Inspection history · 31
24 July 2025
Internal Structural Exam · Periodic Inspection
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 8193348
17 October 2024
Annual Inspection
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 8020536
12 December 2023
MTSA Verification · Annual Inspection
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 7837758
8 September 2022
Deficiency Check · Administrative Inspection · COI Inspection
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 7554511
2 August 2022
Deficiency Check · Internal Structural Exam · Cargo Tank Internal · Drydock Exam
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 7523176
5 August 2021
MTSA Verification · Annual Inspection
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 7277640
20 July 2020
MTSA Verification · Internal Structural Exam · Periodic Inspection
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 7011305
12 September 2019
Annual Inspection · MTSA Verification
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 6810517
30 October 2018
Annual Inspection · MTSA Verification
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 6570882
26 September 2018
Type not recorded
No type recorded · Sector New York · USCG Northeast District (CGD-NE) · Activity 6549339
7 September 2018
Type not recorded
No type recorded · Sector New York · USCG Northeast District (CGD-NE) · Activity 6534617
30 July 2018
Administrative Inspection
Administrative · Sector New York · USCG Northeast District (CGD-NE) · Activity 6495768
14 August 2017
COI Inspection · Drydock Exam · MTSA Verification · Internal Structural Exam · Cargo Tank Internal
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 6240063
19 October 2016
Type not recorded
No type recorded · Sector New York · USCG Northeast District (CGD-NE) · Activity 6026011
25 August 2016
Periodic Inspection · MTSA Verification
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 5982290
23 July 2015
Annual Inspection · MTSA Verification · Internal Structural Exam
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 5193049
27 August 2014
Annual Inspection · MTSA Verification
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 4966670
16 October 2013
Type not recorded
No type recorded · Sector New York · USCG Northeast District (CGD-NE) · Activity 4742333
10 September 2013
Deficiency Check · MTSA Verification · COI Inspection
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 4711160
16 October 2012
Administrative Inspection
Administrative · Sector New York · USCG Northeast District (CGD-NE) · Activity 4465200
6 August 2012
Internal Structural Exam
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 4403504
1 August 2012
MTSA Verification · COI Inspection
Physical examination · Sector Delaware Bay · USCG East District (CGD-E) · Activity 4398165
14 March 2012
Load Line/Change of Employment
Administrative · Sector Delaware Bay · USCG East District (CGD-E) · Activity 4263325
10 August 2011
SIP Inspection/Audit
Administrative · Sector Delaware Bay · USCG East District (CGD-E) · Activity 4111593
26 August 2010
MTSA Verification · Annual Inspection · SIP Inspection/Audit
Physical examination · Sector Delaware Bay · USCG East District (CGD-E) · Activity 3833914
11 August 2009
MTSA Verification · SIP Inspection/Audit
Physical examination · Sector Delaware Bay · USCG East District (CGD-E) · Activity 3561553
9 September 2008
MTSA Verification · SIP Inspection/Audit
Physical examination · Sector Delaware Bay · USCG East District (CGD-E) · Activity 3320816
14 January 2008
Damage Survey
Physical examination · Sector Delaware Bay · USCG East District (CGD-E) · Activity 3129997
12 January 2008
Type not recorded
No type recorded · Sector Delaware Bay · USCG East District (CGD-E) · Activity 3130115
6 December 2007
SIP Initial Entry
Administrative · Sector Delaware Bay · USCG East District (CGD-E) · Activity 3176082
8 August 2007
Cargo Tank Internal · MTSA Verification · Internal Structural Exam · COI Inspection · Hull Examination · Initial Construction-Excluding Oversight · Initial Certification
Physical examination · Marine Safety Detachment Nashville · USCG Heartland District (CGD-H) · Activity 3016345
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 5 August 2021
Resolved
All electrical installations in hazardous locations must comply with the general requirements of section 33 of IEEE 45-1998. Two penetrations in the forward bulkhead of the auxiliary space, which contains electrical equipment not intrinsically safe, creates a direct opening to the hazardous zone.
