Records from 2005 to 2026. Most recent: inspection, 19 March 2026.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Operation of machinery
Issued 5 December 2025
Resolved
Electrical equipment on a vessel must be installed and maintained to provide services necessary for safety under normal and emergency conditions. Vessel reported loss of generator power and port generator failure. Rectify within 14 days. 46CFR120.200 (a).
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 11 December 2025
Resolution: Windings on port generator were replaced. All sat.
09 - Working and Living Conditions › 091 - Living Conditions › Lighting (Accommodation)
Issued 28 April 2025
Resolved
Each vessel must have adequate emergency lighting fitted along the line of escape to the main deck from all passenger and crew accommodation spaces located below the main deck". MIs observed no emergency lighting in the aft stalls in the men and womens bathroom. Provide additional emergency lighting in the aft head.
46 CFR 120.432
Action required: 16 - Rectify deficiencies w/in 14 days
Due 12 May 2025
Resolved 13 May 2025
Resolution: Vessel rep provided emergency lighting.
09 - Working and Living Conditions › 091 - Living Conditions › Lighting (Accommodation)
Issued 28 April 2025
Resolved
All escape hatches and other emergency exits used as means of escape must be marked on both sides in clearly legible letters at least 50 millimeters (2 inches) high: “EMERGENCY EXIT, KEEP CLEAR”, unless such markings are deemed unnecessary by the cognizant OCMI". MIs observed a worn exit markings on the facade covering the watertight bulkhead in the forward male and female bathroom. Additionally, provide exit signage on both water tight doors to clearly articulate the direction and means of escape from restroom though Fixed water sprinkler system compartment to Main Deck.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 12 May 2025
Resolved 13 May 2025
Resolution: Vessel rep provided emergency signage.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 24 May 2024
Resolved
"Propulsion machinery must be suitable in type and
design for propulsion requirements of the hull in which
it is installed." Vessel reported excessive wear on both
stern drive units installed on the vessel. Prior to the
carriage of passengers, the vessel must submit a tow
plan for approval. Once approved, the vessel must only
operate IAW approved tug assist plan during memorial day
weekend and vessel must cease all operations when wind
speeds exceed 25 knots. After 27 May 2024, the vessel
must receive a full tech report and perform permanent,
necessary repairs to both stern drives prior to carrying
passengers. Vessel must perform satisfactory sea trial
in the presence of CG MI prior to carrying passengers.
Action required: 705 - Other - as specified
Resolved 18 October 2024
Resolution: Conducted Sea Trial to verify propulsion characteristics and maneuverability of vessel, all satisfactory
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 20 April 2023
Resolved
Each nozzle must be of a type approved in accordance with the approval series 162.027. Nozzle fitted on forward firehose was found leaking at the time of inspection
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 2 May 2023
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 20 April 2023
Resolved
Nonconducting mats or grating must be provided on the deck in front of each switchboard. Vessel was found to be missing a section of the nonconducting mat in front of the switchboard above the fuel crossover.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 2 May 2023
08 - Alarms › N/A - No Subsystem › Other (alarms)
Issued 20 April 2023
Resolved
Electrical equipment on a vessel must be installed and maintained to provide services necessary for satey under normal and emergency conditions. The alarm panel in the wheelhouse of the vessel has a "system trouble" in alarm module.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 2 May 2023
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 13 April 2021
Resolved
Repair insulation in forward elevator shaft.
Condition: Damaged By Earlier Event
Action required: 705 - Other - as specified
Due 19 April 2021
Resolved 20 October 2021
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 13 April 2021
Resolved
Install insulation missing from bow truster.
Action required: 705 - Other - as specified
Due 19 April 2021
Resolved 20 October 2021
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 13 April 2021
Resolved
Repair damaged insulation in port engine room inboard of generator.
Action required: 705 - Other - as specified
Due 19 April 2021
Resolved 20 October 2021
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 13 April 2021
Resolved
Secure hole at the deck on port and STBD side into engine room from vestibule with fire rated material to meet fire rating of bulkhead.
Action required: 705 - Other - as specified
Due 19 April 2021
Resolved 30 April 2021
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 13 April 2021
Resolved
Replace damaged fire hose in lower galley.
Action required: 705 - Other - as specified
Due 19 April 2021
Resolved 30 April 2021
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 13 April 2021
Resolved
Replace/ secure battery cover in forward STBD engine room.
