Inspection history · 52
21 July 2026
Re-Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 8440425
10 April 2026
Security Breach, Potential
Type not classified · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 8349558
5 November 2025
COI Inspection · Deficiency Check
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 8243247
11 September 2025
Re-Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 8229409
12 June 2025
Re-Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 8161016
21 March 2025
Hull Examination · Examination of Repairs · Internal Structural Exam · In-Service Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 8097588
31 January 2025
Re-Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 8070207
23 October 2024
MTSA Verification · COI Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 8020940
31 July 2024
Re-Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 7970607
22 April 2024
Re-Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 7897717
26 January 2024
Deficiency Check · Re-Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 7856332
18 January 2024
Construction Oversight
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 7851588
15 November 2023
COI Inspection · Deficiency Check
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 7822218
24 July 2023
Re-Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 7750493
19 May 2023
In-Service Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 7692272
20 April 2023
Re-Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 7671751
27 October 2022
Deficiency Check · MTSA Verification · COI Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 7566171
23 August 2022
Re-Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 7536032
14 April 2022
Re-Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 7430272
4 January 2022
Examination of Repairs · Hull Examination · Internal Structural Exam
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 7375299
23 December 2021
Special Consideration
Administrative · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 7371983
10 November 2021
COI Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 7344430
1 September 2021
Re-Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 7301150
20 July 2021
Re-Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 7260765
10 February 2021
Re-Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 7138486
2 October 2020
COI Inspection · Internal Structural Exam · Deficiency Check · MTSA Verification · Hull Examination
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 7069885
23 July 2020
Re-Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 7011139
6 April 2020
Special Consideration
Administrative · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 6935967
19 November 2019
COI Inspection · MTSA Verification
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 6856527
23 October 2019
Re-Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 6839608
10 July 2019
Re-Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 6744983
21 May 2019
Re-Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 6690592
31 March 2019
Type not recorded
No type recorded · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 6679488
13 December 2018
MTSA Verification · COI Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 6587581
2 November 2018
Re-Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 6571123
10 August 2018
Deficiency Check
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 6510160
30 July 2018
Re-Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 6495689
31 May 2018
Internal Structural Exam · Hull Examination
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 6431303
19 December 2017
MTSA Verification · COI Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 6326677
14 August 2017
Type not recorded
No type recorded · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 6271190
30 May 2017
Re-Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 6163395
14 May 2017
Type not recorded
No type recorded · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 6155978
27 April 2017
Deficiency Check
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 6133873
20 March 2017
Examination of Repairs
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 6108178
4 January 2017
COI Inspection · MTSA Verification
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 6065581
30 November 2016
Re-Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 6070068
15 June 2016
Re-Inspection · Deficiency Check
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 5907451
6 May 2016
Deficiency Check
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 5870316
18 March 2016
Examination of Repairs
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 5836125
10 March 2016
Type not recorded
No type recorded · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 5858368
26 January 2016
MTSA Verification · Deficiency Check · COI Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 5803744
22 January 2016
Re-Inspection · Plan Review (Other than "T")
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 5800918
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 5 November 2025
Resolved
Lifejackets stowage positions must be marked with "LIFEJACKETS". One stowage container on portside in the accomodation space is missing the lifejacket placard.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 19 November 2025
Resolved 14 November 2025
Resolution: Placard was replaced.
04 - Emergency Systems › N/A - No Subsystem › Emergency, lighting, batteries and switches
Issued 5 November 2025
Resolved
Emergency lighting must be marked indicating what lights will illuminate on emergency power. One light on the port side was mislabeled as emergency light but did not energize on emergency power.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 19 November 2025
Resolved 14 November 2025
Resolution: Corrected
08 - Alarms › N/A - No Subsystem › Machinery controls alarm
Issued 5 November 2025
Resolved
Port Main engine high water temp was inoperable.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 19 November 2025
Resolved 14 November 2025
Resolution: Switch replaced and retested, sat.
04 - Emergency Systems › N/A - No Subsystem › Emergency source of power - Emergency generator
Issued 5 November 2025
Resolved
Emergency power source must start automatically. The starting battery did not automatically start the emergency source of power. Replaced battery and retesting auto start, all sat. Cleared on the spot.
