Records from 2012 to 2024. Most recent: inspection, 9 February 2024.
Inspection history · 20
9 February 2024
COC-TVE Annual · PSC B
Physical examination · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 7860976
18 June 2023
Administrative Inspection
Administrative · Sector Corpus Christi · USCG Heartland District (CGD-H) · Activity 7717602
11 May 2023
PSC B
Physical examination · Marine Safety Unit Lake Charles · USCG Heartland District (CGD-H) · Activity 7685240
4 April 2023
Administrative Inspection
Administrative · Sector Mobile · USCG Heartland District (CGD-H) · Activity 7662642
15 January 2023
PSC B
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 7621233
7 January 2023
PSC B · COC-TVE Renew · Deficiency Check
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7617865
16 February 2021
COC-TVE Renew · PSC B
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7141204
17 July 2015
Ballast Water Examination · COC-TVE Annual · ISPS II Exam
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 5180029
23 August 2014
Type not recorded
No type recorded · Sector Western Alaska and U.S. Arctic · USCG Arctic District (CGD-A) · Activity 4987549
1 August 2014
Type not recorded
No type recorded · Sector Western Alaska and U.S. Arctic · USCG Arctic District (CGD-A) · Activity 4987538
17 July 2012
Deficiency Check
Physical examination · Marine Safety Unit Savannah · USCG Southeast District (CGD-SE) · Activity 4381565
29 June 2012
STCW 95 Exam
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 4364975
29 June 2012
Random ISPS/MTSA-No PSC
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 4365653
29 June 2012
Type not recorded
No type recorded · Sector Miami · USCG Southeast District (CGD-SE) · Activity 4368148
22 June 2012
Type not recorded
No type recorded · Marine Safety Unit Savannah · USCG Southeast District (CGD-SE) · Activity 4351910
19 June 2012
ISPS III Exam · COC-TVE Renew · Ballast Water Examination
Physical examination · Marine Safety Unit Savannah · USCG Southeast District (CGD-SE) · Activity 4348763
27 February 2012
Deficiency Check
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 4251639
26 January 2012
ISM Exam · ISPS II Exam
Physical examination · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 4232429
10 January 2012
Type not recorded
No type recorded · Sector Delaware Bay · USCG East District (CGD-E) · Activity 4222885
4 January 2012
ISPS III Exam · COC-TVE Annual · Ballast Water Examination · Deficiency Check
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 4218032
03 - Water/Weathertight Conditions › N/A - No Subsystem › Other (load lines)
Issued 11 May 2023
Resolved
Condition: Invalid
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 18 June 2023
Resolution: Provided pictures.
14 - Pollution Prevention › 147 - Anti-Fouling › Other (AFS)
Issued 11 May 2023
Resolved
Condition: Improper/Lack of Maintenance
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 18 June 2023
Resolution: Provided pictures.
15 - Safety Management Systems (ISM) › N/A - No Subsystem › Maintenance of the ship and equipment
Issued 7 January 2023
Resolved
74 SOLAS (2020) CH. IX/3.1/ISM Code 10.2: OBJECTIVE EVIDENCE DISCOVERED DURING AN EXPANDED ISM EXAM
REVEALED THE FOLLOWING DEFICIENCY: THE VESSEL FAILED TO FULLY
IMPLEMENT THE REQUIREMENTS OF THE ISM CODE THROUGH THEIR SMS
PROCEDURES. THE COMPANY DID NOT TAKE APPROPRIATE ACTIONS ON
IDENTIFIED NON-CONFORMITIES. THIS IS MADE EVIDENT BY DEFICIENCY 2. AN EXTERNAL AUDIT IS REQUIRED; A COMPLETE SHIPWIDE INSPECTION OF THE FIREFIGHTING EQUIPMENT IS REQUESTED.
Action required: 30 - Ship detained
Resolved 8 January 2023
Resolution: Vessel submitted satisfactory external audit.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 7 January 2023
Resolved
74 SOLAS (2009) CH. II-2/14.2.1.2:
FIRE-FIGHTING SYSTEMS AND APPLIANCES SHALL BE KEPT IN GOOD
WORKING ORDER AND READILY AVAILABLE FOR IMMEDIATE USE. PSCO
OBSERVED 24 OF 33 FOAM DISCHARGE NOZZLES IN THE ENGINE ROOM WERE BLOCKED PREVENTING THE OPERATION OF PRIMARY FIREFIGHTING
CAPABILITIES WITHIN THE SPACE.
Action required: 30 - Ship detained
Resolved 8 January 2023
Resolution: Vessel provided class report and CG witnessed replaced nozzles
14 - Pollution Prevention › 141 - MARPOL Annex I › Oil discharge monitoring and control system
Issued 7 January 2023
Resolved
MARPOL 73/78 ANNEX I/31.1:
OIL TANKERS OF 150 GROSS TONNAGE AND ABOVE SHALL BE EQUIPPED
WITH AN OIL DISCHARGE MONITORING AND CONTROL SYSTEM (ODME)
APPROVED BY THE ADMINISRATION. PSCO WAS UNABLE TO WITNESS AN
OPERATIONAL TEST OF THE ODME DUE TO SYSTEM ALARMS AND ERRORS.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 8 January 2023
Resolution: Vessel provided class report and CG witnessed proper ODME testing.