Action required: 705 - Other - as specified
Due 19 April 2021
Resolved 30 April 2021
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 13 April 2021
Resolved
Replace missing light cover in STBD engine room over stern drive.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 26 April 2021
Resolved 30 April 2021
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 13 April 2021
Resolved
Install blank in electrical panel in engine room vestibule in space #9.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 26 April 2021
Resolved 30 April 2021
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Operation of machinery
Issued 13 April 2021
Resolved
Conduct satisfactory PSTP in the presence of Coast Guard Inspectors.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 13 May 2021
Resolved 6 April 2022
Resolution: MI witnessed PSTP
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 29 January 2020
Resolved
Electrical equipment on a vessel must be installed and maintained to protect passengers and the vessel from electrical hazards including fire caused by or originating in electrical equipment and electrical shock.
-Myriad extension cords and daisy chaining of power strips found throughout vessel.
-Broken ground prong found still in the galley outlet receptacle. Was found taped over.
-Electrical box in stbd aft engine room next to the watertight door needs to be mounted securely to bulkhead
-Replace all missing and broken light covers in port and stbd engine room
-DP9 electrical panel cover does not close
Condition: Improper Installation
Action required: 30 - Ship detained
Resolved 6 February 2020
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 29 January 2020
Resolved
120.340(g) Each connection to a conductor or terminal part of a conductor must be made within an enclosure. Myriad wires splices made outside of an enclosure throughout the vessel.
Condition: Improper Installation
Action required: 30 - Ship detained
Resolved 6 February 2020
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 29 January 2020
Resolved
120.370(b) Receptacle outlets and attachment plugs for portable lamps, tools, and similar apparatus operating at 100 volts or more, must have a grounding pole and a grounding conductor in the portable cord.
-Multiple plugs for equipment throughout vessel with the grounding prong removed or broken.
-Multiple portable heaters installed onboard vessel without grounding prong.
Condition: Improper Installation
Action required: 30 - Ship detained
Resolved 6 February 2020
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Gauges, thermometers, etc
Issued 29 January 2020
Resolved
120.324(c) Ground detection must be provided that: For an alternating current system, meets §111.05-27 in subchapter J of this chapter; and For a direct current system, meets §111.05-29 in subchapter J of this chapter.Ground detection system for 480v, 120v, 24v DC, 12v DC circuits not operational
Condition: Improper/Lack of Maintenance
Action required: 30 - Ship detained
Resolved 6 February 2020
07 - Fire Safety › N/A - No Subsystem › Maintenance of Fire protection systems
Issued 29 January 2020
Resolved
115.810(a) At each initial inspection for certification the owner shall be prepared to conduct tests and have the vessel ready for inspection of its fire protection equipment. Sprinkler water tank sight glass was not connected to the tank properly.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 6 February 2020
09 - Working and Living Conditions › 092 - Working Conditions › Entry dangerous spaces
Issued 29 January 2020
Resolved
122.612 (i)(2) Each entrance to a space storing carbon dioxide cylinders, a space protected by carbon dioxide systems, or any space into which carbon dioxide might migrate must be conspicuously marked as follows: “CARBON DIOXIDE GAS CAN CAUSE INJURY OR DEATH. WHEN ALARM OPERATES OR WINTERGREEN SCENT IS DETECTED, DO NOT ENTER UNTIL VENTILATED. LOCK OUT SYSTEM WHEN SERVICING.” The reference to wintergreen scent may be omitted for carbon dioxide systems not required to have odorizing units and not equipped with such units. CO2 label required on entrance into engine room hatch.
Condition: Improper/Lack of Maintenance
Action required: 30 - Ship detained
Resolved 6 February 2020
18 - Maritime Labour Convention (Not Applicable to PSC Exams conducted in the U.S.) › N/A - No Subsystem › Investigation after accident
Issued 29 January 2020
Resolved
46 CFR4.06-1(e) The marine employer shall ensure that all individuals engaged or employed on board a vessel are fully indoctrinated in the requirements of this subpart. Crew not trained and unable to identify reporting requirements following a serious marine incident
Condition: Improper/Lack of Maintenance
Action required: 30 - Ship detained
Resolved 6 February 2020
02 - Structural Conditions › N/A - No Subsystem › Closing devices/watertight doors
Issued 29 January 2020
Resolved
115.802 Inspection and operation of all watertight closures in the hull, decks, and bulkheads including through hull fittings and sea valves; Inspection and operation of all weathertight closures above the weather deck
Forward scuttle requires servicing and gasket replacement. Water intrusion is apparent in most forward scuttle space.
