Registered dimensions (L × B × D)243.8 ft × 60.0 ft × 19.5 ft
Registered tonnagegross 2,287 / net 686
ITC dimensions (L × B × D)243.8 ft × 60.0 ft × 19.5 ft
ITC tonnagegross 2,287 / net 686
BuilderEASTERN SHIPBUILDING GROUP INC · PANAMA CITY, FL, UNITED STATES · built 2009
Hull materialSteel
PropulsionDiesel Reduction
Hull shapeUNSPECIFIED
Hull configurationUNSPECIFIED
Hailing portNEW ORLEANS, LA
Endorsements, as the file codes themcw_un, reg
DocumentationValid · issued 20 October 2025 · expires 30 November 2026
Service, as the file records itIndustrial Vessel
Hull formpowered (Maury's inference from propulsion, hull shape, material and length, rule hf-1; not a recorded fact)
Tonnage as PSIX records it2287 - Convention (Subpart B), Gross Ton 3639 - Dead Weight, Gross Ton 686 - Convention (Subpart B), Net Ton
Every line above is a field of the National Vessel Documentation Center's file as served by NOAA Fisheries, dated 10 August 2026, matched to this hull on its Official Number. Registered and ITC measurements are two systems and are never combined. One snapshot is held so far; documentation history begins with the next.
Professional
The full record for this vessel
Behind this panel: 22 inspections, each with its date, unit and type; 14 deficiencies with the resolution recorded against each, 1 without one; operational controls, none recorded without a removal date; 2 other vessels inspected with it; no other recorded names; the documentation record: dimensions, tonnage, builder, hailing port and endorsements. Every line is a record the Coast
Guard wrote; the counts above are the same counts as in the summary, and they are free.
Professional is $39 a month or $299 a year,
or $19.99 a month locked for life at the founding rate, for the first 200 subscribers. It unlocks
every detail section on every vessel page, fleet watch tied to your account, and ownership records
on request. Already a subscriber? Sign in.
Maury does not score, rate or grade vessels, at any price.
Vessel history report
Every record for this hull, in one document — $299
Every recorded inspection, 1972 to
2026, in one chronology · every deficiency, with system, dates
and resolution · operational controls imposed and removed · every name this
hull has been recorded under · the vessels it was inspected alongside, and when
· how its record compares with hulls of similar age and size, as a fact about the
population and never a judgement about this vessel.
This report is in development and is not for sale yet. There is
no date, and nothing is charged. Leave an email and we will tell you when it exists, once.
Used only to tell you when the report exists.
Not shared, not sold, and not added to a mailing list.
The Coast Guard recorded this vessel and the following in the same
inspection activity — normally a tug and the barges in its tow. A recreational or
unclassed hull in the same activity is held and not published, so it does not appear
here: these lists are a floor, not a complete manifest.
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Other (cargo)
Issued 30 October 2025No resolution recorded
No OSV may carry flammable or combustible liquid cargoes in bulk without approval. The COI currently authorizes domestic carriage methyl alcohol. The vessel doesn’t have controlled vents (Pressure /Vacuum) on either the port or starboard methanol tanks, or onboard. Prior to the carriage of methanol.
46 CFR 125.110
Action required: 705 - Other - as specified
Due 30 October 2025 — due date passed with no resolution recorded
MARPOL VI 8.1
The bunker delivery note shall be accomplished by a rep sample of the fuel oil. Delivered taking into account guidelines developed by the org. The sample is to be sealed and signed by the suppliers rep, and the master or officer in charge of the operation on completion of bunkering ops. Returned under the ships control until the fuel oil is consumed but in any case for a period of not less than 12mo from the time of delivery. Ship to ship transfers no fuel samples have been retained.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 29 November 2024
Resolved 10 December 2024
Resolution: Received report from ABS clearing the deficiency and taking corrective action via training.
SOLAS 11.1 Reg 46
Every ship shall be provided with documentary evidence, to the satisfaction of the admin, of its fitness to operate with periodically unattended machinery spaces.
Class cert. has ACC not ACCU for unattended machinery space.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 29 November 2024
Resolved 11 December 2024
Resolution: Vsl agrees with CG to go to Minimally manned machinery space aligning with ACC
Persons assigned duties as officer in charge of, or rating forming part of, a(n) navigational/engineering watch must receive 77 hours of rest in a 7-day period; STCW work rest logs did not accurately reflect the hours worked when compared to rough logs. To be checked at next topside inspection.
