13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Gauges, thermometers, etc
Issued 22 January 2026
No resolution recorded
The following systems must be equipped with gauges at the machinery location: auxiliary generator engine lubricating oil pressure and auxiliary generator engine RPM.
SSDG #1 oil pressure gauge was broken.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 5 February 2026 — due date passed with no resolution recorded
07 - Fire Safety › N/A - No Subsystem › Fire pumps and its pipes
Issued 22 January 2026
No resolution recorded
A fixed fire pump must be capable of: Delivering water simultaneously from the two highest hydrants, or from both branches of the fitting if the highest hydrant has a Siamese fitting, at a pitot-tube pressure of at least 50 pounds per square inch (psi), and a flow rate of at least 80 gallons per minute (gpm).
Due to extreme cold was not able to test fire pump without possibly causing damage to lines. Will reattend vessel withing 30 days to test fire pump.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 22 February 2026 — due date passed with no resolution recorded
11 - Life Saving Appliances › N/A - No Subsystem › Inflatable liferafts
Issued 5 November 2024
Resolved
Each liferaft must be arranged for float free launching. Painter is not connected to hyrdostatic release.
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Due 6 November 2024
Resolved 7 November 2024
Resolution: Painter line was attached to HRU; all sat.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 5 November 2024
Resolved
A 40 lb portable fire extinguisher must be stowed near flammable liquid storage locker. Fire extinguisher is not stowed near storage locker.
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 20 November 2024
Resolved 20 December 2024
Resolution: New extinguisher installed.
11 - Life Saving Appliances › N/A - No Subsystem › Distress flares
Issued 5 November 2024
Resolved
Pyrotechnic distress signals must be stowed in a portable container clearly marked with 0.5 inch letters "Distress Signals". Container is not marked.
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 20 November 2024
Resolved 7 November 2024
Resolution: Container marked. All sat.
09 - Working and Living Conditions › 092 - Working Conditions › Other (accident prevention)
Issued 5 November 2024
Resolved
Existing vessel must meet the pilot house alerter requirements in 46 CFR 143.450 no later than 5 years after issuance of first COI. Pilot house alerter system is not installed or a 2nd person has not been required in the pilothouse.
07NOV: See letter in docs. Company will add a second person until system is install. Vessel allowed to depart with the additional member on board while they wait for system installation.
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Due 6 November 2024
Resolved 7 August 2025
Resolution: Second person used as an alternative. Changed COI until alerter system is installed.
08 - Alarms › N/A - No Subsystem › Emergency signal
Issued 5 November 2024
Resolved
Each towing vessel must have a reliable means to provide notification when an emergency condition exists. High bilge level alarms are required. High bilge level alarms are not functioning.
Condition: Invalid
Action required: 17 - Rectify deficiencies prior to departure
Due 5 November 2024
Resolved 7 November 2024
Resolution: Tested bilge alarms. Crew was able to repair original alerting system on the bridge (wire connection issue); however, a new bilge alarm system was ordered and will be installed shortly after arrival.
08 - Alarms › N/A - No Subsystem › General alarm
Issued 5 November 2024
Resolved
Each towing vessel must be fitted with a general alarm that has a supplemental flashing red light in eingine room. Flashing red light is not functional in engine room.
Condition: Invalid
Action required: 16 - Rectify deficiencies w/in 14 days
Due 18 November 2024
Resolved 7 November 2024
Resolution: Renewed original light was LED; conducted test, all sat.
09 - Working and Living Conditions › 092 - Working Conditions › Cleanliness of engine room
Issued 5 November 2024
Resolved
Paints or flammable or combustible products must be stored in a storage room or cabinet. Flammable material to include welding gases are being stored in the engine room.
Condition: Invalid
Action required: 16 - Rectify deficiencies w/in 14 days
Due 18 November 2024
Resolved 20 December 2024
Resolution: Materials Removed.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 5 November 2024
Resolved
The fire hose must be capable of providing a solid stream and spray pattern. The fie hose burst while in use. Vessel replaced with spare hose.
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 5 November 2024
Resolved 5 November 2024
Resolution: Vessel had additiional new hoses on board. Tested new hose, all sat.
11 - Life Saving Appliances › N/A - No Subsystem › Launching arrangements for survival craft
Issued 3 November 2023
Resolved
Hydrostatic release of liferaft was inaccurately installed.
