that rescue boat weekly maintenance/inspections were missed on the following dates - Sept 03, 17, and 24. As per the vessels Safety Managements System, create a non-conformity and corrective action plan. NC/CAP shall be submitted for review to OCMI.46CFR122.720
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 30 December 2023
Resolution: Received/reviewed NC/CAP
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 17 October 2023
Resolved
Crew Training: MI noted that 05 crew members crew familiarization was expired. As per the vessels Safety Managements System, create a non-conformity and corrective action plan. NC/CAR shall be submitted for review to OCMI.46CFR122.420
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 30 December 2023
Resolution: Received/reviewed NC/CAP
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 9 August 2023
Resolved
Each door, hatch, or scuttle, used as a means of escape, must be capable of being opened by one person,
from either side, in both light and dark conditions. The method of opening a means of escape must be obvious, rapid, and of adequate strength. Emergency escape hatch leading from the lazarette compartment to aft main deck, could not be easily opened by one person in case of an emergency requiring egress from the space. Provide temporary solution by 11AUG2023. 46CFR177.500(h)
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 11 August 2023
Resolved 16 April 2024
Resolution: Verified a new hatch was installed.
14 - Pollution Prevention › 141 - MARPOL Annex I › Oil discharge monitoring and control system
Issued 9 August 2023
Resolved
When within 12 nautical miles of the nearest land, any discharge of oil or oily mixtures into the sea from a ship other than an oil tanker... The oily-water separating equipment is equipped with a 15 ppm bilge alarm; for U.S. inspected ships, approved under 46 CFR 162.050. On-board oily-water separating equipment (USCG App No: 162.050/9017/0), could not display all dates/times of use. Provide evidence of proper use of equipment. 33CFR151.10(b)(5)
Condition: Invalid
Action required: 16 - Rectify deficiencies w/in 14 days
Due 23 August 2023
Resolved 19 August 2023
Resolution: Engineering dept was able to demonstrate OCM history with Oil Record Book data.
09 - Working and Living Conditions › 092 - Working Conditions › Safe means of access
Issued 2 May 2023
Resolved
Except as otherwise provided in this section, all vessels shall be provided with not less than two avenues of escape from all general areas accessible to the passengers or where the crew may be quartered or normally employed, so located that if one is not available the other may be. At least one of the avenues of escape shall be independent of watertight doors. Crew berthing's secondary means of escape currently has plywood and/or couch cushions sitting on top of escape hatches, obstructing escape. Illustrate an effection means of unobstructed escape.
Condition: Design Flaw
Action required: 16 - Rectify deficiencies w/in 14 days
Due 15 May 2023
Resolved 9 May 2023
Resolution: O/O sent pictures of obstructed areas cleared, see documents.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 8 December 2021
Resolved
SOLAS 14 II-2/10.10.4: A minimum of two two-way portable radiotelephone apparatus for each fire party for fire-fighter's communication shall be carried on board. Ships constructed before 1 July 2014 shall comply with the requirements of this paragraph not later than the first survey after 1 July 2018. Fire teams had no radios meeting the requirements of above during fire drill.
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 22 December 2021
Resolved 13 December 2021
Resolution: Master purchased 2 intrinsically safe VHF radios to put on board the vessel.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 8 December 2021
Resolved
46 CFR 116.435(c)(6)(i) Doors in A-Class fire control boundaries must meet the following additional requirements. A door in a stairtower, stairway, and main vertical zone bulkhead must meet the following additional requirements. A door must be of the self-closing type capable of closing against a 3.5 list of the vessel. 06 fire screen doors would not close properly. Bridge indicating panel was malfunctioning.
Condition: Improper Installation
Action required: 10 - Deficiency Rectified
Due 8 December 2021
Resolved 8 December 2021
Resolution: Crew corrected prior to departure.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Railing, gangway, walkway and means for safe passage
Issued 23 October 2021
Resolved
PO1: All observed unsafe practices, fire hazards, and other
hazardous situations must be corrected. Vessel
sustained damage to the port side upper deck knife
edge. Submit repair proposal to ensure protection of
the passengers and crew in vicinity of damaged knife
edge, to satisfaction of Officer in Charge, Marine
Inspection.
