Records from 2003 to 2025. Most recent: inspection, 17 June 2025.
07 - Fire Safety › N/A - No Subsystem › Fire pumps and its pipes
Issued 18 June 2025
Resolved
A fire hose with a nozzle must be attached to each fire hydrant at all times. 2nd Deck fire hose found to be holed.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 18 July 2025
Resolved 22 July 2025
Resolution: Hoses replaced
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 18 June 2025
Resolved
A vessel must be provided with bilge pumps in accordance with Table 182.520(a). One of the required two bilge pumps found inoperable.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 18 July 2025
Resolved 12 September 2025
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Operation of machinery
Issued 17 June 2025
Resolved
Control of the main steering gear, including control of any necessary associated devices (motor, pump, valve, etc.), must be provided from the operating station. Power driven main steering pump is not operating when turned on from the bridge.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 18 June 2025
Resolution: Identified faulty switch. Replaced. Tested satisfactory.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 17 June 2025
Resolved
The engine head, block, and exhaust manifold must be water-jacketed and cooled by water from a pump that operates whenever the engine is operating. Main generator heat exchanger wasted and holed leaking approximately 1 gallon per minute.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 18 June 2025
Resolution: Wasted housing material cropped and renewed.
08 - Alarms › N/A - No Subsystem › Other (alarms)
Issued 17 June 2025
Resolved
On a vessel of at least 7.9 meters (26 feet) in length, a visual and audible alarm must be provided at the operating station to indicate a high water level. High water level alarm panel at operating station is not working properly. An extra crew member is required on vessel to monitor bilges unit deficiency is corrected.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 22 July 2025
Resolution: Replaced panel with new
01 - Certificates & Documentation › 011 - Ships Certificates › USCG Certificate of Documentation (COD)
Issued 17 June 2025
Resolved
The name of the vessel must be marked on some clearly visible exterior part of the port and starboard bow and the stern of the vessel. The markings required by this section must be made in clearly legible letters of the Latin alphabet or Arabic or Roman numerals not less than four inches in height. Vessel's name is not on the bow.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 18 July 2025
Resolved 22 July 2025
Resolution: Name installed
09 - Working and Living Conditions › 091 - Living Conditions › Water, pipes, tanks
Issued 17 June 2025
Resolved
Each potable water tank shall be provided with a means of drainage and, if it is equipped with a manhole, overflow, vent, or a device for measuring depth of water, provision shall be made to prevent entrance into the tank of any contaminating substance. Water tank fill missing cap and vent screen. 21 CFR 1250.82(C)
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 18 July 2025
Resolved 12 September 2025
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 17 June 2025
Resolved
Waste receptacles. Unless other means are provided to ensure that a potential waste receptacle fire would be limited to the receptacle, waste receptacles must be constructed of noncombustible materials with no openings in the sides or bottom. All waste bins on vessel are made of combustible plastic material.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 18 July 2025
Resolved 22 July 2025
Resolution: Replaced with non combustible cans
01 - Certificates & Documentation › 011 - Ships Certificates › Cargo Ship Safety Radio (including exemption)
Issued 17 June 2025
Resolved
Each ship transporting more than six passengers for hire equipped with a radiotelephone station in accordance with Part III of Title III of the Communications Act must carry a radio operator who meets the following requirements:
(1) Where the station power does not exceed 250 watts carrier power or 1500 watts peak envelope power, the radio operator must hold a marine radio operator permit or higher class license. Vessel captain did not have a FCC marine radio operator permit. 47 CFR 80.159(e)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 18 July 2025
Resolved 12 September 2025
05 - Radio Communications › N/A - No Subsystem › Main installation
Issued 17 June 2025
Resolved
Except as noted in paragraph (c) of this section, stations in the maritime service must be licensed by the FCC either individually or by fleet. FCC station license is registered to the vessel's old owner. 47 CFR 80.13(a)
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 18 July 2025
Resolved 12 September 2025
18 - Maritime Labour Convention (Not Applicable to PSC Exams conducted in the U.S.) › N/A - No Subsystem › Other (Conditions of employment)