11 - Life Saving Appliances › N/A - No Subsystem › Operational readiness of lifesaving appliances
Issued 7 January 2023
Resolved
74 SOLAS (2020) CH. III/20.2:
BEFORE THE SHIP LEAVES PORT AND AT ALL TIMES DURING THE VOYAGE, ALL LIFE-SAVING APPLIANCES SHALL BE IN WORKING ORDER AND READY FOR IMMEDIATE USE. PSCO OBSERVED LIFEBOAT EQUIPMENT AND BATTERY CHARGERS OCCUPYING 03 SEATS ON EACH LIFEBOAT, REDUCING SEAT AVAILABILITY BELOW REQUIRED CAPACITY.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 21 January 2023
Resolved 8 January 2023
Resolution: Vessel provided class report and CG saw all seats within lifeboats were cleared.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 7 January 2023
Resolved
74 SOLAS (2004) CH. II-1/45.10.5:
NO ELECTRICAL EQUIPMENT SHALL BE INSTALLED IN ANY SPACE WHERE
FLAMMABLE MIXTURES ARE LIABLE TO COLLECT INCLUDING THOSE ONBOARD TANKERS UNLESS THE ADMINISTRATION IS SATISFIED THAT SUCH EQUIPMENT IS APPROPRIATELY CERTIFIED FOR SAFE USAGE IN THE DUSTS, VAPOURS OR GASES LIKELY TO BE ENCOUNTERED. PSCO OBSERVED BONDING CABLES INSIDE THE CARGO PUMP ROOM FOR THE BALLAST WATER TREATMENT SYSTEM REMOTE VALVE WERE NOT PROPERLY CONNECTED.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 21 January 2023
Resolved 8 January 2023
Resolution: Vessel provided class report.
15 - Safety Management Systems (ISM) › N/A - No Subsystem › Resources and personnel
Issued 7 January 2023
Resolved
74 SOLAS (2020) CH. IX/3.1 ISM Code 6.3:
THE COMPANY SHOULD ESTABLISH PROCEDURES TO ENSURE THAT NEW
PERSONNEL AND PERSONNEL TRANSFERRED TO NEW ASSIGNMENTS RELATED TO SAFETY AND PROTECTION OF THE ENVIRONMENT ARE GIVEN PROPER FAMILIARIZATION WITH THEIR DUTIES. PSCO OBSERVED THE DESIGNATED CREWMEMBER RESPONSIBLE FOR HANDLING CARGO OPERATIONS WAS FOUND UNFAMILIAR WITH CARGO VENTING ARRANGMENTS, THE VAPOUR COLLECTION SYSTEM, AND FUNCTIONAL TESTING FOR PORTABLE GAS DETECTORS. AN INTERNAL AUDIT IS REQUIRED WITHIN THREE MONTHS.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 7 April 2023
Resolved 5 April 2023
Resolution: Recieved satisfactory internal audit from Flag state.
Deck/Cargo › Cargo Transfer/Lightering (liquid) › Electric Bonding
Issued 19 June 2012
Resolved
No apparent bonding on cargo piping in way of dresser couplings. Drawings on vessel did not indicate that the couplings were conductive. Proof of conductive couplings or flagstate's acceptance of bonding technique to be provided prior to next U. S. Port after sailing foreign.
Condition: Improper Installation
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 10 July 2012
Resolution: Recieved documentation proving that couplings are acceptable by flag/class rules.
Deck/Cargo › Holds/Tanks › Tank Level Monitoring Device
Issued 4 January 2012
Resolved
1840 - Instrumentation - Each cargo tank of a tank ship must be equipped with a tank overfill alarm. Vessel's overfill alarm on #1 COT (Port) is inoperable. Vessel prohibited from loading cargo in #1 COT (Port) in US territorial waters. 46 CFR 39.20-7
Action required: 705 - Other - as specified
Due 4 February 2012
Resolved 9 January 2012
Resolution: Received, reviewed and accepted class report from Korean Register of Shipping attesting to proper repair of cargo overfill alarm.
Documentation › Logs/Records › Oil Record Book
Issued 4 January 2012
Resolved
1710 - Oil record book - The quantities of oil residues retained onboard in tanks listed in item 3.1 of the supplement to the IOPP certificate should be recorded weekly as per Appendix III of MARPOL I. Vessel is not recording weekly soundings of two tanks listed on IOPP certificate issued Oct. 2011 - the scavenge and stuffing box drain tanks. MARPOL Annex I/17.
Action required: 705 - Other - as specified
Resolved 4 January 2012
Resolution: Identified source of error to be from the new addition of these two tanks on the Oct. 2011 issued IOPP supplement certificate. Master and C/E aware of issue and requirement to include these two tanks in weekly soundings recorded in ORB.
Fire Fighting › Fixed Low-Expansion Foam Fire Extinguishing System › Foam Source
Issued 4 January 2012
Resolved
0725 - Fixed fire extinguishing installation - Periodical controls of foam concentrates stored on board should be performed after a period of 3 years and, after that, every year per FSS Code Ch. 6/2.3.1.1. Vessel's low-expansion foam analysis expired on 16 Dec 2011. SOLAS Ch. II-2/1.6.4 & MSC/Circ.582
Action required: 705 - Other - as specified
Due 4 February 2012
Resolved 27 February 2012
Resolution: Recieved copy of Foam Analysis Report. All satisfactory.