Action required: 10 - Deficiency Rectified
Resolved 5 November 2025
08 - Alarms › N/A - No Subsystem › Steering gear alarm
Issued 5 November 2025
Resolved
Audible and visible alarm must activate in the pilothouse upon failure of electrical power to the steering gear. Only visible alarms were observed in the pilot house. Fixed loose wire, all sat. Cleared on the spot.
Action required: 10 - Deficiency Rectified
Resolved 5 November 2025
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 31 January 2025
Resolved
FSD on port side aft main deck does not have a handle.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 14 February 2025
Resolved 12 June 2025
Resolution: New handel installed at last drydock.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 31 January 2025
Resolved
FSD on stbd side aft main cabin will not fully close.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 14 February 2025
Resolved 12 June 2025
Resolution: Door repaired at last dry dock.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 31 January 2025
Resolved
FSD on port side bar to upperdeck stairs does not latch.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 14 February 2025
Resolved 12 June 2025
Resolution: Door repaired at last drydock.
02 - Structural Conditions › N/A - No Subsystem › Decks - corrosion
Issued 31 January 2025
Resolved
Crop and renew main deck structure on aft section of bow door. To be completed at upcoming drydock prior to credit.
Action required: 705 - Other - as specified
Resolved 12 June 2025
Resolution: Completed at last dry dock.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 26 January 2024
Resolved
Rec'd report of control head going out on the port control head. After new control head placed on board, it is still not working properly. Make repairs and provide report (identify cause) prior to operating with passengers.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 26 January 2024
Resolution: completed repair, replaced harness and tested satisfactory.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 15 November 2023
Resolved
Before the vessel leaves port and at all times during the voyage, each lifesaving appliance must be in working order. The port aft lifering is in poor condition.
Condition: Damaged By Earlier Event
Action required: 16 - Rectify deficiencies w/in 14 days
Due 29 November 2023
Resolved 28 November 2023
Resolution: completed
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 15 November 2023
Resolved
#2 Generator not able to perform PTSP due to mechanical failure. Make generator full operational and conduct required testing
Condition: Damaged By Earlier Event
Action required: 16 - Rectify deficiencies w/in 14 days
Due 29 November 2023
Resolved 1 December 2023
Resolution: completed tests
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Gauges, thermometers, etc
Issued 15 November 2023
Resolved
Aft STBDside pressure vessel relief valve not operating at OEM required 180 psi to lift. Replace relief valve and conduct required test.
Condition: Damaged By Earlier Event
Action required: 16 - Rectify deficiencies w/in 14 days
Due 29 November 2023
Resolved 28 November 2023
Resolution: installed new
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 15 November 2023
Resolved
Heat traces for outside piping have unauthorized electrical piggy back outlets. Remove outlets and provide plan to meet the required standards.
Condition: Damaged By Earlier Event
Action required: 16 - Rectify deficiencies w/in 14 days
Due 29 November 2023
Resolved 28 December 2023
Resolution: completed
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 27 October 2022
Resolved
Prove proper operation of bilge suction on void #5 and steering void.
Action required: 17 - Rectify deficiencies prior to departure
Due 27 October 2022
Resolved 27 October 2022
Resolution: Vessel replaced steering gear room check valve in bilge system and overhauled the #5 void check valve. Vessel was able to pump water from both spaces. However the vessel rep. intends to conduct more servicing on the bilge system to prevent future non-comp
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 27 October 2022
Resolved
Prove proper operation of e-gen alarms. While conducting testing for the emergency generator the jacket water sensor shorted out when it grounded to the engine. Testing of overspeed, high jacket water and low lube oil alarm will be completed after the sensor is replaced.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 10 November 2022
Resolved 1 November 2022
Resolution: Emergency generator alarms tested and ran under load. Sat.
08 - Alarms › N/A - No Subsystem › Steering gear alarm
Issued 27 October 2022
Resolved
Vessels steering gear alarms on the bridge were cross connected and failed to alarm properly.