Issued 17 June 2025
Resolved
No marine employer may engage or employ any individual to serve as a crewmember unless the individual passes a chemical test for dangerous drugs for that employer. 1 Captain and 1 Deckhand were missing from DAPI test list.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 18 July 2025
Resolved 22 July 2025
04 - Emergency Systems › N/A - No Subsystem › Means of communication between safety centre and other control stations
Issued 17 June 2025
Resolved
On a vessel of more than 19.8 meters (65 feet) in length, the public address system must be a fixed installation and be audible during normal operating conditions throughout the accommodation spaces and all other spaces normally manned by crew members. Public address system was not working
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 18 July 2025
Resolved 12 September 2025
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 17 June 2025
Resolved
The minimum number of portable fire extinguishers required on a vessel must be acceptable to the cognizant Officer in Charge, Marine Inspection, but must not be fewer than the minimum number required by table 1 to § 181.500(b) and other provisions of this section. Vessel is missing extinguisher for engine room and pantry/bar area.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 18 July 2025
Resolved 12 September 2025
10 - Safety of Navigation › N/A - No Subsystem › Lights, shapes, sound-signals
Issued 17 June 2025
Resolved
A vessel at anchor shall exhibit where it can best be seen in the fore part, an all-round white light. Anchor light not working
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 18 July 2025
Resolved 12 September 2025
10 - Safety of Navigation › N/A - No Subsystem › Nautical publications
Issued 17 June 2025
Resolved
As appropriate for the intended voyage, a vessel must carry adequate and up-to-date: (2) U.S. Coast Pilot or similar publication; (3) Coast Guard Light List; (4) Tide tables; and (5) Current tables, or a river current publication issued by the U.S. Army Corps of Engineers or a river authority. Required publications were missing
Action required: 50 - Rectify deficiencies w/in 30 days
Due 18 July 2025
Resolved 12 September 2025
11 - Life Saving Appliances › N/A - No Subsystem › Distress flares
Issued 17 June 2025
Resolved
Lakes, bays, and sounds, and rivers routes. A vessel on a lakes, bays, and sounds, or rivers route must carry:
(1) Three hand red flare distress signals approved in accordance with § 160.021 in subchapter Q of this chapter, or other standard specified by the Commandant; and (2) Three hand orange smoke distress signals approved in accordance with § 160.037 in subchapter Q of this chapter, or other standard specified by the Commandant. Distress signals on vessel were expired.
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 18 July 2025
Resolved 22 July 2025
Resolution: Replaced with new
04 - Emergency Systems › N/A - No Subsystem › Emergency, lighting, batteries and switches
Issued 17 June 2025
Resolved
Each vessel must be equipped with at least two operable portable battery lights. One of these lights must be located at the operating station and the other at the access to the propulsion machinery space. Portable light at operating station not working
Condition: Improper/Lack of Maintenance
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Due 18 July 2025
Resolved 22 July 2025
Resolution: Provided working light
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 17 June 2025
Resolved
Valves for removing water or impurities from diesel fuel in water traps or strainers are permitted. These valves must be provided with caps or plugs to prevent fuel leakage. Racor fuel filter for main generator equipped with drain valve but missing cap.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 18 July 2025
Resolved 12 September 2025
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 17 June 2025
Resolved
In systems where flexible hoses are permitted, two clamps must be on each end of the hose. The cooling hose on the steering system is missing a clamp.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 18 July 2025
Resolved 22 July 2025
Resolution: Hose clamp installed
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 17 June 2025
Resolved
All machinery and equipment must be installed and maintained in such a manner as to afford adequate protection from causing fire, explosion, machinery failure, and personnel injury. Belt on starboard engine for bilge pump PTO loose and belt for port engine jacket water pump loose.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 18 July 2025
Resolved 12 September 2025
09 - Working and Living Conditions › 091 - Living Conditions › Medical Equipment
Issued 17 June 2025
Resolved
A vessel must carry either a First Aid Kit that meets the requirements of 46CFR199.175(b)(10) or a kit with equivalent contents and instructions. FA kit must meet the requirements of ISO 188.13:2006(E). First Aid kit was missing items.
