Records from 2009 to 2025. Most recent: inspection, 7 July 2025.
Documentation record
Registered dimensions (L × B × D)491.8 ft × 72.0 ft × 41.0 ft
Registered tonnagegross 9,726 / net 9,726
ITC dimensions (L × B × D)491.8 ft × 72.0 ft × 41.0 ft
ITC tonnagegross 10,884 / net 6,139
BuilderBAY SHIPBUILDING CORP · STURGEON BAY, WI, UNITED STATES · built 2009
Hull materialSteel
PropulsionNot recorded
Hull shapeNot recorded
Hull configurationNot recorded
Hailing portWILMINGTON, DE
Trade endorsementsCoastwise, unrestricted, Registry
DocumentationValid · issued 17 October 2025 · expires 30 November 2026
Service, as the file records itTank Barge
Hull formbarge (Maury's inference from propulsion, hull shape, material and length, rule hf-1; not a recorded fact)
Tonnage as PSIX records it6139 - Convention (Subpart B), Net Ton
9726 - Regulatory (Subpart C or D), Net Ton
10884 - Convention (Subpart B), Gross Ton
9726 - Regulatory (Subpart C or D), Gross Ton
Every line above is a field of the National Vessel Documentation Center's file as served by NOAA Fisheries, dated 10 September 2026, matched to this hull on its Official Number. Registered and ITC measurements are two systems and are never combined. One snapshot is held so far; documentation history begins with the next.
Inspection history · 32
7 July 2025
Administrative Inspection · Annual Inspection · MTSA Verification
Physical examination · Marine Safety Unit Baton Rouge · USCG Heartland District (CGD-H) · Activity 8178438
30 July 2024
Administrative Inspection
Administrative · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 7970771
20 May 2024
Drydock Exam · Internal Structural Exam
Physical examination · Sector Puget Sound · USCG Northwest District (CGD-NW) · Activity 7915679
29 April 2024
COI Inspection · Administrative Inspection
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 7899480
25 June 2023
Administrative Inspection · Deficiency Check
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 7723499
27 July 2022
Administrative Inspection · Internal Structural Exam · Periodic Inspection
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 7517641
2 April 2022
Administrative Inspection
Administrative · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7423428
28 February 2022
Administrative Inspection
Administrative · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7403077
18 October 2021
Administrative Inspection
Administrative · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7333679
18 October 2021
Deficiency Check · Annual Inspection
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7335262
22 January 2021
Administrative Inspection
Administrative · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 7129466
11 September 2020
Annual Inspection · Deficiency Check
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7057451
17 February 2020
Administrative Inspection
Administrative · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 6914537
13 June 2019
Drydock Exam · Cargo Tank Internal · COI Inspection · Internal Structural Exam
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6745660
23 April 2019
Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6673363
23 August 2018
Deficiency Check · Annual Inspection
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 6521426
21 August 2017
Deficiency Check
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6242351
11 August 2017
Periodic Inspection
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 6236612
16 May 2017
Internal Structural Exam
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 6148956
29 August 2016
Annual Inspection
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 5986884
24 June 2016
Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 5980684
8 September 2015
Administrative Inspection
Administrative · Sector Mobile · USCG Heartland District (CGD-H) · Activity 5238684
28 August 2015
Annual Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 5722504
20 July 2014
Type not recorded
No type recorded · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 4959410
3 June 2014
Plan Review (Other than "T") · COI Inspection · Administrative Inspection · MARPOL Annex VI Survey · Drydock Exam · Internal Structural Exam · Welding Related Inspections Qualification Testing · MARPOL Annex II Examination · MTSA/ISPS Verification · MARPOL Annex I Examination · Hull Examination · MARPOL Annex IV Survey
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 4878050
10 July 2013
Annual Inspection
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 4649688
7 October 2012
Deficiency Check
Physical examination · Sector Delaware Bay · USCG East District (CGD-E) · Activity 4459286
9 August 2012
Deficiency Check
Physical examination · Marine Safety Unit Savannah · USCG Southeast District (CGD-SE) · Activity 4411573
23 July 2012
Internal Structural Exam · MTSA Verification · Deficiency Check · Periodic Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 4383218
19 August 2010
MTSA Verification · Annual Inspection
Physical examination · Sector Puget Sound · USCG Northwest District (CGD-NW) · Activity 3832169
2 April 2010
Type not recorded
No type recorded · Sector Portland · USCG Northwest District (CGD-NW) · Activity 3715066
21 January 2009
Construction Oversight · Hull Examination · Initial Certification · MARPOL Annex VI Survey · Cargo Tank Internal · MTSA/ISPS Verification · Internal Structural Exam
Physical examination · Marine Safety Unit Sturgeon Bay · USCG Great Lakes District (CGD-GL) · Activity 3541660
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Cargo transfer - Tankers
Issued 18 October 2021
Resolved
The pressure used for the test required by 33 CFR156.170 must not be marked on the hose and must be recorded elsewhere at the facility. Cargo transfer hoses were found to be improperly marked with the hose test pressure.
