Every line above is a count of records the US Coast Guard wrote, or a date it recorded.
A blank resolution means none was recorded in this data; it does not establish that a
deficiency is outstanding. Years with a record are calendar years in which a record
exists, not years in service. What Maury does
not do.
1754 - Simplified, Gross Ton
1754 - Simplified, Net Ton
Maury page id
psix-1041109
Vessel history report
Every record for this hull, in one document — $299
Every recorded inspection, 1972 to
2026, in one chronology · every deficiency, with system, dates
and resolution · operational controls imposed and removed · every name this
hull has been recorded under · the vessels it was inspected alongside, and when
· how its record compares with hulls of similar age and size, as a fact about the
population and never a judgement about this vessel.
This report is in development and is not for sale yet. There is
no date, and nothing is charged. Leave an email and we will tell you when it exists, once.
Used only to tell you when the report exists.
Not shared, not sold, and not added to a mailing list.
The Coast Guard recorded this vessel and the following in the same
inspection activity — normally a tug and the barges in its tow. Only barges and towing
vessels are in this archive, so any other vessel type in the same activity does not
appear here: these lists are a floor, not a complete manifest.
Electrical › Electric Supply System (service) › Cable
Issued 3 March 2017Resolved
Revise electrical one line drawing to address the installation of a ground conductor between the barges, that tan electrical interlock is provided between the 100 amp overboard power circuit breaker and that suitable ground detection is intalled on the distribution system.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 1 August 2017
Resolved 1 November 2017
Resolution: One line drawing revised addressing the installation of a ground conductor between the barges, an interlock was provided between teh 100 amp overboard power circuit breaker and a suitable ground detection is installed on the distribution system.
Engineering › Fuel Oil Service System › Hose
Issued 17 February 2016Resolved
Repair or replace fuel hose.
Condition: Invalid
Due 17 February 2016
Resolved 17 February 2016
Resolution: Replaced Hose
Electrical › Electric Generation Source (service) › Generator
Issued 21 January 2014Resolved
Provide Ammeter for generator powering thermal fluid heater. 46 CFR 111.12-5, 46 CFR 111.30-25
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 21 February 2014
Resolved 31 January 2014
Resolution: Ammeter installed as per regulations.