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 18 July 2025
Resolved 22 July 2025
Resolution: Replaced with new
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 17 June 2025
Resolved
Placards containing instructions for the donning and use of the life jackets aboard the vessel must be posted in conspicuous places that are regularly accessible to the crew and passengers. Placard was missing on second deck.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 18 July 2025
Resolved 22 July 2025
Resolution: Plaquared installed
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 17 June 2025
Resolved
The number and identification of the items stowed inside and their sized must be marked in clearly legible letters and numbers on each container. Letters and numbers must be at least 2 inches high. Storage location was not marked legibly.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 18 July 2025
Resolved 22 July 2025
Resolution: Location marked
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 17 June 2025
Resolved
A vessel must carry one floating waterlight. Lifebouy waterlight inop. Replace.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 18 July 2025
Resolved 22 July 2025
Resolution: Battery replaced
09 - Working and Living Conditions › 091 - Living Conditions › Electrical devices
Issued 17 June 2025
Resolved
Each light fixture globe, lense or diffuser must have a guard. All florescent lights below deck were secured with zip ties and did not have guards.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 18 July 2025
Resolved 12 September 2025
07 - Fire Safety › N/A - No Subsystem › Ventilation
Issued 17 June 2025
Resolved
The discharge ends of fuel tank vent pipes must be fitted with removable flame screens or flame arresters. The flame screens must consist of a single screen corrosion resistant wire of at least 30 x 30. The flame screen was missing.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 18 July 2025
Resolved 12 September 2025
01 - Certificates & Documentation › 013 - Documents › Log-books/compulsory entries
Issued 17 June 2025
Resolved
Portable fire extinguishers must be inspected and maintained IAW NFPA 10. Vessel did not have log of monthly fire extinguisher checks.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 18 July 2025
Resolved 12 September 2025
01 - Certificates & Documentation › 013 - Documents › Log-books/compulsory entries
Issued 17 June 2025
Resolved
Man over board drills and training shall be logged. Vessel did not have proof of completion of MOB drills and training.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 18 July 2025
Resolved 22 July 2025
Resolution: Drills completed
01 - Certificates & Documentation › 013 - Documents › Log-books/compulsory entries
Issued 17 June 2025
Resolved
Fire firefighting drills and training shall be logged. Vessel did not have proof of completion of fire fighting drills and training.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 18 July 2025
Resolved 22 July 2025
Resolution: Drills completed
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 12 July 2024
Resolved
Failure to meet requirements of 46 CFR Part 16
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 21 April 2026
Resolution: DAPI updated, all sat.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 13 June 2024
Resolved
46 CFR 46.180.70:A vessel must have one or more ring life buoys.02 lifebouys have deteriorated grab lines. Repair or replace to Marine Inspector satisfaction.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 4 July 2024
Resolved 14 June 2024
Resolution: Life rings replaced, all sat.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 13 June 2024
Resolved
46 CFR 182.420:Engine cooling, all engines must be water cooled. Primary generator has a pinhole leak in Heat exchanger. Repair/Replace to the satisfation of Coast Guard Marine Inspector.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 June 2024
Resolved 14 June 2024
Resolution: Coolant pipe replaced, all sat.
04 - Emergency Systems › N/A - No Subsystem › Man Overboard Drill (MOB)
Issued 13 June 2024
Resolved
46 CFR 185.728 (f):Abandon ship and man overboard drills and training shall be logged or otherwise documented for review by the Coast Guard upon request. The drill entry shall include the following information: (1) Date of the drill and training; and (2) General description of the drill scenario and training topics. Master shall ensure drills are being logged IAW CFR
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 June 2024
Resolved 14 June 2024
Resolution: Drill logs updated, all sat.
