Records from 2009 to 2025. Most recent: inspection, 25 March 2025.
07 - Fire Safety › N/A - No Subsystem › Fire pumps and its pipes
Issued 20 June 2023
Resolved
A fixed fire pump must be capable of: Delivering water simultaneously from the two highest hydrants, or from both branches of the fitting if the highest hydrant has a Siamese fitting, at a pitot-tube pressure of at least 344 kilopascals (kPa) (50 pounds per square inch (psi)), and a flow rate of at least 300 liters per minute (lpm) (80 gallons per minute (gpm). Inspector discovered that the fire pump was only outputting 40 psi pressure. 46 CFR 142.325(a)(1)
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 23 June 2023
Resolution: Received video footage of pump operating at 50 psi.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 20 June 2023
Resolved
Electrical systems and equipment must function properly and minimize system failures and fire and shock hazards. Submersible pumps had an exposed wire, posing a potential electrical hazard. 46 CFR 143.400(a)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 4 July 2023
Resolved 29 June 2023
Resolution: Received picture of submersible pump wire replaced and zip-tied so as to no longer pose a hazard.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 20 June 2023
Resolved
Individual circuit breakers on switchboards and distribution panels must be labeled with a description of the loads they serve. Inspector discovered unlabeled "spares" that were energized. 46 CFR 143.400(d)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 4 July 2023
Resolved 11 July 2023
Resolution: Received picture evidence of spares blanked off.
04 - Emergency Systems › N/A - No Subsystem › Emergency, lighting, batteries and switches
Issued 20 June 2023
Resolved
Electrical equipment and electrical cables must be suitably protected from wet and corrosive environments. Liquid of unknown origin was found in battery enclosures. 46 CFR 143.400(f)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 4 July 2023
Resolved 29 June 2023
Resolution: Received photos of the battery cases. Cleared of liquid.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 20 June 2023
Resolved
Electrical connections must be suitably installed to prevent them from coming loose through vibration or accidental contact. Wiring for the batteries for the main diesel engines were inappropriately rigged, possibility for wiring to come loose. 46 CFR 143.400(e)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 4 July 2023
Resolved 11 July 2023
Resolution: Received pictures of the wingnuts replacement.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 20 June 2023
Resolved
Paints, coatings, or other flammable or combustible products onboard a towing vessel must be stored in a designated storage room or cabinet when not in use. Flammable liquids onboard vessel must be stored in the above-mentioned cabinet.
46 CFR 142.225(a)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 4 July 2023
Resolved 11 July 2023
Resolution: Received pictures of the flammable products in a proper storage room.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 20 June 2023
Resolved
The connections of flexible cable plugs and socket outlets must be designed to prevent unintended separation. Outlet near starboard generator needs to be mounted. 46 CFR 143.400(i)
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 4 July 2023
Resolved 9 July 2023
Resolution: Received picture evidence of replacement.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 20 June 2023
Resolved
Propulsion machinery, including main engines, reduction gears, shafting, bearings, and electrical equipment and systems, must: Be maintained to ensure proper operation. Port Main Engine heat exchanger was discovered to be leaking. 46 CFR 143.205(c)(1)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 4 July 2023
Resolved 21 August 2023
Resolution: Vessel sent video of heat exchanger functioning properly. No leaks.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 20 June 2023
Resolved
Propulsion machinery, including main engines, reduction gears, shafting, bearings, and electrical equipment and systems, must: Be maintained to ensure proper operation. Starboard generator raw water hose is beginning to fail. 46 CFR 143.205(c)(1)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 4 July 2023
Resolved 9 July 2023
Resolution: Received photo evidence of replacement.
04 - Emergency Systems › N/A - No Subsystem › Fire drills
Issued 24 June 2022
Resolved
The master of a towing vessel must ensure that each crew member participates in fire-fighting drills and receives instruction at least once each month. Marine Inspector observed vessel did not have monthly training and fire drill records. Complete and record fire drill/training in TVR.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 30 June 2022
Resolution: crew received training and ran drills while CG was on board
05 - Radio Communications › N/A - No Subsystem › Reserve source of energy
Issued 24 June 2022
Resolved
Machinery and electrical systems must be designed and maintained to provide for safe operation of the towing vessel and safety of persons on board under normal and emergency conditions. Marine Inspector observed general alarm, navigation equipment and radios did not operate during Deadship test. Connect Radios and general alarm to a functioning battery back up.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 30 June 2022
Resolution: fixed battery back up
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 20 April 2021
Resolved
All fire-detection systems, and fixed fire-extinguishing systems, including ventilation, machinery shutdowns, on board the vessel, must be inspected or tested at least once every 12 months, as prescribed in paragraphs (a)(1) through (8) of this section.