Stbd hatch on stern requires servicing and gasket replacement.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 6 February 2020
09 - Working and Living Conditions › 092 - Working Conditions › Obstruction/slipping, etc.
Issued 29 January 2020
Resolved
116.700 Crew work space must be of adequate construction to provide for the safe operation of the vessel and the protection and accommodation of the crew in a manner practicable for service. Large deck plate in galley evidenced severe wastage to supports eliminating installation of the deck plate. Deckplate was found in the vertical position against the bulkhead and a temporary small piece of steel installed to enable transiting through the space.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 6 February 2020
09 - Working and Living Conditions › 091 - Living Conditions › Cleanliness
Issued 29 January 2020
Resolved
115.818 At each inspection for certification and at every other vessel inspection, quarters, toilet and washing spaces, galleys, serving pantries, lockers, and similar spaces may be examined to determine that they are serviceable and in a sanitary condition. Cleanliness of bathrooms
Condition: Improper/Lack of Maintenance
Action required: 30 - Ship detained
Resolved 6 February 2020
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 22 January 2020
Resolved
PROPULSION MACHINERY MUST BE SUITABLE IN TYPE AND DESIGN FOR PROPULSION REQUIREMENTS OF THE HULL IN WHICH IT IS INSTALLED AND CAPABLE OF OPERATING AT CONSTANT MARINE LOAD.
VESSEL REPORTED CASUALTY TO STARBOARD ENGINE. 46CFR119.200
REQUIREMENTS TO CARRY PASSENGERS AS FOLLOWS:
1. VESSEL MUST BE ESCORTED BY TUG WITH HORSEPOWER EQUIVALENT TO 10% OF CELESTIALS DEAD WEIGHT TONNAGE AT ALL TIMES WHEN PASSENGERS ARE ABOARD AND VESSEL IS UNDERWAY.
2. VESSEL MUST CONDUCT BRIEF WITH TUG PRIOR TO GETTING UNDERWAY ON PROCEDURES TO TAKE IN CASE TUG IS NEEDED.
3. VESSEL MUST CHECK OUT WITH VTS AND CHECK IN WITH VTS FOR ALL TRIPS.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 5 February 2020
Resolved 6 February 2020
09 - Working and Living Conditions › 092 - Working Conditions › Machinery
Issued 17 December 2019
Resolved
Electrical equipment on a vessel must be installed and maintained to provide services necessary for safety under normal and emergency conditions.
Auxiliary generator for AC system suffered internal component failure during routine maintenance checks with no passengers onboard. Vessel self-reported failure. Vessel must submit a written and signed technical report addressing the following in order for this deficiency to be rectified:
1. Provide causal analysis of failure.
2. Provide identification of parts replaced/installed and statement that repair is complete.
3. Conduct satisfactory operational load test.
4. Provide statement that generator is fully repaired, fully functional and that a satisfactory load test has been completed.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 16 January 2020
Resolved 31 December 2019
Resolution: received tech report.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 3 September 2019
Resolved
Vessel experienced a hydraulic leak on port z-drive. Vessel rep to submit a tech report to USCG SEC NY attesting to sat repairs or have a stdby tug available 1900-2200 on 03AUG19 prior to carrying pax.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 4 September 2019
Resolution: Tech report received
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 20 March 2019
Resolved
Demonstrate proper operation of vessels sprinkler system.
46 CFR 115.810
Action required: 701 - Prior to carriage of passengers/cargo
Due 20 March 2019
Resolved 21 March 2019
Resolution: Observed satisfactory test of the fire fighting sprinkler system.