04 - Emergency Systems › N/A - No Subsystem › Fire drills
Issued 13 June 2024
Resolved
46 CFR 185.524 (d):Fire fighting drills and training shall be logged or otherwise documented for review by the Coast Guard upon request.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 June 2024
Resolved 14 June 2024
Resolution: Drill logs updated, all sat.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 13 June 2024
Resolved
46 CFR 16.260:Employers must maintain records of chemical tests and must make these records available to Coast Guard officials upon request. Only Master and one deckhand were on Consortium. All crew need to be in in full compliance on the consortium. Submit updated consortium with a Master and 2 deckhands in full compliance.
Condition: Invalid
Action required: 701 - Prior to carriage of passengers/cargo
Due 27 June 2024
Resolved 18 July 2024
Resolution: All deckhands were added to the consortium, all sat.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 13 June 2023
Resolved
Each floating water light… must be attached to the lanyard with a corrosion resistant clip. Replace floating water light battery and attach to the ring buoy via lanyard and clip.
46 CFR 180.70(d)
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 16 June 2023
Resolution: Proof of item correction recieved.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 13 June 2023
Resolved
Fire hazards to be minimized. Correct fuel leaks for aux generator's fuel strainers and isolation valves.
46 CFR 177.405(a)
Action required: 17 - Rectify deficiencies prior to departure
Resolved 16 June 2023
Resolution: Proof of item correction recieved.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 13 June 2023
Resolved
A vessel of more than 65ft in length must carry a minimum of three life buoys. Renew deteriorated ring buoy lines or replace ring buoys.
46 CFR 180.70
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 16 June 2023
Resolution: Proof of item correction recieved.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 13 June 2023
Resolved
A bilge suction must be fitted with a suitable strainer. Install strainer in aft compartment.
46 CFR 182.510(b)
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 16 June 2023
Resolution: Proof of item correction recieved.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 13 June 2023
Resolved
A vessel must be provided with a satisfactory arrangement for draining any watertight compartment. Clean all check valves for bilge suction and perform operational testing.
46 CFR 182.500(a)
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 16 June 2023
Resolution: Proof of item correction recieved.
11 - Life Saving Appliances › N/A - No Subsystem › Other (life saving)
Issued 13 June 2023
Resolved
A vessel must carry either a first aid kit that meets the requirements in 46 CFR 199.175(b)(10) or a kit with equivalent contents. Obtained proper first aid kit.
46 CFR 184.710
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 16 June 2023
Resolution: Proof of item correction recieved.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 13 June 2023
Resolved
Electrical equipment on a vessel must be installed and maintained to provide services necessary for safety and emergency conditions. Charge or renew (if necessary) electrical equipment for starting propulsion machinery. Perform testing of machinery remotely form the operating station.
46 CFR 183.200
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 16 June 2023
Resolution: Proof of item correction recieved.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Insulation wetted through (oil)
Issued 7 April 2022
Resolved
At each inspection for certification and at every other vessel inspection the bilges and other spaces may be examined to see that there is no excessive accumulation of oil, some of the overhead insulation is saturated with oil. Remove and replace insulation with approved material.
46 CFR 176.830(b)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 21 April 2022
Resolved 21 April 2022
Resolution: All insulation was removed and replaced with new.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 7 April 2022
Resolved
A suitable metal marine type strainer, meeting the requirements of the engine manufacturer, must be fitted in the fuel supply line in the engine compartment. Strainers must be leak free. Aft generator had a leak on Raicor housing. Replace necessary parts and test for leaks.
46 CFR 182.455(b)(6)
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 8 April 2022
Resolution: Vessel replaced parts. No leaks found.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 7 April 2022
Resolved
Shutoff valves, installed so as to close against the fuel flow, must be fitted in the fuel supply lines, one at the tank connection. Stbd valve wasn't fully closing when pulling from emergency shutoff. Adjust until valve is fully close.