Vessel fire-detection panel was last serviced May 2019. Vessel is required to have a servicing facility service fire detection panel to the satisfaction of the Marine Inspector prior to movement.
Action required: 30 - Ship detained
Resolved 22 April 2021
Resolution: Reviewed the Eagle Control Certification of the fire detection panel.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 20 April 2021
Resolved
Electrical systems and equipment must function properly and minimize system failures and fire and shock hazards.
Vessel had multiple dead end wires under the wheel house space and had many splices of wires without proper connectors. Vessel also had 3 large wires spliced into one plug into an surge protector. Vessel is required to remove, cap and fix wiring under wheelhouse to the satisfaction of the Marine Inspector prior to movement.
Action required: 30 - Ship detained
Resolved 22 April 2021
Resolution: Vessel crew removed and cleaned up wiring under the wheelhouse.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 20 April 2021
Resolved
Machinery and electrical systems must be designed and maintained to provide for safe operation of the towing vessel and safety of persons onboard under normal and emergency conditions. Vessel SSDGs windings were coated in oil. Clean windings to the satisfaction of the Marine Inspector prior to movement.
Action required: 30 - Ship detained
Resolved 22 April 2021
Resolution: Vessel crew cleaned the windings covers of both SSDG.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Machinery space openings
Issued 20 April 2021
Resolved
Machinery and electrical systems must be designed and maintained to provide for safe operation of the towing vessel and safety of persons onboard under normal and emergency conditions. Vessels shaft seals had an excessive leaks estimated ¼” steady stream. Vessel is required to provide proof that the vessels shaft seals are corrected to the satisfaction of the Marine Inspector prior to movement.
Action required: 30 - Ship detained
Resolved 22 April 2021
Resolution: Vessel crew tightened shaft seals and conducted an operational test proving that the shaft seals were properly adjusted.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 20 April 2021
Resolved
The crew of each towing vessel must demonstrate the ability to operate the primary and auxiliary machinery and electrical systems for which they are responsible, and to do so under normal and emergency conditions. This includes, but is not limited to, responses to alarms and restoration of propulsion and steering in the event of failure. Vessels Port MDE and SSDG was unable to start during the inspection.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 22 April 2021
Resolution: Vessel crew conducted mainteance on the starter on port MDE. Vessel owner hired mechanic to determine the cause of the port SSDG to determine the cause failure. Replaced wiring altenator to battery. Witnessed satisfactory op of MDE & SSDG starting.
01 - Certificates & Documentation › 013 - Documents › Log-books/compulsory entries
Issued 20 April 2021
Resolved
The TVR must include a chronological record of events as required by this subchapters. Vessel TVR did not list any items chronological and was missing 06 months of logs from October to April. Vessel managers are required to give training to Master on the responsibility of items that must be logged under 46CFR140.915 to the satisfaction of the Marine Inspector prior to movement.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 22 April 2021
Resolution: Vessel Master was given training on TVR and prior to getting U/W completed form. After returning checked TVR and was completed for U/W.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 20 April 2021
Resolved
Fire detection systems control panel includes labels for all switches and indicator lights, identifying their functions. Vessel fire control panel did not have zones labeled for the zones on board. Provide proper labeling for the fire detection panel to the satisfaction of the Marine Inspector prior to movement.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 22 April 2021
Resolution: Fire control panel was labeled with zones during servicing.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 20 April 2021
Resolved
Machinery and electrical systems must be designed and maintained to provide for safe operation of the towing vessel and safety of persons onboard under normal and emergency conditions. Vessel Stbd MDE had an excessive exhaust leak at the elbow of the exhaust system. Vessel is required to ensure that the exhaust leak has been fixed to the satisfaction of the Marine Inspector within 14 days.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 4 May 2021
Resolved 22 April 2021
Resolution: Vessel replaced exhaust coupler with new one to fix exhaust leak.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 20 April 2021
Resolved
A towing vessel must carry lifebuoys as follows: be capable of being rapidly cast loose; not be permanently secured to the vessel in any way; marked in block capital letters with name of vessel, lifebuoys must have the following attachments. Floating electric water light approved under 161.010 or 161.110. Vessels Stbd side light did not have a lanyard with a corrosion resistant clip and was tied to lifebuoy. Wrong battery was inside the light. Vessels Port side life buoy was tied to the vessel and light was not secured to the ring by any means. The Port side life buoy setup also made it impossible to cast free lifebuoy based on the set up. Vessels name was faded on both ring buoys. Repair all items listed above prior to movement to the satisfaction of the Marine Inspector.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 3 June 2021
Resolution: Vessel crew replaced battery and installed floating lights properly.