Condition: Improper Installation
Action required: 10 - Deficiency Rectified
Due 3 November 2023
Resolved 3 November 2023
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 3 November 2023
Resolved
Missing light on pfd.
Condition: Improper Installation
Action required: 10 - Deficiency Rectified
Due 3 November 2023
Resolved 3 November 2023
11 - Life Saving Appliances › N/A - No Subsystem › Operational readiness of lifesaving appliances
Issued 3 November 2023
Resolved
Floating waterlight on port side ring life buoy had incorrect battery installation. Replaced battery prior to departure.
Condition: Improper Installation
Action required: 10 - Deficiency Rectified
Due 3 November 2023
Resolved 3 November 2023
05 - Radio Communications › N/A - No Subsystem › Satellite EPIRB 406MHz/1.6GHz
Issued 11 January 2023
Resolved
EPIRB, registration expired. Provide valid EPIRB registration as required by 46 CFR 141.380.
Condition: Improper/Lack of Maintenance
Action required: 60 - Rectify deficiencies prior to movement
Due 11 January 2023
Resolved 11 January 2023
Resolution: Copy provided pdf file reflecting the EPIRB was updated through NOAA's web site.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 11 January 2023
Resolved
Water light, on pilot house stbd side ring buoy not operational. Repair as required by 46 CFR 141.360.
Condition: Improper/Lack of Maintenance
Action required: 60 - Rectify deficiencies prior to movement
Due 11 January 2023
Resolved 11 January 2023
Resolution: Discrepancy corrected and cleared prior to CG MI’s departure.
15 - Safety Management Systems (ISM) › N/A - No Subsystem › Company verification, review and evaluation
Issued 11 January 2023
Resolved
Documentation not available to verify company complaint with DOT Chemical Testing. Make Chemical testing documentation available to CG MI for examination, as required by 46 CFR Part 16.
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 11 February 2023
Resolved 17 March 2023
Resolution: Documentation provided by company rep [name withheld] reflecting company in full compliance with 46 CFR Part 16. Requirement cleared.
01 - Certificates & Documentation › 013 - Documents › Log-books/compulsory entries
Issued 11 January 2023
Resolved
Training Records were not available to verify compliance. Make training records available to CG MI as required by 46 CFR 140.905
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 11 February 2023
Resolved 7 February 2023
Resolution: Documentation provided by company rep [name withheld] reflecting company in full compliance, requirement cleared.
01 - Certificates & Documentation › 013 - Documents › Log-books/compulsory entries
Issued 11 January 2023
Resolved
Observed numerous trip entries in vessels official log book that were missing Masters/Captains signature. 46 USC 11.302 requires the vessel Master/Captain to sign the official log and entries. Have Masters review and sign where missing. * If this discrepancy continues, attending CG MI will recommend a civil penalty be issued.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 11 February 2023
Resolved 7 February 2023
Resolution: Observed discrepaince corrected.
11 - Life Saving Appliances › N/A - No Subsystem › Distress flares
Issued 11 January 2023
Resolved
Seven Flares expired. Only 5 unexpired flares onboard. Obtain seven new CG approved flares as required by 46 CFR 141.375 Discrepancy to be corrected before vessel movement. Vessel rep purchased 12 new CG approved flares.
Condition: Improper/Lack of Maintenance
Action required: 60 - Rectify deficiencies prior to movement
Due 11 January 2023
Resolved 11 January 2023
Resolution: Text with photos to CG MI, reflecting new approved flares purchased. requirement resolved and cleared on 11JAN2023 at 1434 CST
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 11 January 2023
Resolved
Observed two ring buoys on the stbd main deck, and stbd bridging wing, tears in ring body, worn, and missing proper amount of retro-reflective tape. Renew both ring buoys as required by 46 CFR 141.360
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 11 February 2023
Resolved 6 February 2023
Resolution: Company rep provided an e-mail with statement and photo's reflecting two ring buoys were renewed.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 14 April 2022
Resolved
Upon boarding the vessel it was determined that 835s previously issued on 4NOV21 classified as "prior to departure" had not been cleared to the satisfaction of an attending CG Marine Inspector prior to the vessel departing Escanaba, MI and transiting to Sturgeon Bay, WI on 13APR22 to conduct commercial towing service.