Condition: Improper Installation
Action required: 10 - Deficiency Rectified
Resolved 18 October 2021
Resolution: Vessel operator removed the test pressure from all onboard cargo transfer hoses.
09 - Working and Living Conditions › 092 - Working Conditions › Entry dangerous spaces
Issued 11 September 2020
Resolved
It was found that the emergency escape trunk/hatch within the Nitrogen Gas Generator (Inert Gas) space could not be opened. The opening/closing mechanism was seized and could not be actuated.
46 CFR 31.30-1
Action required: 10 - Deficiency Rectified
Due 11 September 2020
Resolved 11 September 2020
Resolution: Engineering crew assigned to the barge conducted maitenance; opening/closing mechanism was lubiricated and actuated.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 11 September 2020
Resolved
Two fire extinguishers within the Thermal Fluid Heater space were found to be held in place (attached to bulkhead) by improper mounting/retaining brackets.
46 CFR 34.50-20
Action required: 16 - Rectify deficiencies w/in 14 days
Due 25 September 2020
Resolved 15 September 2020
Resolution: Proper brackets were installed on bulkhead and portable fire extinguishers securely held in place.
07 - Fire Safety › N/A - No Subsystem › Division - decks, bulkheads and penetrations
Issued 11 September 2020
Resolved
The Class A fire boundary (bulkhead) separating the ship service generator space and the thermal fluid heater space was found to have open penetrations that may allow the passage of heat/smoke/flame.
46 CFR 32.57-10
Action required: 16 - Rectify deficiencies w/in 14 days
Due 25 September 2020
Resolved 15 September 2020
Resolution: Penetrations in Class A Boundary were filled by installing steel bolts with retaining nuts into the holes.
02 - Structural Conditions › N/A - No Subsystem › Loading/Ballast condition
Issued 30 July 2019
Resolved
Prior to leaving Veracruz, MX provide class report from ABS illustrating that all alarms associated with the commissioning of the Ecochlor system have been performed satisfactory.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 31 July 2019
Resolution: Received report form ABS stated alarms have been performed satisfactory.
02 - Structural Conditions › N/A - No Subsystem › Loading/Ballast condition
Issued 30 July 2019
Resolved
Prior to departing Veracruz, MX Ecochlor's commissioning document must be completed, signed, and verified by all parties involved.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 31 July 2019
Resolution: Recieved signed commissioning document from vessel.
02 - Structural Conditions › N/A - No Subsystem › Loading/Ballast condition
Issued 30 July 2019
Resolved
Prior to conducting ballast operations in the US, the ballast water treatment system must be verified fully operational, to include samples taken of ballast water.
Action required: 15 - Rectify deficiencies by next port
Resolved 2 August 2019
Resolution: Attended vessel and verified samples taken from ballast tanks are tested and water is able to be discharged.
01 - Certificates & Documentation › 013 - Documents › Log-books/compulsory entries
Issued 30 July 2019
Resolved
Prior to issuance of new SOVC ballast water management certificate, an updated and approved ballast water management plan must be onboard.
Action required: 705 - Other - as specified
Resolved 31 July 2019
Resolution: Recieved ABS approved updated ballast water management plan.