Action required: 705 - Other - as specified
Resolved 6 December 2024
Resolution: Received work rest logs and filled out for the month of november 2024
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Gauges, thermometers, etc
Issued 24 January 2022Resolved
Pressure-indicating gauges shall be such that the upper range of the gauge is not less than 1.2 times to 2 times the pressure at which the relieving device is set to function; the #1 Drybulk pump compressor air receiver, #2 Drybulk pump compressor air receiver, and 02 air receivers for the port Z-drive all had gauges not within 1.2 to 2 times the setting of the relieving device.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 21 February 2022
Resolution: 835V was accepted by attending ABS Surveyor, see attached finding report.
07 - Fire Safety › N/A - No Subsystem › Fire pumps and its pipes
Issued 24 January 2022Resolved
All required fire pump remote control locations must include the ability to accurately monitor fire pump pressure; fire pump pressure gauge on the bridge read 40 psi despite the pressure at the pump reading 90 psi.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 21 February 2022
Resolution: 835V was accepted by ABS with an issued finding number, see attached report.
Where penetrations of watertight bulkheads are necessary for access, arrantements are to be made to maintain the watertight integrity. All the watertight doors and hatches were loose and required to be tighten.
74 SOLAS (14) II-1/13-1.1
Action required: 10 - Deficiency Rectified
Due 14 January 2021
Resolved 14 January 2021
Resolution: Adjusted all watertight door and hatches to be secured.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 14 January 2021Resolved
The crew shall have necessary knowledge and skills to handle fire emergency cases. Fire drill performed by the crew was inadequate. 74 SOLAS (14) II-2/15.1
Action required: 10 - Deficiency Rectified
Due 14 January 2021
Resolved 14 January 2021
Resolution: Required crew to perform three fire drills and educated the crew.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 30 October 2019Resolved
For machinery spaces, the fixed piping system shall be such that 85% of the gas can be discharged into the space within 2 min. The flexible lines on the vessels CO2 system were only hand tightened, which would have casued leakage into the Co2 storage space.
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Due 18 November 2019
Resolved 18 November 2019
Resolution: ABS verified and cleared.
07 - Fire Safety › N/A - No Subsystem › Personal equipment for fire safety
Issued 30 October 2019Resolved
Firefighter's outfit shall consist of protective clothing of material to protect the skin from the heat radiating from the fire and from burns and scalding by steam. The outer surface shall be water-resistant. Vessel did not have sufficient fire suit that fit crew member/ fire team member.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 18 November 2019
Resolved 18 November 2019
Resolution: ABS verified and cleared.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 30 October 2019Resolved
All life-saving appliances shall: where exposed to sunlight, be resistant to deterioration. Vessel had at least three lifebuoys that displayed deterioration of the attached line.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 18 November 2019
Resolved 18 November 2019
Resolution: ABS verified and cleared.
11 - Life Saving Appliances › N/A - No Subsystem › Immersion suits
Issued 30 October 2019Resolved
An immersion suit which has buoyancy and is designed to be worn without a lifejacket shall be fitted with a light complying with the requirements of paragraph 2.2.3 and the whistle prescribed by paragraph 2.2.1.14. The immersion suits aboard the vessel were missing lights.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 18 November 2019
Resolved 18 November 2019
Resolution: ABS verified and cleared.
11 - Life Saving Appliances › N/A - No Subsystem › Embarkation arrangements rescue boats
Issued 30 October 2019Resolved
An embarkation ladder complying with the requirements of paragraph 6.1.6 of the Code extending, in a single length, from the deck to the waterline in the lightest seagoing condition under all conditions of trim of up to 10 degrees and a list of up to 20 degrees either way shall be provided at each embarkation station or at every two adjacent embarkation stations for survival craft launched down the side of the ship. Vessels embarkation ladder had multiple shackles on ladder seized up from rust. Unable to attach to vessel.
Action required: 17 - Rectify deficiencies prior to departure
Due 18 November 2019
Resolved 18 November 2019
Resolution: ABS verified and cleared.
07 - Fire Safety › N/A - No Subsystem › Ventilation
Issued 30 October 2019Resolved
The ignitability of combustible materials shall be restricted. The vessels fuel oil day tank (Port/Stbd) did not have sufficient flame screens on the vents.
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Due 18 November 2019
Resolved 18 November 2019
Resolution: ABS verified and cleared.