Condition: Placed in Improper Service
Action required: 17 - Rectify deficiencies prior to departure
Due 14 April 2022
Resolved 14 April 2022
Resolution: All previously issued 835s were verified as having being completed. Vessel cleared to sail.
11 - Life Saving Appliances › N/A - No Subsystem › Distress flares
Issued 15 November 2021
Resolved
12 Flares required only 6 onboard. Obtain 6 additional handheld flares IAW 46 CFR 141.375(a)
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 15 December 2021
Resolved 15 April 2022
11 - Life Saving Appliances › N/A - No Subsystem › Inflatable liferafts
Issued 15 November 2021
Resolved
6-man life raft due for annual servicing. Have life raft serviced IAW 46 CFR 141.235
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 15 December 2021
Resolved 15 April 2022
11 - Life Saving Appliances › N/A - No Subsystem › Launching arrangements for survival craft
Issued 15 November 2021
Resolved
Renew life raft hydrostatic release IAW 46 CFR 141.235
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 15 December 2021
Resolved 15 April 2022
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 15 November 2021
Resolved
Missing. Fit the vessel with 9 adult life jackets IAW 46 CFR 141.340(a)
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Due 15 December 2021
Resolved 15 April 2022
11 - Life Saving Appliances › N/A - No Subsystem › Immersion suits
Issued 15 November 2021
Resolved
Missing. Fit vessel with 6 immersion suits IAW 46 CFR 141.350(a)(1)
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Due 15 December 2021
Resolved 15 April 2022
07 - Fire Safety › N/A - No Subsystem › Remote Means of control (opening,pumps,ventilation,etc.) Machinery spaces
Issued 15 November 2021
Resolved
Install remote Fuel Oil shut off valve for engine room heater IAW 46 CFR 143.260(c)
Condition: Placed in Improper Service
Action required: 50 - Rectify deficiencies w/in 30 days
Due 15 December 2021
Resolved 15 April 2022
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 15 November 2021
Resolved
Renew-Replace asprin and eye wash solution in 1st aid kit IAW 46 CFR 140.435
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 29 November 2021
Resolved 15 April 2022
10 - Safety of Navigation › N/A - No Subsystem › Lights, shapes, sound-signals
Issued 15 November 2021
Resolved
Noted 8 inch bell. Install 11.9 inch bell IAW 33 CFR 86.23
Condition: Placed in Improper Service
Action required: 50 - Rectify deficiencies w/in 30 days
Due 15 December 2021
Resolved 15 April 2022
05 - Radio Communications › N/A - No Subsystem › Operation/maintenance
Issued 12 November 2020
Resolved
FCC station license was expired. All towing vessels must meet the communications requirements of 33 CFR 164.72. Equipment and license must be maintained IAW 47 CFR 80.
46CFR140.715
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 13 December 2020
Resolved 9 December 2020
Resolution: sent proof of current radio station authorization
05 - Radio Communications › N/A - No Subsystem › Operation/maintenance
Issued 12 November 2020
Resolved
The Great Lakes annual inspection of radiotelephone installations was expired. Towing vessels must meet the communications requirements of 33 CFR 164.72. Equipment and license must be maintained IAW 47 CFR 80.
46 CFR 140.715
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 13 December 2020
Resolved 9 December 2020
Resolution: sent proof of current inspection
05 - Radio Communications › N/A - No Subsystem › VHF EPIRB
Issued 12 November 2020
Resolved
The EPIRB registration was expired. Each towing vessel that operates on the Great Lakes, beyond 3NM from shore must carry a CAT 1 EPIRB that meets the requirements of 47 CFR 80 and maintain valid proof of registration.
46 CFR 141.380
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 13 December 2020
Resolved 9 December 2020
Resolution: sent proof of current registration.
09 - Working and Living Conditions › 092 - Working Conditions › Personal equipment
Issued 12 November 2020
Resolved
The alcohol testing strips onboard the vessel were expired. The marine employer must have a sufficient number of alcohol testing devices readily accessible on board the vessel to determine the presence of alcohol in the system of each individual who was directly involved in the SMI.