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 20 March 2019
Resolved
Provide current Safety Radio Telephone Certificate. Vessel is limited to 1000 ft from shore. 47 CFR 80.59(a)(2)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 3 April 2019
Resolved 22 March 2019
Resolution: Recieved email copy
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 20 March 2019
Resolved
Provide current FCC Bridge to Bridge Certificate. Vessel is limited to 1000 ft from shore. 47 CFR 80.1001
Action required: 16 - Rectify deficiencies w/in 14 days
Due 3 April 2019
Resolved 22 March 2019
Resolution: Receieved email copy
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 20 March 2019
Resolved
Clean up sound room to minimize fire hazard. 46 CFR 115.830
Action required: 16 - Rectify deficiencies w/in 14 days
Due 3 April 2019
Resolved 3 April 2019
Resolution: Visted vessel for def follow-up. Def cleared
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 20 March 2019
Resolved
Properly label sending galley electrical panel DP-10. 46 CFR 120.220(d)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 3 April 2019
Resolved 3 April 2019
Resolution: Def cleared
03 - Water/Weathertight Conditions › N/A - No Subsystem › Manholes/flush scuttles
Issued 20 March 2019
Resolved
Replace gasket and clean knife edge area of bow thruster scuttle. 46 CFR 115.802(a)(2)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 3 April 2019
Resolved 3 April 2019
Resolution: Def cleared
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 20 March 2019
Resolved
Provide Vessel Security Plan annual audit for 2018. 33 CFR 104.415(b)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 3 April 2019
Resolved 22 March 2019
Resolution: Receieved email copy
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 20 March 2019
Resolved
Provide Company security exercise for 2018. 33 CFR 104.230
Action required: 16 - Rectify deficiencies w/in 14 days
Due 3 April 2019
Resolved 22 March 2019
Resolution: Received email copy
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 20 March 2019
Resolved
Ground indicating light on DC distribution panel is inoperable. 46 CFR 120.378
Action required: 16 - Rectify deficiencies w/in 14 days
Due 3 April 2019
Resolved 3 April 2019
Resolution: Def cleared
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 20 March 2019
Resolved
Port side engine room emergency lights were inoperable. 46 CFR 120.432(b)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 3 April 2019
Resolved 3 April 2019
Resolution: Def cleared
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 20 March 2019
Resolved
Repair leaking sight glass in sprinkler system tank. 46 CFR 115.810
Action required: 16 - Rectify deficiencies w/in 14 days
Due 3 April 2019
Resolved 3 April 2019
Resolution: Def cleared
02 - Structural Conditions › N/A - No Subsystem › Hull - corrosion
Issued 3 January 2019
Resolved
Observed numerous areas on the hull with pitting. Blast the following areas for further inspection: Port side outboard running along the chine up 3 feet toward deck line from midship to stern quarter, Starboard outboard midship section above the chine appx. 3'x4', and 3 sections along the keel running from bow to midship.
Action required: 705 - Other - as specified
Resolved 15 January 2019
Resolution: Observed hull within standards.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 3 January 2019
Resolved
Vessel not ready for ISE. Clean out bilge in the fore peak tank for further inspection.
Action required: 705 - Other - as specified
Resolved 15 January 2019
Resolution: Observed space within standards.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 3 January 2019
Resolved
Not ready ISE. Clean out bilge in the galley space for further inspection. Bilge was obstructed with deck plates and oily water residue.
Action required: 705 - Other - as specified
Resolved 15 January 2019
Resolution: Observed bilge area within standards.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 3 January 2019
Resolved
Remove excess hydraulic oil from aft machinery space (steering gear room).
Action required: 705 - Other - as specified
Resolved 15 January 2019
Resolution: Observed space within standards.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Operation of machinery
Issued 3 January 2019
Resolved
Repair hydraulic oil leak from the starboard Z-drive system.
Action required: 705 - Other - as specified
Resolved 15 January 2019
Resolution: Fixed hydraulic oil leak.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 3 January 2019
Resolved
Crop and renew to good metal deck plate support bracket located on the starboard aft main deck.
Action required: 705 - Other - as specified
Resolved 12 February 2019
Resolution: Completed satisfactory repair of wasted support bracket.
Accommodation/Occupational Safety › Refrigeration (stores) › General
Issued 5 March 2018
Resolved
Make chill cabin door A-0 and provide escape device on inside of door.
Due 28 March 2018
Resolved 18 April 2018
Resolution: Door made properly to A-0 boundary with escape device.
Electrical › Electrical Distribution System (service) › Ground Detection
Issued 5 March 2018
Resolved
Demonstrate proper operation of 24V ground detection panel.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 28 March 2018
Resolved 30 April 2018
Resolution: Received documentation from vessel rep that ground lights are properly working.
Fire Fighting › Structural - A Class Divisions › Open Deck Spaces
Issued 5 March 2018
Resolved
Place insulation in overhead of forepeak where missing.