Condition: Damaged By Earlier Event
Action required: 17 - Rectify deficiencies prior to departure
Due 23 October 2021
Resolved 25 October 2021
Resolution: Received photos from master of temporary repair to the knife edge on the second deck. The crew used splash zone, hardened epoxy to smooth the damaged area, and placed a fitted wooden board in front of the opening to protect passengers.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Scuppers, inlets and discharges
Issued 23 October 2021
Resolved
Where bulwarks on the weather portions of freeboard
or superstructure decks form wells, ample provision
shall be made for rapidly freeing the deck of water
and for draining them. Vessel sustained damage to
port side scupper. Submit repair proposal and
conduct repairs to satisfaction of Officer in Charge,
Marine Inspection, and class.
Condition: Damaged By Earlier Event
Action required: 50 - Rectify deficiencies w/in 30 days
Due 23 November 2021
Resolved 8 December 2021
Resolution: Verified repairs completed, satisfactory to Class and USCG
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 5 May 2021
Resolved
MI to verify ship's repairs to starboard side fuel transfer line and fire main line. For credit drydock.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 21 May 2021
Resolution: Fuel transfer line renewed IAW spcifications and pressure tested. All sat.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 4 November 2019
Resolved
THE MEANS PROVIDED FOR PUMPING BILGES SHALL BE TESTED BY OPERATION. ALL SUCTION STRAINERS SHALL BE EXAMINED. BILGE SUCTION TESTS WERE UNABLE TO BE PERFORMED DUE TO CAGE INSTALLATIONS AND ARRANGEMENT. MAKE ALL WATER TIGHT SPACES AVAILABLE FOR OPERATIONAL TEST OF BILGE SUCTION TO THE SATISFACTION OF THE ATTENDING COAST GUARD MARINE INSPECTOR.
46CFR 176.25-10(a)(7)
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 4 November 2019
Resolved 6 November 2019
Resolution: Vessel proved proper operation of the bilge suction system.
02 - Structural Conditions › N/A - No Subsystem › Bulkhead strength
Issued 4 November 2019
Resolved
PENETRATIONS OF REQUIRED WATERTIGHT DECKS AND BULKHEADS BY ANY RIGID PLASTIC PIPE SYSTEMS ARE PROHIBITED, EXCEPT WHEN: EACH SUCH PENETRATION IS ACCOMPLISHED USING AN ACCEPTABLE METALLIC FITTING, WELDED OR OTHERWISE ATTACHED TO THE BULKHEAD OR DECK BY AN ACCEPTED METHOD; AND AN ACCEPTABLE METALLIC SHUTOFF VALVE IS INSTALLED ADJACENT TO THE THROUGH DECK OR THROUGH BULKHEAD FITTING. THIS VALVE SHALL BE OPERABLE FROM THE BULKHEAD DECK. IF TWO VALVES ARE INSTALLED, ONE ON EITHER SIDE OF THE BULKHEAD, THE VALVES NEED NOT BE OPERABLE FROM THE BULKHEAD DECK PROVIDED IMMEDIATE ACCESS TO BOTH IS POSSIBLE. VESSEL HAS PLASTIC PIPING FROM OWS PENETRATING WATERTIGHT BULKHEAD BETWEEN ENGINE ROOM AND LAZARETTE WITH NO METALLIC FITTING OR ACCEPTABLE VALVE INSTALLATION. PROVE PROPER INSTALLATION IAW REGULATIONS.
46CFR 182.40-1(a)(1)
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Due 4 November 2019
Resolved 6 November 2019
Resolution: Verified proper installation of OWS piping penetrating watertight bulkhead between engine room and lazarrette.