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 5 August 2021
Resolved 5 August 2021
Resolution: Vessel effected permanent repairs by sealing the two penetrations.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 20 July 2020
Resolved
(a) The owner, master, or person-in-charge of a tank vessel must ensure that portable and semi-portable extinguishers are inspected and maintained in accordance with NFPA 10.
The pressure gauge of the Fire Extinguisher on deck read zero pressure. Recommend creating a monthly maintenance schedule to inspect the condition of on board extinguishers.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 3 August 2020
Resolved 28 July 2020
Resolution: Received evidence that the unsatisfactory extingusher has been replaced with RFI unit.
Construction/Loadline › Hull › Weld
Issued 14 August 2017
Resolved
Washed out welds identified during dry dock exam, documented on worklist. To be cleared by credit dry dock exam.
Action required: 705 - Other - as specified
Due 31 August 2017
Resolved 31 August 2017
Resolution: Welds have been repaired.
Deck/Cargo › Vapor Control Systems › Liquid Overfill Protection
Issued 10 September 2013
Resolved
Vessel must demonstrate proper testing of intrinsically safe overfill control system. 46 CFR 39.20-9(b)(3)
Action required: 705 - Other - as specified
Due 3 October 2013
Resolved 1 October 2013
Resolution: Using a multi-meter, tested continuity in the high level and overfill circuits. Using the #3 P/S cargo tank sensors, witnessed proper break in continuity indicating successful signal delivery to the overfill control system connection.
Electrical › Electrical Distribution System (service) › Ground Detection
Issued 10 September 2013
Resolved
Demonstrate proper operation of the ground detection system for the 120v panel in the machinery space. 46 CFR 111.05-21(c)
Action required: 705 - Other - as specified
Due 3 October 2013
Resolved 1 October 2013
Resolution: Vessel had a ground in the stern void, electrician corrected the problem and inspectors witnessed 120v panel with no ground fault indication with all breakers on.
Deck/Cargo › Vapor Control Systems › Liquid Overfill Protection
Issued 10 September 2013
Resolved
Demonstrate high level/overfill alarm system alarms in the event of a loss of power. 46 CFR 39.20-7 (b) (2)
Action required: 705 - Other - as specified
Due 3 October 2013
Resolved 1 October 2013
Resolution: Vessel demonstrated loss of power alarm (audible/visual). On/off switch inside APM-2 alarm panel is used to simulate loss of power and demonstrate operation of this safety feature.
Construction/Loadline › Hull › Side Shell
Issued 6 August 2012
Resolved
# 1 Portside void, bay 2 from Aft, 2nd long from top V/W as marked.
Due 6 November 2012
Resolved 25 October 2012
Construction/Loadline › Hull › Hull Plating
Issued 6 August 2012
Resolved
Have all void space hatch covers removed and ready for USCG inspection.
Due 6 November 2012
Resolved 25 October 2012
Construction/Loadline › Hull › Longitudinal Frame
Issued 6 August 2012
Resolved
# 7 port side void bay 2 from forward, 3rd long from bottom R/W
Due 6 November 2012
Resolved 25 October 2012
Construction/Loadline › Hull › Longitudinal Frame
Issued 6 August 2012
Resolved
#3 STBD void had 3 cracked welds. Located 1st bay from forward along the side long as marked and 2nd bay from side longs, V/W.