46 CFR 182.455 (b)(4)
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 8 April 2022
Resolution: Vessel adjusted valve. Test Sat
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 7 April 2022
Resolved
At each inspection for certification and at every other vessel inspection all observed unsafe practices, fire hazards, must be in satisfactory condition. Center fuel tank supply valve is leaking. Fix and test.
46 CFR 176.830(a)
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 8 April 2022
Resolution: Vessel tighten valve. No leaks found.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 7 April 2022
Resolved
Electrical equipment on a vessel must be installed and maintained to, protect passengers, crew, other persons, and the vessel from electrical hazards, including fire, caused by or originating in electrical equipment, and electrical shock. Remove all temporary extension cords and lights from Engine Room and Steering Compartment.
46 CFR 183.200(b)
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 8 April 2022
Resolution: Vessel removed all temporary extension cords and lights.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 7 April 2022
Resolved
Each battery must be located as high above the bilge as practicable, secured to protect against shifting with the roll and pitch of the vessel... Mount and secure anchor windlass batteries to prevent shifting.
46 CFR 183.350(b)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 21 April 2022
Resolved 21 April 2022
Resolution: All batteries were secured with approved brackets and straps.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 7 April 2022
Resolved
Electrical equipment on a vessel must be installed and maintained to, protect vessel from electrical hazards, clean corrosion on battery terminals.
46 CFR 183.200 (b)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 21 April 2022
Resolved 21 April 2022
Resolution: Vessel cleaned and protected all battery terminals onboard.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 7 April 2022
Resolved
Electrical equipment on a vessel must be installed and maintained to, protect vessel from electrical hazards, clean corrosion on battery terminals.
46 CFR 183.200 (b)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 21 April 2022
Resolved 21 April 2022
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 7 April 2022
Resolved
All machinery and equipment must be installed and maintained in such a manner as to afford adequate protection from machinery failure, Air conditioning pump is leaking, replace parts and test.
46 CFR 182.100
Action required: 16 - Rectify deficiencies w/in 14 days
Due 21 April 2022
Resolved 21 April 2022
Resolution: Vessel replaced pump with new one. Test Sat.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 7 April 2022
Resolved
All machinery and equipment must be installed and maintained in such a manner as to afford adequate protection from machinery failure, Forward generator water pump is leaking. Replace parts and test.
46 CFR 182.100
Action required: 16 - Rectify deficiencies w/in 14 days
Due 21 April 2022
Resolved 21 April 2022
Resolution: Vessel replaced pump gasket. Test Sat
09 - Working and Living Conditions › 092 - Working Conditions › Guards - fencing around dangerous machinery parts
Issued 7 April 2022
Resolved
All machinery and equipment must be installed and maintained in such a manner as to afford adequate protection from machinery failure, remove plastic zip-ties from generator exhaust blanket.
46 CFR 182.100
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 8 April 2022
Resolution: Zip ties were replaced with metal wire.
07 - Fire Safety › N/A - No Subsystem › Ventilation
Issued 7 April 2022
Resolved
Provision must be made for closing all supply duct cowls or scoops and exhaust duct discharge openings for a space protected by a fixed gas extinguishing system, Both engine room vents aren't closing. Adjust and test
46 CFR 182.465(h)
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 8 April 2022
Resolution: Ventilation pull handles were lube and vessel added foam in between vents. Test Sat
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 7 April 2022
Resolved
Each ring life buoy on a vessel must: (1) Be approved in accordance with § 160.050 in subchapter Q of this chapter, or other standard specified by the Commandant, life rings grab lines are deteriorating. Replace with new life ring.
46 CFR 180.70 (b)(1)
Action required: 701 - Prior to carriage of passengers/cargo
Due 13 April 2022
Resolved 8 April 2022
Resolution: Vessel acquired new life rings.
01 - Certificates & Documentation › 012 - Crew Certificates › Medical certificate
Issued 7 April 2022
Resolved
Medical certificates issued to all other mariners will be issued for a maximum period of 5 years. Provide medical certificates for all MMC holders.