46 CFR 4.06-15
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 13 December 2020
Resolved 9 December 2020
Resolution: sent proof of new alcohol test strips.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 12 November 2020
Resolved
The grab line on the STBD side,pilot house life buoy was deteriorated. Each life bouy carried by a towing vessel must be approved IAW 46 CFR 160.050 or 160.150.
46 CFR 141.360
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 13 December 2020
Resolved 9 December 2020
Resolution: replaced grab lines; verified with picture.
11 - Life Saving Appliances › N/A - No Subsystem › Inflatable liferafts
Issued 12 November 2020
Resolved
Painter line for the inflatable life raft was not connected to the vessel. Survival craft must be stowed IAW requirements of 46 CFR 199.130.
46 CFR 141.310
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 13 December 2020
Resolved 11 December 2020
Resolution: verified painter line properly attached via picture.
09 - Working and Living Conditions › 092 - Working Conditions › Safe means of access Shore - Ship
Issued 12 November 2020
Resolved
Vessel's work boat floor plank was rotted and the rubber covering over it was ripped up. Crew work spaces must be of adequate construction to provide for the safe accommodation of the crew.
46 CFR 144.700
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 13 December 2020
Resolved 9 December 2020
Resolution: vessel made repairs to the flooring of the work boat; verified with picture.
09 - Working and Living Conditions › 091 - Living Conditions › Electrical devices
Issued 12 November 2020
Resolved
The cover of the electrical junction box n front of the AC by crew berthing was missing. Connections and terminations must be suitable and be maintained as originally installed.
46 CFR 143.575
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 13 December 2020
Resolved 11 December 2020
Resolution: verified def rectified via picture.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 12 November 2020
Resolved
The cover of the electrical junction box on pump motor in port side, aft E/R. Connections and terminations must be suitable and be maintained as originally installed.
46 CFR 143.575
Condition: Placed in Improper Service
Action required: 50 - Rectify deficiencies w/in 30 days
Due 13 December 2020
Resolved 11 December 2020
Resolution: verified def rectified via picture.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 12 November 2020
Resolved
The light fixture in the STBD side E/R, outboard of the generators is missing the bulbs and cover. Electrical systems must function properly and minimize system failures and shock hazards.
46 CFR 143.400
Condition: Placed in Improper Service
Action required: 50 - Rectify deficiencies w/in 30 days
Due 13 December 2020
Resolved 9 December 2020
Resolution: cover replaced on light fixture; verified with picture.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 12 November 2020
Resolved
The ground detection panel for the 120V had a light extinguished. An ungrounded system must be provided with a ground detection system providing continuous indication of circuit status.
46 CFR 143.570
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 13 December 2020
Resolved 9 December 2020
Resolution: replaced the light bulb ni the ground detector display. Sent proof of proper operation via picture.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 12 November 2020
Resolved
A plastic garbage can was being used for oily rag storage in the E/R. Combustible products must not be stored in the E/R unless in a suitable container.
46 CFR 143.220
Condition: Placed in Improper Service
Action required: 10 - Deficiency Rectified
Resolved 9 December 2020
01 - Certificates & Documentation › 011 - Ships Certificates › Load Lines (including Exemption)
Issued 1 November 2019
Resolved
Vessel's Load Line required by 46 USC 5103 is expired. Vessel is prohibited from movement until the Load Line is renewed.
Condition: Invalid
Action required: 60 - Rectify deficiencies prior to movement
Resolved 12 November 2019
Resolution: ABS verified successful completion of Load Line survey.
18 - Maritime Labour Convention (Not Applicable to PSC Exams conducted in the U.S.) › N/A - No Subsystem › Other (Conditions of employment)
Issued 16 September 2019
Resolved
Company’s chemical testing program not verified. Attending CG MI to complete a Chemical Testing Program compliance audit (per USCG Commandant Audit checklist).