Action required: 10 - Deficiency Rectified
Resolved 27 October 2022
Resolution: corrected on the spot
08 - Alarms › N/A - No Subsystem › Machinery controls alarm
Issued 10 October 2020
Resolved
Generator 1 high jacket water sensor did not function correctly
Action required: 10 - Deficiency Rectified
Resolved 10 November 2020
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 19 November 2019
Resolved
Remove dead end wires from car deck
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 20 November 2019
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 19 November 2019
Resolved
Hydrostatic test of ships PVs was required due to excess rust build up and inability to conduct a full visual inspection
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 20 November 2019
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 19 November 2019
Resolved
Properly terminate dead end wiring located under the operating station
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 20 November 2019
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 19 November 2019
Resolved
Post instructions for the proper operation of the CO2 system located outside the boiler room.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 20 November 2019
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 19 November 2019
Resolved
Replace high jacket water temperature shut down sensor for the #1 generator
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 20 November 2019
09 - Working and Living Conditions › 091 - Living Conditions › Water, pipes, tanks
Issued 30 July 2018
Resolved
Repair/replace sink drain in bar area.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 30 August 2018
Resolved 10 August 2018
Resolution: New sink drain installed.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 30 July 2018
Resolved
Repair/replace electrical junction box IWO fire station NO.12
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 30 August 2018
Resolved 10 August 2018
Resolution: New junction box installed.
07 - Fire Safety › N/A - No Subsystem › Operation of Fire protection systems
Issued 30 July 2018
Resolved
Repair/replace safety pins on manual activation pull lever.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 30 August 2018
Resolved 10 August 2018
Resolution: Safty pins cleand and found sat.
07 - Fire Safety › N/A - No Subsystem › Ready availability of fire fighting equipment
Issued 30 July 2018
Resolved
Install spanner wrench on fire station No.15 and No.11
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 30 August 2018
Resolved 10 August 2018
Resolution: Spanner wrenches installed.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Gauges, thermometers, etc
Issued 30 July 2018
Resolved
Repair/replace P/S bridge wing tach rpm guage
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 30 August 2018
Resolved 10 August 2018
Resolution: RPM guage replaced.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 30 July 2018
Resolved
Relocate e-fuel shut offs for main fuel tank to a position that no car can part over.
Condition: Placed in Improper Service
Action required: 50 - Rectify deficiencies w/in 30 days
Due 30 August 2018
Resolved 2 November 2018
Resolution: New fuel shut off installed and tested.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 30 July 2018
Resolved
Replace outlet PS upper car deck.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 30 August 2018
Resolved 10 August 2018
Resolution: New outlet cover installed.
04 - Emergency Systems › N/A - No Subsystem › Emergency, lighting, batteries and switches
Issued 30 July 2018
Resolved
Label e-lights on car deck.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 30 August 2018
Resolved 10 August 2018
Resolution: E lights labled.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 30 July 2018
Resolved
Label hydralic pump motor controller PS upper car deck.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 30 August 2018
Resolved 10 August 2018
Resolution: Moter controller labled.
09 - Working and Living Conditions › 092 - Working Conditions › Danger areas
Issued 30 July 2018
Resolved
Provide thernmal protection PS exhaust towers on upper car deck
Condition: Placed in Improper Service
Action required: 50 - Rectify deficiencies w/in 30 days
Due 30 August 2018
Resolved 10 August 2018
Resolution: Thermal protection for both exhaust towers was installed.
Accommodation/Occupational Safety › Occupational Safety › Tripping/Falling Hazard
Issued 19 December 2017
Resolved
Close off aft 01 deck to passengers due to the benches rotting.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 9 February 2018
Resolved 31 July 2018
Electrical › Lighting (emergency) › Lighting Fixture
Issued 19 December 2017
Resolved
Adjust starboard embarkation light to point down.