Due 28 March 2018
Resolved 18 April 2018
Resolution: Required insulation installed in forepeak.
Fire Fighting › Fixed Fire Detection System › Power Supply
Issued 5 March 2018
Resolved
Replace voltmeter for fire detection system batteries.
Due 28 March 2018
Resolved 18 April 2018
Resolution: Voltmeter replaced and operational.
Fire Fighting › Automatic Sprinkler System › Pressure Tank
Issued 5 March 2018
Resolved
Replace gasket on inspection hole and sight glass on sprinkler system water tank.
Due 28 March 2018
Resolved 18 April 2018
Resolution: Gasket and sight glass replaced on water tank.
Fire Fighting › Automatic Sprinkler System › Pressure Gauges
Issued 5 March 2018
Resolved
Replace gauge on air compressor for sprinkler tank.
Due 28 March 2018
Resolved 18 April 2018
Resolution: Pressure gauge replaced on air compressor.
Fire Fighting › Structural - A Class Divisions › Fire Doors
Issued 5 March 2018
Resolved
Prove proper ability of fire doors to close that were inoperable at time of inspection.
Due 28 March 2018
Resolved 18 April 2018
Resolution: Witnessed proper closure of fire doors.
Electrical › Lighting (emergency) › Lighting Fixture
Issued 5 March 2018
Resolved
Replace emergency light in forward section of galley.
Due 28 March 2018
Resolved 18 April 2018
Resolution: Emergency light replaced in galley.
Electrical › Lighting (emergency) › Lighting Fixture
Issued 5 March 2018
Resolved
Replace exit sign in STBD female head.
Due 28 March 2018
Resolved 18 April 2018
Resolution: Exit sign replaced.
Fire Fighting › Grease Extraction Hood › General
Issued 5 March 2018
Resolved
Prove proper operation of galley hood fire extinguishing system. Until galley hood suppression system is fully operational, provide 01 fire watch for each deck in galley when equipment that has cooking surfaces with temperatures >250F are in use.
Due 28 March 2018
Resolved 18 April 2018
Resolution: Witnessed proper testing of galley hood fire extinguishing system after installation.
Engineering › Diesel Engine (propulsion-electric) › Gear/Clutch Starter (hydraulic)
Issued 15 December 2017
Resolved
Vell;s port Z drive will not go into neutral, must not use this engine during operation unless needed for an emergency until fixed to normal operations, tech report received and proper operations verified by Coast Guard Marine inspector.
Due 16 December 2017
Resolved 20 December 2017
Resolution: See Narrative.
Engineering › Diesel Engine (propulsion/auxiliary-electric) › Gear/Clutch Starter (hydraulic)
Issued 15 December 2017
Resolved
Vessel must have a plan/other vessels in stby while operating in this condition and will not be allowed to operate with passengers on Saturday until cleared by CGMI.
Due 16 December 2017
Resolved 20 December 2017
Resolution: See Narrative.
Fire Fighting › Fixed Fire Detection System › Smoke Detectors
Issued 5 January 2017
Resolved
Smoke detector in the stbd aft female head is inoperable. Replace batteries in smoke detector.
Due 5 February 2017
Resolved 15 February 2017
Resolution: Operator installed proper batteries
Deck/Cargo › Holds/Tanks › Watertight Door
Issued 5 January 2017
Resolved
The watertight door indicator at frames 41 and 42 for the stbd engineroom door is inoperable.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 27 January 2017
Fire Fighting › Structural - A Class Divisions › Doors
Issued 5 January 2017
Resolved
Port amidships fire safety door does not close upon activation. Ensure door properly closes.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 27 January 2017
Fire Fighting › Ventilation Systems › Exhaust Ducts (Galley Ranges)
Issued 5 January 2017
Resolved
Stbd outboard ovens in galley are not labeled. Label accordingly.
Due 5 February 2017
Resolved 27 January 2017
Fire Fighting › Ventilation Systems › Exhaust Ducts (Galley Ranges)
Issued 5 January 2017
Resolved
Grease hood is leaking grease; clean hood properly.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 27 January 2017
Engineering › Non-conventional Propulsion/Steering › Bearing (z-drive)
Issued 5 January 2017
Resolved
Write testing procedures for all alarms installed on z-drive.
