Inspection history · 17
27 April 2026
PSC B · COC-GAS Renew
Physical examination · Sector Delaware Bay · USCG East District (CGD-E) · Activity 8356319
29 March 2024
COC-GAS Renew · PSC B
Physical examination · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 7886303
28 April 2018
Deficiency Check
Physical examination · Marine Safety Unit Victoria · USCG Heartland District (CGD-H) · Activity 6402272
23 April 2018
Ballast Water Examination · ISPS II Exam · COC-GAS Renew
Physical examination · Marine Safety Unit Port Arthur · USCG Heartland District (CGD-H) · Activity 6395138
27 December 2017
Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6329596
27 August 2017
COE-Administrative
Administrative · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6252712
25 August 2017
Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6251549
26 May 2017
COC-GAS Annual · Ballast Water Examination · ISPS II Exam
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6152455
19 April 2017
COE-Dockside
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6125982
23 January 2017
Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6075083
11 December 2016
Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6056496
7 December 2016
COE-Administrative
Administrative · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6054228
6 November 2016
Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6036157
1 August 2016
Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 5959705
23 April 2016
Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 5860720
22 April 2016
Ballast Water Examination · ISPS II Exam · COC-GAS Renew
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 5855341
9 March 2016
Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 5830264
Deck/Cargo › Cargo Condition › Bulk Liquefied Gas
Issued 23 April 2018
Resolved
Gas detection equipment should be designed that it may readily be tested and suitable equipment for this purpose should be carried on board. PSCO were unable to witness satisfactory test of the ship's fixed gas detection system. During testing PSCO's witnessed 13 out of 17 sampling points that had readings of between 5% - 10% LEL for NH3. When introducing span gas of NH3 with a balance of nitrogen, LEL reading raised to 100% even though span gas is 5% NH3 by volume with a balance of nitrogen.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 23 April 2018
Resolved 27 April 2018
Resolution: Vsl provided class report attesting to repair of fixed gas detection system.
Electrical › Lighting (service) › Lighting Fixture
Issued 23 April 2018
Resolved
In zones on open decks over the cargo area and 3 M forward and aft of the cargo area where such is exposed to the weather, certified safe type equipment must be installed. Numerous lighting fixtures observed to have cracks through lenses and compromised gasket fixtures by way of FWD superstructure, aft motor room, aft of forecastle.
Condition: Improper/Lack of Maintenance
Action required: 15 - Rectify deficiencies by next port
Due 23 April 2018
Resolved 28 April 2018
Resolution: Vessel recieved new lenses for lights.
Operations/Management › Vessel Safety Management › Maintenance of Ship/Equipment
Issued 23 April 2018
Resolved
The company should establish procedures to ensure that the ship is maintained in conformity with the provisions of the relevant rules. PSCO found a steady fuel leak on the #3 SSDG due to a wasted o-ring, several explosion proof lightfixtures were found cracked and compromised.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 23 May 2018
Resolved 28 April 2018
Resolution: Company set up new procedures and risk management analysis to rectify holes in pms on vessels equipment.
Engineering › Fuel Oil Service System › Piping
Issued 23 April 2018
Resolved
Means shall be provided to control leaks of flammable liquids. Substantial fuel leaks observed in the following locations in the machinery spaces on #3 SSDG, in purifier room, and from fuel supply line by #6 cylinder on Main Engine.
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 23 April 2018
Resolved 23 April 2018
Resolution: Engineers replaced o-ring on #3SSDG and tightened fittings securing fuel leak in purifier room and on main engine.
Lifesaving › Inflatable Liferafts › Painter
Issued 23 April 2018
Resolved
The life raft painter system shall provide a connection between the ship and the life raft and shall be so arranged as to ensure the life raft when released, and in the case of an inflatable life raft, inflated is not dragged under by the sinking ship. The starboard life raft observed with sea painter disconnected from ship inhibiting its float free readiness.
Condition: Improper Installation
Action required: 10 - Deficiency Rectified
Due 23 April 2018
Resolved 23 April 2018
Resolution: 2nd officer reattached painter to weak link.
Deck/Cargo › Cargo Condition › Bulk Liquefied Gas
Issued 23 April 2018
Resolved
Gas detection equipment acceptable to the administration and suitable for the gases to be carried should be provided in accordance with column F in the table of chapter 19. Ships fixed system does not measure NH3 PPM. Ships enclosed space entry permit requires PPM readings taken less than 50% TLV of specified cargo. Ships crew provided they enter the space with their personal gas meter. Both the fixed gas detection and personal gas meter does not protect the crew from entering a space so as not to be exposed from the TLV of product that is being carried onboard.
Condition: Design Flaw
Action required: 17 - Rectify deficiencies prior to departure
Due 23 April 2018
Resolved 27 April 2018
Resolution: Vsl provided class report attesting to proper installation of system
Deck/Cargo › Cargo Condition › Bulk Liquefied Gas
Issued 23 April 2018
Resolved
Gas detection sample heads should be positioned with due regard to the density of the vapors. The gas detection sample head is in the airlock is located in the lower part of the space. The vessel carries ammonia whose vapors are lighter than air.
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Due 23 April 2018
Resolved 27 April 2018
Resolution: Vsl crew installed sample head in proper position.
Deck/Cargo › Cargo Condition › Bulk Liquefied Gas
Issued 23 April 2018
Resolved
Airlock doors should be self-closing and without any hold backs arrangements. The airlock door on the weather deck is not self-closing.
Condition: Improper/Lack of Maintenance
Action required: 15 - Rectify deficiencies by next port
Due 1 May 2018
Resolved 27 April 2018
Resolution: Vsl crew adjusted self-closing device and removed hold back hook.
Deck/Cargo › Cargo Condition › Bulk Liquefied Gas
Issued 23 April 2018
Resolved
A warning notice requiring the use of ventlation should be outside the compressor room and motor room. Port State Control Officers could not identify a ventilation warning sign outside of the compressor or motor room.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 23 May 2018
Resolved 27 April 2018
Resolution: Vsl crew installed warning sign outside spaces.
Fire Fighting › Combustible Materials › Primary Deck Coverings
Issued 26 May 2017
Resolved
1850:The condition of the ship and its equipment should be maintained to conform with the provisions of the Code to ensure the ship will remain fit to proceed to sea without danger to the ship or persons onboard. Vessel could not provide documentation attesting to the fire rating of the cat walk deck grating. Deck grating n question is the only access to installed powder fire extinguishing system,
Condition: Design Flaw
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 30 May 2017
Resolution: Received documentation attesting to approval and fire resistant ratings.