Records from 2006 to 2019. Most recent: inspection, 24 July 2019.
Inspection history · 21
24 July 2019
ISPS II Exam · COE-Offshore · PII Safety Exam · Ballast Water Examination
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 6760126
24 March 2017
Type not recorded
No type recorded · Marine Safety Unit Portland OR · USCG Northwest District (CGD-NW) · Activity 6110701
21 March 2017
ISPS III Exam · NPV Safety Exam · Ballast Water Examination
Physical examination · Marine Safety Unit Portland OR · USCG Northwest District (CGD-NW) · Activity 6104949
27 November 2016
Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6047975
27 November 2016
Type not recorded
No type recorded · Marine Safety Unit Belfast · USCG Northeast District (CGD-NE) · Activity 6048374
26 November 2016
Special
Type not classified · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6047777
26 November 2016
Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6048660
1 April 2016
ISPS II Exam · Ballast Water Examination · PII Safety Exam
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 5839122
29 March 2016
Type not recorded
No type recorded · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 5843292
23 March 2016
Type not recorded
No type recorded · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 5839215
10 October 2014
ISPS II Exam · PII Safety Exam · Ballast Water Examination
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 4998874
20 January 2011
Type not recorded
No type recorded · Sector New York · USCG Northeast District (CGD-NE) · Activity 3927354
19 January 2011
Ballast Water Examination · PII Safety Exam · ISPS II Exam
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 3929223
22 June 2007
Administrative Inspection
Administrative · Sector Corpus Christi · USCG Heartland District (CGD-H) · Activity 2970222
30 May 2007
Deficiency Check
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 2946130
25 May 2007
Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 2940003
23 October 2006
MARPOL Annex I Examination · Ballast Water Examination · PII Safety Exam · MARPOL Annex V Examination · ISPS III Exam
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 2806423
10 October 2006
PII Safety Exam · Ballast Water Examination · ISPS II Exam
Physical examination · Sector Delaware Bay · USCG East District (CGD-E) · Activity 2797073
8 October 2006
Type not recorded
No type recorded · Sector Delaware Bay · USCG East District (CGD-E) · Activity 2796179
7 October 2006
Type not recorded
No type recorded · Sector Delaware Bay · USCG East District (CGD-E) · Activity 2795518
7 October 2006
Type not recorded
No type recorded · Sector Delaware Bay · USCG East District (CGD-E) · Activity 2795819
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 24 July 2019
Resolved
74SOLAS(14)II-2/4.1.1 40ac The purpose of this regulation is to prevent the ignition of combustible materials or flammable liquids. For this purpose, the following functional requirements shall be met: means shall be provided to control leaks of flammable liquids. PSCO observed excessive oil leak from intake and exhaust manifold on #1 generator.
Condition: Invalid
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 31 July 2019
Resolution: Received e-mail with scanned NKK classification society survey report. Survey report states: All leakages from D/G's now rectified.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 24 July 2019
Resolved
74SOLAS(14)II-2/4.1.1 40ac The purpose of this regulation is to prevent the ignition of combustible materials or flammable liquids. For this purpose, the following functional requirements shall be met: means shall be provided to control leaks of flammable liquids. PSCO observed leakage from #1 generator exhaust pipe.
Condition: Invalid
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 31 July 2019
Resolution: Received e-mail with scanned NKK classification society survey report. Survey report states: All leakages from D/G's now rectified.
09 - Working and Living Conditions › 092 - Working Conditions › Steam pipes and pressure pipes
Issued 24 July 2019
Resolved
74SOLAS(14)I/11(a) 40ac The condition of the ship and its equipment shall be maintained to conform with the provisions of the present regulations to ensure that the ship in all respects will remain fit to proceed to sea without danger to the ship or persons onboard. PSCO observed missing handle on steam tracing pipe in the purifier room.
Condition: Improper/Lack of Maintenance
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 31 July 2019
Resolution: Received e-mail with scanned NKK classification society survey report. Survey report states: Missing valve handle replaced with new valve.