Due 6 November 2012
Resolved 25 October 2012
Construction/Loadline › Hull › Longitudinal Frame
Issued 6 August 2012
Resolved
2 STBD void, 3 frames from aft bulkhead, re attach weld on 3 longs from bottom, as marked.
Due 6 November 2012
Resolved 25 October 2012
Construction/Loadline › Hull › Longitudinal Frame
Issued 6 August 2012
Resolved
2 STBD void, 4 frames from aft bulkhead, re-attached welds on 1 and 2 longs from bottom and middle bottom longs.
Due 6 November 2012
Resolved 25 October 2012
Construction/Loadline › Hull › Longitudinal Frame
Issued 6 August 2012
Resolved
2 STBD void, 4 frames from aft bulkhead, re-attached welds on 1 and 2 longs from bottom and middle bottom longs.
Due 6 November 2012
Resolved 25 October 2012
Construction/Loadline › Hull › Longitudinal Frame
Issued 6 August 2012
Resolved
# 1 STBD void 4 cracked welds. #3 bay from fwd side longs # 2, 3, 6 , from bottom. V/W # 4 bay from Fwd. #6 side long from bottom V/W as marked.
Due 6 November 2012
Resolved 25 October 2012
Construction/Loadline › Hull › Longitudinal Frame
Issued 6 August 2012
Resolved
# 2 portside void bay 2 from Aft, 3rd long from bottom , V/W as marked.
Due 6 November 2012
Resolved 25 October 2012
Construction/Loadline › Hull › Hull Plating
Issued 6 August 2012
Resolved
#2 portside void Bay 3 and Bay 4 from Aft, 3rd long from bottom , V/W as marked.
Due 6 November 2012
Resolved 25 October 2012
Construction/Loadline › Hull › Longitudinal Frame
Issued 6 August 2012
Resolved
# 3 portside void Bay 4 from Aft, 6rd long from top, V/W as marked.
Due 25 October 2012
Resolved 25 October 2012
Construction/Loadline › Hull › Longitudinal Frame
Issued 6 August 2012
Resolved
# 3 portside void Bay 4, and Bay 6, from Aft, 6rd long from top, V/W as marked.
Due 6 November 2012
Resolved 25 October 2012
Construction/Loadline › Hull › Longitudinal Frame
Issued 6 August 2012
Resolved
#6 STBD void 2 side shell stiffeners from aft bulkhead, 3 longs from bottom V/W broken weld as marked
Due 25 October 2012
Resolved 25 October 2012
Construction/Loadline › Hull › Side Shell
Issued 6 August 2012
Resolved
# 4 STBD void, 3 frames from aft bulkhead, on fwd side, middle bottom long V/W.
Due 6 November 2012
Resolved 30 October 2012
Deck/Cargo › Cargo Transfer/Lightering (liquid) › Transfer Hose
Issued 1 August 2012
Resolved
Cargo hose not labeled with "Oil Service"
Due 2 September 2012
Resolved 6 August 2012
Resolution: Corrected on the spot by stenciling cargo hose.
Lifesaving › Lifebuoys › Markings (ship name/port)
Issued 1 August 2012
Resolved
During annual USCG audit, both life rings were found poorly stenciled, and the forward life ring's plug was deteriorated.
Due 6 August 2012
Resolved 6 August 2012
Deck/Cargo › Holds/Tanks › Flame Arrester
Issued 9 February 2012
Resolved
Flame screen missing hold down screw
Due 10 March 2012
Resolved 9 February 2012
Resolution: Corrected on site, added screen to flame screen.
Deck/Cargo › Vapor Control Systems › Piping/Hoses
Issued 9 February 2012
Resolved
Vapor hose missing red color stenciling.
Due 16 February 2012
Resolved 20 February 2012
Resolution: Colored vapor hose appropriately.
Engineering › Diesel Engine (auxiliary) › Gear/Clutch Starter (electric)
Issued 8 August 2007
Resolved
provide proof of cargo pump engine wiring harness meeting 46 cfr 111.50 NEC Class1/Div 1 per D8 (m) policy letter dated 02-2005 NLT 01 Aug 08. Historically archived due to inactivity.
Condition: Design Flaw
Action required: 705 - Other - as specified
Due 31 October 2008
Resolved 17 August 2017
Resolution: Reissued under activity 3624788.