Condition: Invalid
Action required: 705 - Other - as specified
Due 26 September 2019
Resolved 11 December 2019
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 17 July 2019
Resolved
FCC Radio License Expired, renew/update.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 August 2019
Resolved 20 August 2019
05 - Radio Communications › N/A - No Subsystem › Operation/maintenance
Issued 17 July 2019
Resolved
Missing Great Lakes Yearly Radio Inspection. Inspect and provide report.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 August 2019
Resolved 20 August 2019
08 - Alarms › N/A - No Subsystem › Fire alarm
Issued 17 July 2019
Resolved
Remote [name withheld] indicating panel not fitted in upper pilot house, install.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 August 2019
Resolved 16 September 2019
08 - Alarms › N/A - No Subsystem › General alarm
Issued 17 July 2019
Resolved
Install a General Alarm switch in the upper pilot house.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 August 2019
Resolved 16 September 2019
04 - Emergency Systems › N/A - No Subsystem › Means of communication between safety centre and other control stations
Issued 17 July 2019
Resolved
Whistle not operational in the upper Pilot House, repair.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 17 August 2019
Resolved 16 September 2019
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 17 July 2019
Resolved
Vessels Stern Name Board missing, install.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 17 July 2019
Resolved 17 July 2019
Resolution: name board installed prior to completion of the inspection.
08 - Alarms › N/A - No Subsystem › General alarm
Issued 17 July 2019
Resolved
Label engine room general alarm bell.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 August 2019
Resolved 16 September 2019
01 - Certificates & Documentation › 013 - Documents › Shipboard working arrangements
Issued 17 July 2019
Resolved
Provide fuel oil transfer procedures.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 August 2019
Resolved 16 September 2019
02 - Structural Conditions › N/A - No Subsystem › Marking of IMO number
Issued 17 July 2019
Resolved
Missing and add NO before the vessels official number.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 August 2019
Resolved 16 September 2019
11 - Life Saving Appliances › N/A - No Subsystem › Stowage and provision of liferafts
Issued 17 July 2019
Resolved
Missing, install an approved survival craft - Inflatable life raft.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 August 2019
Resolved 16 September 2019
Resolution: Observed 01 six man SOLAS B Park inflatable life raft installed.
10 - Safety of Navigation › N/A - No Subsystem › Magnetic compass
Issued 17 July 2019
Resolved
Missing and install an illuminated magnetic compass in the upper operating station. 46 CFR 140.725
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 August 2019
Resolved 16 September 2019
01 - Certificates & Documentation › 013 - Documents › Fire safety operational booklet
Issued 17 July 2019
Resolved
Missing, Post Emergency station bill at upper operating station.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 August 2019
Resolved 16 September 2019
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 17 July 2019
Resolved
Removed aluminum paint locker, install an approved or acceptable steel paint locker.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 August 2019
Resolved 16 September 2019
11 - Life Saving Appliances › N/A - No Subsystem › Rescue boats
Issued 17 July 2019
Resolved
Rescue Boat, name not properly marked, label. 46 CFR Part 141.315 and 46 CFR 199.176
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 August 2019
Resolved 16 September 2019
11 - Life Saving Appliances › N/A - No Subsystem › Immersion suits
Issued 17 July 2019
Resolved
Provide an approved immersion suit for each crewmember.
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Due 17 July 2019
Resolved 17 July 2019
Resolution: Immersion Suits were installed onboard the vessel prior to CG MI departure.
01 - Certificates & Documentation › 013 - Documents › Log-books/compulsory entries
Issued 17 July 2019
Resolved
Company failed to fully fill out various forms as required by companies Towing Vessel Record (TVR) Subchapter Compliance Management System (Maritime Compliance International, LLC Publication). Forms list include operations, Survey’s, Inspections, & training. Applicable forms include O-1 thru 0-13, S- thru S-11, & T-1 thru T-3, must be filled out, complete and re-verified by attending CG Marine Inspector. 46 CFR 140.500
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 August 2019
Resolved 16 September 2019
01 - Certificates & Documentation › 013 - Documents › Log-books/compulsory entries
Issued 17 July 2019
Resolved
Official log book incomplete, failed to reflect all required tests and checks. O/O to obtain and fit vessel with a Towing vessel log book.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 August 2019
Resolved 16 September 2019
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 17 July 2019
Resolved