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Cargo transfer - Tankers
Issued 23 August 2018
Resolved
Each vessel vapor connection flange must have a permanent stud projecting outward that has a .5inch diameter and is at 1 inch long. The VCS flange stud on the forward Starboard manifold was broken off. Provide proof of repair to the flange stud prior to conducting cargo operations requiring VCS use.
Action required: 705 - Other - as specified
Resolved 27 August 2018
Resolution: removed the reducer and installed a different reducer in its'
Vessel crew removed the broken reducer and installed a different reducer in its place. Repairs made to original Flange stud on the reducer and kept as spare parts.
Electrical › Electrical Distribution System (service) › Wiring
Issued 11 August 2017
Resolved
Noted several wire nuts installed in various locations, replace the wire nuts with crimp on type connectors; noted three in the Skarpenord cabinet in the control room and three in the housing associated with the flame sensor for the thermal fluid heater.
Action required: 705 - Other - as specified
Due 10 September 2017
Resolved 21 August 2017
Resolution: Verified wire crimps have been installed in all locations where wire nuts wee listed.
Engineering › Freshwater System (jacketwater cooling) › Piping
Issued 11 August 2017
Resolved
Lagging has been removed from the J/W piping on the inboard generator, replace lagging where missing.
Action required: 705 - Other - as specified
Due 10 September 2017
Resolved 21 August 2017
Resolution: Verified new lagging has been installed on the J/W piping of the inboard generator.
Fire Fighting › Portable Dry Chemical Fire Extinguisher › Service
Issued 11 August 2017
Resolved
Service records indicate that the portable fire extinguishers in the machinery space have not been serviced since June; conduct monthly maintenance and document accordingly.
Action required: 705 - Other - as specified
Due 10 September 2017
Resolved 21 August 2017
Resolution: Verified monthly maintainence of fire extinguishers has been conducted and logged correctly.
Documentation › Certificates/Documents › Certificate of Fitness (BCH Code)
Issued 28 August 2015
Resolved
Provide original certificate of fitness onboard.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 28 September 2015
Resolved 18 September 2015
Resolution: Sector Mobile re-issued Certificate of fitness
Pollution Prevention/Response › Prevention Equipment › Means of Removal from within Coaming
Issued 23 July 2012
Resolved
Replace Spill pump hoses to Slop tank. Hoses are rotted and cracked.
Action required: 705 - Other - as specified
Due 23 August 2012
Resolved 9 August 2012
Resolution: Noted three new hoses installed.
Engineering › Diesel Engine (auxiliary) › Block
Issued 23 July 2012
Resolved
Replace hotel services generator radiator, radiator leaking coolant.
Action required: 705 - Other - as specified
Due 1 October 2012
Resolved 7 October 2012
Resolution: Ran generator, verified not leaks from radiator and all connections.
Electrical › Electric Generation Source (service) › Switch
Issued 23 July 2012
Resolved
Test reverse power relays, crew could not demonstrate proper operation of the reverse power relays.
Action required: 705 - Other - as specified
Due 23 August 2012
Resolved 9 August 2012
Resolution: Observed satisfactory operation of the both reverse power relays.
Deck/Cargo › Inert Gas System › Inert Gas Generator (IGG)
Issued 23 July 2012
Resolved
Make repairs to IG s/w suction line in #5P ballast tank by next drydock. Line has been temporarily repaired.
Action required: 705 - Other - as specified
Due 31 July 2014
Resolved 24 October 2012
Resolution: Verified approx. 80ft of piping replaced satisfactorily.
Construction/Loadline › Markings › Load Line Mark
Issued 23 July 2012
Resolved
Repaint all load line and draft marks.
Action required: 705 - Other - as specified
Due 1 October 2012
Resolved 7 October 2012
Resolution: Verified draft marks and load line were painted.
Documentation › Logs/Records › Operational Procedures for Engines or Equipment
Issued 23 July 2012
Resolved
Provide TFH automatic control and safety test procedures for all required items IAW 61.30-20
Action required: 705 - Other - as specified
Due 1 November 2012
Resolved 9 August 2012
Resolution: Observed proper test procedures performed on the Thermal Fluid Heater as per requirement. (Def cleared by [name withheld] at MSU Savannah)