46 CFR 10.301 (b)(3)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 5 May 2022
Resolved 5 May 2022
10 - Safety of Navigation › N/A - No Subsystem › Record of drills and steering gear tests
Issued 7 April 2022
Resolved
Abandon ship, man overboard drills, Fire fighting drills and training shall be logged or otherwise documented for review by the Coast Guard upon request. Provide logbook with all drills records.
46 CFR 185.520/524
Action required: 50 - Rectify deficiencies w/in 30 days
Due 5 May 2022
Resolved 5 May 2022
05 - Radio Communications › N/A - No Subsystem › Other (radio communication)
Issued 7 April 2022
Resolved
Radio telephony safety certificate wasn't on-board at the time of inspection. Provide this office with certificate. Vessel is restricted to 1000 FT from shore until certificate is provided.
46 CFR 80.903
Action required: 16 - Rectify deficiencies w/in 14 days
Due 21 April 2022
Resolved 5 May 2022
11 - Life Saving Appliances › N/A - No Subsystem › Distress flares
Issued 7 April 2022
Resolved
Each flare carried to meet this section must be stowed in one of the following: (1) A portable watertight container marked as required by § 185.614 of this chapter, carried at the operating station; Replace and mark new container.
46 CFR 180.68(e)(1)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 21 April 2022
Resolved 21 April 2022
Resolution: Vessel replaced container with new. All Sat
07 - Fire Safety › N/A - No Subsystem › Ventilation
Issued 25 March 2021
Resolved
Provision must be made for closing all supply duct cowls or scoops and exhaust duct discharge openings for a space protected by a fized fas entringuishing system.
Engine room ventilation louvers were not closing.
46CFR182.465(h)
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 8 April 2021
Resolved 25 March 2021
Resolution: Crew members conducted repairs on and demonstrated proper operation of ventilation louvers.
10 - Safety of Navigation › N/A - No Subsystem › Lights, shapes, sound-signals
Issued 23 April 2019
Resolved
Stern light was inoperable.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 7 May 2019
Resolved 17 May 2019
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Gauges, thermometers, etc
Issued 23 April 2019
Resolved
Oil pressure gauge port side inoperable.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 7 May 2019
Resolved 17 May 2019
01 - Certificates & Documentation › 013 - Documents › Log-books/compulsory entries
Issued 23 April 2019
Resolved
Drills are not being recorded as required.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 17 May 2019
Engineering › Shafting/Propeller Arrangements › Propeller (fixed pitch)
Issued 23 July 2015
Resolved
Vessel is to dry dock and make permanent repairs to port prop to the satisfaction of the attending Coast Guard Marine Inspector.
Condition: Damaged By Earlier Event
Action required: 705 - Other - as specified
Due 4 August 2015
Resolved 3 August 2015
Resolution: Attended in dry-dock and witnessed instillation of 2 new props.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Servicing
Issued 5 May 2014
Resolved
Provide service report for fixed CO2 system in machinery space.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 14 May 2014
Resolution: Received copy of service report.
Engineering › Fuel Oil Service System › Filter
Issued 29 April 2009
Resolved
Remove and replace both generators Fuel oil Strainers IAW 46 CFR 182.455 Plastic Bowls not marine type approved.
Action required: 705 - Other - as specified
Due 29 May 2009
Resolved 18 June 2009
Resolution: Metal bowls installed
Stability › Incline Test › General
Issued 29 April 2009
Resolved
Secure Fixed Ballast within Fuel Oil Tank Compartment IAW 46 CFR 178.510
Action required: 705 - Other - as specified
Due 29 May 2009
Resolved 8 April 2010
Resolution: Ballast Secured
Documentation › Certificates/Documents › Stability Letter
Issued 29 April 2009
Resolved
Obtain proper stability letter and approved Ballast Drawing from MSC. Current Stability letter does not mention Fix Ballast located in the Fuel Tank Compartment. IAW 46 CFR 178.230
Action required: 705 - Other - as specified
Due 29 May 2009
Resolved 18 June 2009
Resolution: Stability ltr and ballast drawing obtained
Operations/Management › Passenger Operations › Safety Orientation
Issued 5 May 2008
Resolved
Provide means for providing passenger count on shore when vessel is underway 46 CFR 185.504
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 6 May 2008
Resolution: Box provided on home dock with passenger count maintained for each voyage.