Excessive flammable/combustible containers observed in the engine room. Remove, limited to one 5 gallon container or one 55 gallon drum.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 August 2019
Resolved 16 September 2019
01 - Certificates & Documentation › 013 - Documents › Conformance Test Report
Issued 17 July 2019
Resolved
Records unavailable reflecting serving and testing of the engine room fixed CO2 system, including verification of the CO2 cylinder weight and testing of the CO2 systems pressure switches
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 August 2019
Resolved 16 September 2019
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 17 July 2019
Resolved
Fire hoses not attached to fire plugs and nozzles missing. Attach and fit with approved firefighting nozzles.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 17 July 2019
Resolved 17 July 2019
Resolution: Hoses and nozzles installed prior to CG MI departure
08 - Alarms › N/A - No Subsystem › Fire alarm
Issued 17 July 2019
Resolved
Missing, install Smoke Detectors in the berthing and accommodation spaces.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 August 2019
Resolved 16 September 2019
08 - Alarms › N/A - No Subsystem › Engineers' alarm
Issued 17 July 2019
Resolved
Provide engineering emergency summary alarm in the upper pilot house.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 August 2019
Resolved 16 September 2019
Resolution: Requirement rescinded, as engine room manned.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 17 July 2019
Resolved
Observed several electrical wires not properly dead ended. Properly terminate dead end wires in the berthing and accommodation spaces. 46 CFR 143.400
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 August 2019
Resolved 16 September 2019
10 - Safety of Navigation › N/A - No Subsystem › Navigation bridge visibility
Issued 17 July 2019
Resolved
Hair dryer used to defog pilot house windows. Fit pilot house windows with proper defogger.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 August 2019
Resolved 16 September 2019
05 - Radio Communications › N/A - No Subsystem › Satellite EPIRB 406MHz/1.6GHz
Issued 17 July 2019
Resolved
EPIRB outdated/expired. Fit vessel with a valid EPIRB. *Vessel limited to within 3 miles of shore until corrected & verified by CG MI.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 August 2019
Resolved 16 September 2019
05 - Radio Communications › N/A - No Subsystem › Satellite EPIRB 406MHz/1.6GHz
Issued 17 July 2019
Resolved
EPIRB hydro release outdated, renew. *Vessel limited to within 3 miles of shore until corrected & verified by CG MI.
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 August 2019
Resolved 16 September 2019
10 - Safety of Navigation › N/A - No Subsystem › Automatic Identification System (AIS)
Issued 10 September 2018
Resolved
Vessel is transmitting inaccurate IMO number, Call sign, and draft of the vessel.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 10 October 2018
Resolved 6 November 2018
Resolution: VIVS database is showing no discrepancies.
Electrical › Lighting (emergency)
Issued 10 June 2003
Resolved
Current system requires that each light be turned on manually, recommended installing new emergency lighting system or retrofit exsisting system that automatically operates after loss of power.
Condition: Improper Installation
Action required: 705 - Other - as specified
Resolved 10 June 2003
Fire Fighting › Portable CO2 Fire Extinguisher › Mounting Bracket
Issued 10 June 2003
Resolved
Fire extinguisher not mounted, aft area of engine room.
Condition: Unknown
Action required: 705 - Other - as specified
Resolved 10 June 2003
Resolution: Mounted fire Extinguisher
Lifesaving › Inflatable Liferafts
Issued 10 June 2003
Resolved
liferaft not installed properly to allow float free.
Condition: Improper Installation
Action required: 705 - Other - as specified
Resolved 10 June 2003
Resolution: Liferafts have been inspected and are now installed properly.
Lifesaving › Lifejacket/PFD (General)
Issued 10 June 2003
Resolved
Lifejackets not marked with vessels name. LEGACY COMPONENT DESC: Marking
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Resolved 10 June 2003
Resolution: Marked all lifejackets with vessel name.
Lifesaving › Lifejacket/PFD (General) › Lights
Issued 10 June 2003
Resolved
Lights missing on lifejackets.
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 31 July 2012
Resolved 18 July 2012
Operations/Management › Equipment Service/Testing › EPIRB
Issued 10 June 2003
Resolved
EPIRB out dated.
Condition: Unknown
Action required: 705 - Other - as specified
Resolved 10 June 2003
Resolution: EPIRB replaced with new unit.
Operations/Management › Pollution › Compliance with Transfer Procedures
Issued 10 June 2003
Resolved
Fuel oil transfer procedures outdated.
Action required: 705 - Other - as specified
Resolved 10 June 2003
Resolution: Fuel oil transfer procedures updated.
Navigation › Collision/Grounding Avoidance › Searchlight
Issued 10 June 2003
Resolved
Bulb burned out.
Condition: Unknown
Action required: 705 - Other - as specified
Resolved 10 June 2003
Resolution: Replaced bulb.