01 - Certificates & Documentation › 011 - Ships Certificates › Certificate of Inspection (COI)
Issued 4 November 2019
Resolved
EACH VESSEL INSPECTED AND CERTIFICATED UNDER THE PROVISIONS OF THIS SUBCHAPTER MUST, WHEN ANY PASSENGERS ARE ABOARD DURING THE TENURE OF THE CERTIFICATE, BE IN FULL COMPLIANCE WITH THE TERMS OF THE CERTIFICATE. PLAN REVIEW AND OFFICIAL CERTIFICATION FOR DIBS AND ZODIACS AUTHORIZED AS TENDERS ON VESSEL'S COI ARE INCOMPLETE. TENDERS ARE INELLIBIBLE FOR OPERATION AS CERTIFICATED SMALL PASSENGER VESSELS UNTIL COMPLETION OF CERTIFICATION, AND THEREFORE ARE RESTRICTED TO CARRYING NO MORE THAN SIX PASSENGERS IN ACCORDANCE WITH APPLICABLE REGULATIONS FOR UNINSPECTED PASSENGER VESSELS.
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Resolved 8 June 2021
Resolution: Tenders completed successful COI Inspections.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 15 February 2019
Resolved
Submit plans for repair to V-2 sewage tank. Crop and renew holed area on inboard bulkhead of the V-2 tank on the sewage processing system.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 15 March 2019
Resolved 15 February 2019
Resolution: Plans submitted by vessel rep.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 11 September 2018
Resolved
Provide proper fire locker installation.
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 1 April 2019
Resolved 15 January 2019
Resolution: Pint store box lined with sheet metal liner.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 11 September 2018
Resolved
Propvide proper storage for excess constuction materials.
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 1 April 2019
Resolved 19 April 2019
Resolution: All gear stowed.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 11 September 2018
Resolved
Confrim all components are completed on the letter from MSC reguarding the UPS bridge navigation equipment dated August 24, 2018 Project # PO11649
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 1 April 2019
Resolved 19 April 2019
Resolution: Compenents all installed. Standing by for approval letter from MSC for specfic vessel.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 11 September 2018
Resolved
Chase and eliminate 120 VAC ground fault located on bridge panel
Condition: Improper/Lack of Maintenance
Due 1 April 2019
Resolved 27 February 2019
Resolution: 120 VAC ground fault located and eliminated.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 11 September 2018
Resolved
Replace busted prop on Dib "Leo"
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 April 2019
Resolved 16 December 2018
Resolution: Received picture of replace prop.
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 11 September 2018
Resolved
Seal all penetrations on th ebridge with approved SFP
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 April 2019
Resolved 31 January 2019
Resolution: All penetrations have been sealed.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 11 September 2018
Resolved
Demontrate proper operation FSD at galley
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 April 2019
Resolved 22 December 2018
Resolution: Viseo sent of FSD in galley operating as designed.
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 11 September 2018
Resolved
Provide proper escape route markings to properly match the FCP
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Resolved 24 January 2019
Resolution: Escape route marking now properly matches the fire control plan.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 11 September 2018
Resolved
Provide proper markings and number for PFD storage.
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 1 April 2019
Resolved 25 February 2019
Resolution: Photo received showing new placards installed for lifejacket storage.
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 11 September 2018
Resolved
Demontrate proper operation of the emergency lighting in the aft passageway.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 April 2019
Resolved 4 January 2019
Resolution: Emergency light is now working above emergency swithcboard in aft passageway.
01 - Certificates & Documentation › 011 - Ships Certificates › Continuous synopsis record
Issued 11 September 2018
Resolved
Provide current/up to date CSR
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 April 2019
Resolved 8 January 2019
Resolution: CSR updated at NVDC.
14 - Pollution Prevention › 144 - MARPOL Annex IV (Not Applicable to PSC Exams conducted in the U.S.) › Other (MARPOL Annex IV)
Issued 11 September 2018
Resolved
Holed inboard V-2 sewage tank.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 February 2019
Resolved 19 April 2019
Resolution: Sewage tank repaired. Welded 18x18 insert.
Fire Fighting › Means of Escape › Escape Route Signs
Issued 22 May 2016
Resolved
Label laz emergency escape hatch in accordance with 46 CFR 122.606
Condition: Invalid
Action required: 705 - Other - as specified
Due 29 May 2016
Resolved 26 May 2016
Resolution: vessel marked escape hatch.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Operating Controls
Issued 22 May 2016
Resolved
Controls for engine room fixed CO2 system engine shut down shall be moved to a location outside the space protected by an authorized company.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 1 November 2016
Resolved 11 November 2016
Resolution: Pressure switch moved to outside engine room during 2016 drydock.