09 - Working and Living Conditions › 092 - Working Conditions › Other (accident prevention)
Issued 24 July 2019
Resolved
74SOLAS(14)I/11(a) 40ac The condition of the ship and its equipment shall be maintained to conform with the provisions of the present regulations to ensure that the ship in all respects will remain fit to proceed to sea without danger to the ship or persons onboard. PSCO observed missing eye protection from grinding wheel in electrical workshop.
Condition: Improper Installation
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 31 July 2019
Resolution: Received e-mail with scanned NKK classification society survey report. Survey report states: Missing eye protector from grinding wheel in electrical workshop now in order.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Operating Instructions
Issued 21 March 2017
Resolved
0915-Sign indicators-At each location there shall be clear instructions relating to the operation of the fire-extinguishing system having regard to the safety of personnel. No instructions were posted relating to the operation of the local purifier room CO2 system. SOLAS 74(09) II-2/10.4.1.1.1 FSS Code 5.2.1.3.3 -50ac
Action required: 705 - Other - as specified
Due 21 April 2017
Resolved 24 July 2019
Resolution: Instructions were found to be posted for all activations points for CO2 systems during exam on 24JUL19.
Fire Fighting › Fixed Fire Detection System › Alarms
Issued 21 March 2017
Resolved
1099-Other(alarm-signals)-Activation of any local application system shall give a visual and distinct audible alarm in the protected space and at continuously manned stations. Fixed local CO2 system for purifier room is not equipped with visual or audible alarms. SOLAS74(09) II-2/10.5.6.4- 50ac
Action required: 705 - Other - as specified
Due 21 April 2017
Resolved 24 July 2019
Resolution: CO2 system for purifier room was found to be equipped with visual or audible alarms during exam on 24JUL19.
Navigation › Piloting/Steering › Gryo Compass Repeater
Issued 21 March 2017
Resolved
1540-Gyrocompass-All ships of 500 gross tonnage and upwards shall have a gyro-compass heading repeater, or other means, to supply heading information at emergency steering position. Gyro-compass heading repeater is inoperable in steering gear room. SOLAS74(14) V/19.2.5.2- 50ac
Action required: 705 - Other - as specified
Due 21 April 2017
Resolved 31 July 2019
Resolution: Received e-mail with scanned NKK classification society survey report. Survey report states: Steering gear room gyro repeater was repaired by the attending service technician and is now in good order.
Navigation › Piloting/Steering › Gryo Compass Repeater
Issued 21 March 2017
Resolved
1540-Gyrocompass-All ships of 500 gross tonnage and upwards shall have a gyro-compass bearing repeater, or other means, to take bearings. Gyro-compass bearing repeaters on bridge wings had a +/- 5 degree deviation from main gyrocompass. SOLAS74(14) V/19.2.5.3- 50ac
Action required: 705 - Other - as specified
Due 21 April 2017
Resolved 24 July 2019
Resolution: Gyro-compass bearing repeaters on bridge wings were found satisfactory during exam conducted on 24JUL19.
Fire Fighting › Miscellaneous Items › A Class Division Penetrations
Issued 21 March 2017
Resolved
0750-Fire prevention-"A" class divisions are so constructed as to be capable of preventing the passage of smoke and flame. Cable ducts in the A and B decks had cable penetrations. SOLAS74(09) II-2/3.2.4- 50ac
Action required: 705 - Other - as specified
Due 21 April 2017
Resolved 24 July 2019
Resolution: No "A" class divisions were found to have improper cable penetrations during exam conducted on 24JUL19.
Fire Fighting › Structural - A Class Divisions › Fire Doors
Issued 21 March 2017
Resolved
0750-Fire prevention-Stairways which penetrate more than a single deck shall be surrounded by at least "A-0" class divisions and be protected by self-closing doors at all levels. Doors from galley to provisions store and crew pantry are designated as self-closing on the fire control plan but are not self-closing. SOLAS74(09) II-2/9.2.3.4.1- 50ac
Action required: 705 - Other - as specified
Due 21 April 2017
Resolved 24 July 2019
Resolution: Doors in and around galley and to provisions store and crew pantry were found to comply with fire control plan during exam conducted on 24JUL19.