Engineering › Lubricating Oil Service System › Gauge
Issued 5 May 2008
Resolved
Oil pressure guage for port main engine inoperable . Repair and make operational
Action required: 705 - Other - as specified
Due 19 May 2008
Resolved 22 July 2008
Resolution: Oil Pressure Gauge was replaced. Operator showed both oil pressure gauges operating normally.
Electrical › Electrical Distribution System (service) › Conductor
Issued 5 May 2008
Resolved
Remove electrical extension cord from tv on main deck to space below.
Action required: 705 - Other - as specified
Due 19 May 2008
Resolved 22 July 2008
Resolution: Electric cord extension was removed from TV located on the main deck. The owner install additional electric outlet located within the cabinetry housing the TV.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Servicing
Issued 11 April 2007
Resolved
Fixed fire fighting system was not annually serviced for engine room or galley.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 13 April 2007
Resolution: Both systems satisfactorily tested by Nardini Fire Equipment Co.
Lifesaving › Lifejacket/PFD (General) › Quantity
Issued 11 April 2007
Resolved
Missing 2 required child life jackets Vessel restricted to only 13 child size individuals until required life jackets are on board.
Action required: 705 - Other - as specified
Resolved 13 April 2007
Resolution: Vessel has required number of approved child size life jackets.
Documentation › Certificates/Documents
Issued 27 April 2004
Resolved
Provide and post original stability letter IAW 46 CFR 176.306 LEGACY COMPONENT DESC: Stability Letter
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Resolved 7 May 2004
Resolution: Observed properly posted stability letter.
Personnel › Certificates/Documents/Licenses
Issued 27 April 2004
Resolved
Provide proof of First Aid/CPR training for 50% of crew IAW NVIC 1-91. LEGACY COMPONENT DESC: First Aid/CPR Training
Action required: 705 - Other - as specified
Resolved 7 May 2004
Resolution: Observed First Aid/CPR Training Certificates for over 50% of the crew.
Documentation › Certificates/Documents
Issued 27 April 2004
Resolved
[withheld — contains personal information; the deficiency system, dates, and resolution status are shown above]
Action required: 705 - Other - as specified
Resolved 7 May 2004
Resolution: Observed master''s pictured driver''s license.
Engineering › Fuel Oil Storage/Transfer System
Issued 27 April 2004
Resolved
Provide flame screens at fuel vents IAW 46 CFR 182.450. LEGACY COMPONENT DESC: Vent Pipe
Action required: 705 - Other - as specified
Resolved 7 May 2004
Resolution: Observed proper flame screens on fuel & sewage vent pipes.
Engineering › Fuel Oil Storage/Transfer System
Issued 27 April 2004
Resolved
Prove proper installation fuel tank and vent hose to meet standards IAW 46 CFR 182.445. LEGACY COMPONENT DESC: Hose
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Resolved 7 May 2004
Resolution: Owner provided paper documentation showing hoses meet USCG Regulations.
Engineering › Fuel Oil Service System
Issued 27 April 2004
Resolved
Install flexible hose in all piping systems and double clamp IAW 46 CFR 182.720. LEGACY COMPONENT DESC: Hose
Condition: Improper Installation
Action required: 705 - Other - as specified
Resolved 7 May 2004
Resolution: Observed proper installation of all piping systems.
Lifesaving › Lifejacket/PFD (General)
Issued 27 April 2004
Resolved
Properly label the adult PFD storage locker IAW 46 CFR 185.604. LEGACY COMPONENT DESC: Storage
Action required: 705 - Other - as specified
Resolved 7 May 2004
Resolution: Observed proper labeling of adult PFD storage locker.