15 - Safety Management Systems (ISM) › N/A - No Subsystem › Maintenance of the ship and equipment
Issued 20 April 2021
Resolved
Fuel systems for towing vessel main engines and generators must have a documented maintenance plan to ensure proper operation of the system.Vessel did not have a documented maintenance plan for fuel filters. Vessel operators must develop a maintenance plan to cover fuel filters with in 14 days to satisfaction of MI
Action required: 16 - Rectify deficiencies w/in 14 days
Due 4 May 2021
Resolved 22 April 2021
Resolution: Vessel owner updated mainteance procedures to reflect 300 hour interval in writing.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 20 April 2021
Resolved
Electrical systems and equipment must function properly and minimize system failures and fire and shock hazards. Marine Inspector observed STBD generator battery enclosure not secured and being supported electric conductors and Port Side with no enclosure.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 4 May 2021
Resolved 22 April 2021
Resolution: Vessel crew installed battery boxes properly and fastened them to ensure movement was limited.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 20 April 2021
Resolved
Machinery and electrical systems must be designed and maintained to provide for safe operation of the towing vessel. Marine Inspector observed disconnected air filter on the STBD generator.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 4 May 2021
Resolved 22 April 2021
Resolution: Vessel fashioned an intake elbow to attach the air filter to the SSDG.
09 - Working and Living Conditions › 092 - Working Conditions › Protection machines/parts
Issued 20 April 2021
Resolved
Piping and machinery components that exceed 220 °C (428 °F), including fittings, flanges, valves, exhaust manifolds, and turbochargers, must be insulated. Marine Inspector observed exposed turbo charger and exhaust manifold on the PORT main engine.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 4 May 2021
Resolved 22 April 2021
Resolution: Vessel Crew installed heat shiedling on the Port MDE.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 20 April 2021
Resolved
Electrical components that pose an electrical hazard must be in an enclosure. Marine Inspector observed one inch hole, as the result of corrosion, in the electrical enclosure for the steering gear system.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 4 May 2021
Resolved 22 April 2021
Resolution: Vessel crew replaced the wasted enclousre with a new plastic electric enclosure.
09 - Working and Living Conditions › 092 - Working Conditions › Personal equipment
Issued 20 April 2021
Resolved
All individuals must wear PPE appropriate to the activity being performed. Master and crewmember did not wear steel-toed boots while working in areas requiring their use. Vessel owner required to provide training to master and crew member on general health and safety requirements.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 4 May 2021
Resolved 4 June 2021
Resolution: Training was conducted and logged for varification.
15 - Safety Management Systems (ISM) › N/A - No Subsystem › Safety and environment policy
Issued 20 April 2021
Resolved
All crewmembers must be provided with health and safety information and training that includes the content and procedures of the operator’s health and safety plan. Annual refresher training required but can be done in modules over time. Vessels crew wasnt knowledgeable of Health and Safety Manual.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 4 May 2021
Resolved 4 June 2021
Resolution: Health and Safety plan training was conducted and verified.
02 - Structural Conditions › N/A - No Subsystem › Bulkheads - cracking
Issued 20 April 2021
Resolved
The vessel has been both in satisfactory service insofar as structural adequacy is concerned and does not cause the structure of the vessel to be questioned by the [name withheld] top deck walk way and vessels stack had a few inch crack vertical and couple inch crack horizontal. Provide a repair plan to the OCMI within 14 days prior to making repairs.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 4 May 2021
Resolved 3 June 2021
Resolution: Witnessed satisfactory weld repairs.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 20 April 2021
Resolved
The frame or support of any semi-portable fire extinguisher fitted with wheels must be welded or otherwise permanently attached to a steel bulkhead or deck to prevent it from rolling under heavy sea conditions.