Due 5 February 2017
Resolved 3 May 2017
Resolution: Vessel has PSTPs dated 02/24/2015 and provided a copy to attending USCG MI.
Fire Fighting › Miscellaneous Items › Paint/Flammable Liquid Lockers
Issued 5 January 2017
Resolved
Remove aresol paint cans from port engine room.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 27 January 2017
Construction/Loadline › Penetrations › Gasket
Issued 5 January 2017
Resolved
Replace both escape hatch gaskets for port and stbd engine room.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 27 January 2017
Electrical › Electric Generation Source (service) › Ground Detection
Issued 5 January 2017
Resolved
Fix ground on port side transformer and provide a report from a licensed electrician.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 3 May 2017
Resolution: Vessel has rectified deficiency, identified faulty equipment in galley.
Communications › Alarms/Indicators › Bilge Alarm
Issued 5 January 2017
Resolved
Repair forward bilge alarm in the galley.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 27 January 2017
Fire Fighting › Means of Escape › Escape Route Signs
Issued 5 January 2017
Resolved
Place tape on arrows of exit sign in aft head space.
Due 5 February 2017
Resolved 3 May 2017
Resolution: Wittnessed escape signage properly indicating route of egress.
Lifesaving › Lifebuoys › Buoyant Lifeline
Issued 5 January 2017
Resolved
Replace grab line on all ring buoys.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 27 January 2017
Lifesaving › Lifejacket/PFD (General) › Quantity
Issued 5 January 2017
Resolved
Passenger and crew limited to 356 passengers until damaged life jackets are replaced.
Action required: 705 - Other - as specified
Resolved 3 May 2017
Resolution: Vessel has provide proof of properly labeled and installed life jackets.
Lifesaving › Lifebuoys › Self-igniting Lights
Issued 5 January 2017
Resolved
Replace battery and light on ring life buoy float light.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 27 January 2017
Engineering › Steering Gear System › Hydraulic Hose
Issued 18 May 2016
Resolved
Make repair in kind to H/O return line iwo of Port Z-Drive service tank. Submit technician report to local [name withheld] All repairs must be made to the satisfaction of the attending Marine Inspector.
Condition: Design Flaw
Action required: 701 - Prior to carriage of passengers/cargo
Due 26 May 2016
Resolved 19 May 2016
Resolution: Received tech report for cause and proper install
Fire Fighting › Structural - A Class Divisions › Fire Doors
Issued 20 January 2016
Resolved
Centerline fire screen doors do not latch. Prove proper operation of FSD.
Action required: 705 - Other - as specified
Due 3 February 2016
Resolved 9 February 2016
Resolution: Replaced hardware to FSD, conducted operational test.
Fire Fighting › Fire Hoses › Condition
Issued 20 January 2016
Resolved
Aft fire hose holed. Replace aft fire hose.
Action required: 705 - Other - as specified
Due 3 February 2016
Resolved 9 February 2016
Resolution: Installed new fire hose.
Accommodation/Occupational Safety › Medical/First Aid › Medicine Chest
Issued 20 January 2016
Resolved
First aid kit missing numerous items. Provide first aid kit supplied IAW 160.041
Action required: 705 - Other - as specified
Due 3 February 2016
Resolved 9 February 2016
Resolution: Restocked first aid kit with proper, un-expired supplies.
Fire Fighting › Means of Escape › Escape Route Signs
Issued 20 January 2016
Resolved
Labels on emergency escap hatche FWD secondary means of escape FWD storage, 2 in galley labels not clearly legible. Label IAW 122.606
Action required: 705 - Other - as specified
Due 3 February 2016
Resolved 9 February 2016
Resolution: Properly labeled emergency exits
Documentation › Certificates/Documents › Proof of Consortium Enrollment (DAPI)
Issued 20 January 2016
Resolved
Provide employee enrollment list for DAPI
Action required: 705 - Other - as specified
Due 3 February 2016
Resolved 9 February 2016
Resolution: provided employee enrollment list
Electrical › Electrical Distribution System (service) › Ground Indicator
Issued 20 January 2016
Resolved
Ground indicated on 75KVAammeter and 112 1/2 kva and 170 kva TXFR lights. Identify source of grounds and eliminate.
Action required: 705 - Other - as specified
Due 3 February 2016
Resolved 9 February 2016
Resolution: vessel eliminated grounds as verified on ground detection meters.