Condition: Design Flaw
Action required: 705 - Other - as specified
Due 9 February 2018
Resolved 31 July 2018
Lifesaving › Inflatable Buoyant Apparatus › Stowage
Issued 19 December 2017
Resolved
Stencil life frat stations to "PULL PINS PRIOR TO LAUNCHING"
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 9 February 2018
Resolved 31 July 2018
Communications › Alarms/Indicators › General Alarm
Issued 19 December 2017
Resolved
Add General Alarm bell to aft sleeping quarters IWO Captains cabin.
Condition: Design Flaw
Due 9 February 2018
Resolved 31 July 2018
Electrical › Electrical Distribution System (service) › Cable
Issued 11 January 2017
Resolved
Provide proper cable supports for new outlets in void spaces (Heat tape outlets).
Due 10 February 2017
Resolved 27 April 2017
Electrical › Electrical Distribution System (service) › Cable
Issued 11 January 2017
Resolved
Seal cable penetrations (2) on upper and lower car decks, starboard side, adjacent to elevator trunk.
Due 11 February 2017
Resolved 27 April 2017
Fire Fighting › Ventilation Systems › Ventilation Fire Dampers
Issued 15 June 2016
Resolved
Repair wasted damper for crew space furnace room.
Due 15 July 2016
Resolved 23 June 2016
Resolution: Damper repaired.
Electrical › Electrical Distribution System (service) › Wiring
Issued 26 January 2016
Resolved
Repair smashed cable supports in overhead of car deck, forward.
Due 2 March 2016
Resolved 6 May 2016
Lifesaving › Lifebuoys › Serviceable
Issued 26 January 2016
Resolved
Renew retro tape on ring buoy on aft car deck.
Due 2 March 2016
Resolved 6 May 2016
Construction/Loadline › Structures › Transverse Bulkhead
Issued 26 January 2016
Resolved
Complete welding on renewed bulkhead stiffeners in forepeak.
Due 2 March 2016
Resolved 9 February 2016
Resolution: Stiffeners welded.
Engineering › Bilge Water Management System › Not Operational
Issued 26 January 2016
Resolved
Clean debris out of forepeak bilge.
Due 2 March 2016
Resolved 9 February 2016
Resolution: Bilge cleaned.
Engineering › Bilge Water Management System › Strainer
Issued 26 January 2016
Resolved
Clean bilge strainer in forepeak.
Due 2 March 2016
Resolved 9 February 2016
Resolution: New strainer installed.
Construction/Loadline › Structures › Scuttle
Issued 26 January 2016
Resolved
Provide captive chains for void #1 and forepeak scuttles.
Due 2 March 2016
Resolved 9 February 2016
Resolution: Chains installed.
Engineering › Steering Gear System › Linkage
Issued 26 January 2016
Resolved
Switch bolt placement and double nut port rudder feedback device linkage.
Due 9 February 2016
Resolved 6 May 2016
Engineering › Bilge Water Management System › Not Operational
Issued 26 January 2016
Resolved
Demonstrate proper operation of forepeak bilge suction.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 9 February 2016
Resolution: Bilge main repaired and tested satisfactory.
Construction/Loadline › Structures › Door
Issued 26 January 2016
Resolved
Repair door on port stack so it closes.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 4 February 2016
Resolution: Door gasket properly installed.
Lifesaving › Rescue Boat Equipment › Painter
Issued 26 January 2016
Resolved
Provide cleats for rescue boat tending lines.
Due 2 March 2016
Resolved 6 May 2016
Accommodation/Occupational Safety › Occupational Safety › Deck Rail
Issued 26 January 2016
Resolved
Provide child proof latches for the IBA railing gates.
Due 2 March 2016
Resolved 6 May 2016
Accommodation/Occupational Safety › Occupational Safety › Deck Rail
Issued 26 January 2016
Resolved
Reposition or extend railing on at port IBA entrance.
Due 2 March 2016
Resolved 6 May 2016
Fire Fighting › Fixed Pressure Water-Spraying Fire Extinguishing System › Piping
Issued 26 January 2016
Resolved
Repair holed supply piping in zones C & D.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 9 February 2016
Resolution: piping repaired and tested satisfactory.