Lifesaving › Lifejacket/PFD (General)
Issued 27 April 2004
Resolved
Properly display PFD donning instructions placard IAW 185.516. LEGACY COMPONENT DESC: Instructions
Action required: 705 - Other - as specified
Resolved 7 May 2004
Resolution: Observed properly posted PFD donning instructions.
Lifesaving › Lifebuoys
Issued 27 April 2004
Resolved
Provide 60ft floatable line for ring buoy IAW 46 CFR 180.70. LEGACY COMPONENT DESC: Buoyant Lifeline
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 7 May 2004
Resolution: Observed proper new 60ft floatable line for ring buoy.
Fire Fighting › Portable Dry Chemical Fire Extinguisher
Issued 27 April 2004
Resolved
Properly relocate galley fire extinguisher to make readilly accessable IAW 181.520. LEGACY COMPONENT DESC: Location
Condition: Improper Installation
Action required: 705 - Other - as specified
Resolved 7 May 2004
Resolution: Observed properly relocated and mounted portable fire extinguisher.
Documentation › Logs/Records
Issued 27 April 2004
Resolved
Provide crew training records and log IAW 46 CFR 185.420. LEGACY COMPONENT DESC: Training Records
Action required: 705 - Other - as specified
Resolved 7 May 2004
Resolution: Observed proper training and log for master and crewmembers.
Operations/Management › Navigation Safety
Issued 27 April 2004
Resolved
Provide updated Light List and Charts for area of operation IAW 46 CFR 184.420 LEGACY COMPONENT DESC: Carriage of Charts and Publications
Action required: 705 - Other - as specified
Resolved 7 May 2004
Resolution: Observed up to date chart and light list for area of operation.
Operations/Management › Drug and Alcohol Testing › Proof of Enrollment
Issued 17 November 2003
Resolved
NEW OWNER OR OPERATOR MUST PROVIDE COMPLIANCE OF ENROLLEMNET.
Condition: Unknown
Action required: 705 - Other - as specified
Resolved 7 May 2004
Documentation › Certificates/Documents › Certificate of Documentation (CG-1270)
Issued 17 November 2003
Resolved
PROVIDE PROOF OF DOCUMENTATION.
Condition: Unknown
Action required: 705 - Other - as specified
Resolved 7 May 2004
Lifesaving › Lifebuoys › Self-igniting Lights
Issued 17 November 2003
Resolved
MISSING BATTERIES.
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 10 January 2004
Resolved 7 May 2004
Operations/Management › Drills/Instruction › Man Overboard Recovery
Issued 17 November 2003
Resolved
NEW OWNER MUST CONDUCTED DRILLS PRIOR TO CARRYING PASSENGERS.
Condition: Unknown
Action required: 705 - Other - as specified
Resolved 7 May 2004
Personnel › Certificates/Documents/Licenses › License, Master
Issued 17 November 2003
Resolved
[withheld — contains personal information; the deficiency system, dates, and resolution status are shown above]
Condition: Unknown
Action required: 705 - Other - as specified
Resolved 7 May 2004
Electrical › Electric Generation Source (emergency) › Panelboard
Issued 17 November 2003
Resolved
GAUGES AND GENERATOR COULD NOT OPERATE AT FULL CAPACITY DUE TO A MALFUNTION IN THE INTERNAL WORKINGS OF GENERATOR. TECH REP COMING OUT TO FIX GENSET AND PROVIDE COPY OF REPORT.
Condition: Damaged By Earlier Event
Action required: 705 - Other - as specified
Resolved 7 May 2004
Documentation › Logs/Records › Logbook (official)
Issued 17 November 2003
Resolved
NEED TO PROVIDE ALL PUBS AND LOG BOOKS.
Condition: Unknown
Action required: 705 - Other - as specified
Resolved 7 May 2004