Fire Fighting › Structural - B Class Divisions › Doors
Issued 21 March 2017
Resolved
0750-Fire prevention-Doors required to be self-closing shall not be fitted with hold-back hooks. Self-closing door to purifying flat had a hold-back. SOLAS74(09) II-2/9.4.2.2- 10c
Action required: 705 - Other - as specified
Due 21 March 2017
Resolved 21 March 2017
Construction/Loadline › Structures › Door
Issued 21 March 2017
Resolved
1270-Doors-All access openings in bulkheads at ends of enclosed superstructures shall be weathertight when closed. Stern doors to steering gear room and food provision stores would not close with a weathertight seal. ICLL 88 Protocol/12(1)- 10c
Action required: 705 - Other - as specified
Due 21 March 2017
Resolved 21 March 2017
Construction/Loadline › Hull › Side Shell
Issued 26 November 2016
Resolved
The Adm shall satisfy itself that the gen structural strength of the ship is adequate. Vessel sustained hull plate dmg and puncture to STBD BOW. Make repairs to the satisfaction to class prior ro departure.
Condition: Damaged By Earlier Event
Action required: 705 - Other - as specified
Resolved 27 November 2016
Resolution: Repairs were made to the satisfaction of class
Fire Fighting › Fixed Gas Fire Extinguishing System › Tanks
Issued 1 April 2016
Resolved
0725-Fixed fire extinguishing installation-High pressure cylinders should be subjected to periodical tests at intervals not exceeding 10 years, at which at least 10% of the total number provided should be subjected to an internal inspection and hydrostatic test. PSCO observed that CO2 bottles had not been hydrostatically tested since October 2005. SOLAS(14) II-2/14.2.1.2 & MSC.1/Circ.1318
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 15 April 2016
Resolved 8 April 2016
Resolution: Recieved proper documentation from Captain clearing deficiency.
Electrical › Lighting (emergency) › Lighting Fixture
Issued 1 April 2016
Resolved
0680-Embarkation arrangt. Surv. craft-Muster and embarkation stations shall be adequately illuminated by lighting supplied from the emergency source of electrical power. PSCO observed multiple emergency lights at the port side lifeboat muster station that were not operational.
Condition: Damaged By Earlier Event
Action required: 705 - Other - as specified
Due 1 April 2016
Resolved 1 April 2016
Resolution: Lights were fixed to the satisfaction of the attending Coast Guard Marine Inspector.
Fire Fighting › Fixed Fire Detection System › Alarms
Issued 10 October 2014
Resolved
The activation of any detector shall initiate a visual and audible alarm; if the signal has not received attention within 2 min, an audible alarm shall be sounded throughout machinery spaces of category A. PSCO tested and received the alarm on the bridge and engine control room, but no audible or visual alarm sounded in the engine room itself. 74SOLAS(01)II-2/13.1.4 CODE 16 A,C
Action required: 705 - Other - as specified
Due 25 October 2014
Resolved 1 November 2014
Resolution: PSC NOLA received a class report from NKK satisfying the requirement.
Construction/Loadline › Structures › Door
Issued 10 October 2014
Resolved
All access opening in bulkheads at ends of enclosed superstructure shasll be fitted with doors. The means for securing these doors weatherthight shall consist of gaskets and clamping devices or other equivalent means. The door leading from the engine room to the main deck in the dogged position, allowed light to be seen on 3 sides of the door. ICLL, Ch. II/Reg. 12.1 Code 16 A, C
Action required: 705 - Other - as specified
Due 25 October 2014
Resolved 1 November 2014
Resolution: PSC NOLA received a class report from NKK satisfying the requirement.