Vessels semi portable was not secured to the vessel.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 3 June 2021
Resolution: Witnessed semi-portable extinguisher properly secured.
04 - Emergency Systems › N/A - No Subsystem › Emergency, lighting, batteries and switches
Issued 20 April 2021
Resolved
Emergency lighting must be provided for all internal crew working and living areas. Emergency lighting sources must provide for sufficient illumination under emergency conditions to facilitate egress from each space.
Vessel did not have emergency lighting in the berthing area or forward hole of the engine room. Provide emergency lights in the above spaces.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 22 April 2021
Resolution: Vessel hired electrican to add emergency lighting to accomdation and front hold.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 20 April 2021
Resolved
Individual circuit breakers on switchboards and distribution panels must be labeled with a description of the loads they serve.
Vessels Circuit breakers in the galley were not properly marked. Clean and mark with proper loads for each breaker. Ensure breaker blank is fully blocking the panel.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 3 June 2021
Resolution: Witnessed satisfactory labeling and load service for the galley circuit breaker.
11 - Life Saving Appliances › N/A - No Subsystem › Operational readiness of lifesaving appliances
Issued 20 April 2021
Resolved
All lifesaving equipment must be tested and maintained in accordance with the minimum requirements of §199.190 of this chapter, as applicable,
Vessels Buoyant apparatus was deteriorated. Vessel is restricted to a rivers route no more than 1 mile from shore until proper buoyant apparatus or above is installed on the vessel.
Action required: 705 - Other - as specified
Resolved 22 April 2021
Resolution: Vessel replaced Buoyant appartus with one in servicable condition and marked it.
11 - Life Saving Appliances › N/A - No Subsystem › Other (life saving)
Issued 20 April 2021
Resolved
Appropriate Personal Protective Equipment (PPE) must be made available and on hand for all personnel engaged in an activity that requires the use of PPE. Incorrect Work vest were being used on board the vessel for use by crew.
Action required: 10 - Deficiency Rectified
Resolved 3 June 2021
Resolution: Witnessed crew utilize proper work vest.
04 - Emergency Systems › N/A - No Subsystem › Emergency, lighting, batteries and switches
Issued 20 April 2021
Resolved
Emergency lighting must be provided for all internal crew working and living areas. Emergency lighting sources must provide for sufficient illumination under emergency conditions to facilitate egress from each space. Marine Inspector observed engine room emergency lighting was inoperable.
Condition: Improper Installation
Action required: 60 - Rectify deficiencies prior to movement
Resolved 24 June 2021
Resolution: Engine room emergency lighting was repaired and a tech report was submitted, all sat.
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 20 April 2021
Resolved
Each escape hatch and emergency exit used as means of escape must be marked on both sides in clearly legible letters at least 50 millimeters (2 inches) high: “EMERGENCY EXIT, KEEP CLEAR”. Marine Inspector observed forward engine room emergency escape hatch was labeled "Confined Space", properly label prior to operation.
Condition: Improper/Lack of Maintenance
Action required: 60 - Rectify deficiencies prior to movement
Resolved 24 June 2021
Resolution: Hatch was properly marked, all sat.
07 - Fire Safety › N/A - No Subsystem › Maintenance of Fire protection systems
Issued 20 April 2021
Resolved
The owner or managing operator must provide satisfactory evidence of the required servicing to the marine inspector or TPO, as applicable. Vessel's crew and owner were unable to provide fire-fighting servicing documentation.
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Resolved 4 June 2021
Resolution: Tech report was provided, all sat.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 26 April 2019
Resolved
The owner / managing operator must ensure the fire detection system is tested IAW the manufacturer's design manual. Found no on-board procedures for testing fire detectors and crew was not familiar with test methods. Provide on-board fire detector test procedures and ensure crew is properly trained on test methods to the satisfaction of the attending USCG MI.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 26 May 2019
Resolved 14 May 2019
Resolution: Crew tested the fire detection system, provided on-board fire detector test procedures and ensured crew was properly trained on test methods to the satisfaction of the attending USCG MI.