Records from 1989 to 2019. Most recent: inspection, 8 June 2019.
Fire Fighting › Fixed Fire Detection System › Heat Detectors
Issued 21 July 2015
Resolved
Heat detectors not operating in the Port & STBD engine rooms and galley.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 24 July 2015
Resolution: All heat detectors properly working.
Accommodation/Occupational Safety › Occupational Safety › Guards for Exposed Hazards
Issued 21 July 2015
Resolved
P/S Main engines and generators missing guards for rotating machinery.
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Resolved 24 July 2015
Resolution: All guards added to rotating machiney.
Pollution Prevention/Response › Prevention Equipment › Fixed Containment
Issued 21 July 2015
Resolved
P/S gear stuffing box needs protective shield from above. To eliminate possible oil in the containment.
Condition: Improper Installation
Due 28 July 2015
Resolved 24 July 2015
Resolution: Protective shield added.
Fire Fighting › Fire Hoses › Condition
Issued 26 June 2014
Resolved
Fire hose burst at connection to fire main valve.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 1 July 2014
Fire Fighting › Nozzles › Condition
Issued 26 June 2014
Resolved
Fire nozzle frozen. Inoperable.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 1 July 2014
Engineering › Diesel Engine (auxiliary) › Piping (exhaust)
Issued 26 June 2014
Resolved
Repair exhaust leak on Stbd generator.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 1 July 2014
Accommodation/Occupational Safety › Medical/First Aid › Medicine Chest
Issued 26 June 2014
Resolved
Provide First Aid Kit.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 1 July 2014
Communications › Alarms/Indicators › General Alarm
Issued 26 June 2014
Resolved
Show operation of Tilt Alarm
Action required: 17 - Rectify deficiencies prior to departure
Due 2 July 2014
Resolved 26 June 2014
Fire Fighting › Fire Hoses › Material
Issued 13 December 2011
Resolved
Replace submersible pump discharge fire hose.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 6 February 2012
Resolution: Renewed fire hose.
Lifesaving › Hand Flares › Quantity
Issued 13 December 2011
Resolved
Missing one hand flare.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 31 January 2012
Resolution: Replaced missing flare.
Engineering › Diesel Engine (propulsion-reduction gear) › Piping (exhaust)
Issued 13 December 2011
Resolved
Install exhaust lagging on the STBD MDE and the Port SSDG.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 30 January 2012
Resolution: Exhaust lagging was installed.
Accommodation/Occupational Safety › Heating › Metal Protection
Issued 12 October 2011
Resolved
Port side engine exhaust stack holed under support brace (rusted through)
Action required: 705 - Other - as specified
Resolved 22 November 2011
Resolution: Repaired.
Electrical › Electric Supply System (service) › Battery Installation
Issued 11 October 2011
Resolved
Batteries for main engine sitting on deck not in container - place in an appropriate battery box
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Battery boxes installed.
Construction/Loadline › Penetrations › Pipe Flange
Issued 11 October 2011
Resolved
Deck plate above port engine has a pipe penetration that is open and not connected to anything. Crop and renew plate
Action required: 705 - Other - as specified
Resolved 27 January 2012
Resolution: Pipe was capped.
Engineering › Lubricating Oil Storage/Transfer System › Piping
Issued 11 October 2011
Resolved
Fuel piping to port generator (located below electrical switchboard) bracket broken and cloth used to reduce rubbing of pipe on metal. Install proper bracket - remove soiled rags.
Action required: 705 - Other - as specified
Resolved 27 January 2012
Resolution: C/R broken bracket and renewed as original.
Electrical › Electric Generation Source (service) › Metallic Enclosure/Frame
Issued 11 October 2011
Resolved
Port switchboard - cap all unused electrical conduit holes.
Action required: 705 - Other - as specified
Resolved 22 November 2011
Resolution: Repaired.
Electrical › Electric Generation Source (service) › Metallic Enclosure/Frame
Issued 11 October 2011
Resolved
All outlets in engine room must be approved for a wet enviroment
Action required: 705 - Other - as specified
Resolved 27 January 2012
Resolution: Approved outlets installed.
Engineering › Generator (propulsion/auxiliary-electric) › System Grounding
Issued 11 October 2011
Resolved
Port generator not welded to the skid and/or deck. Renew all welds, it appears generator is a new installation. Unknown if deck removal was approved/inspected by USCG.
Action required: 705 - Other - as specified
Resolved 27 January 2012
Resolution: Welds were grinded out and re-welded.
Deck/Cargo › Ballast › Piping
Issued 11 October 2011
Resolved
Multiple locations of piping leaking evident throughout vessel. Crop and renew. Perform a function test to the satisfaction of USCG
Action required: 705 - Other - as specified
Resolved 27 January 2012
Resolution: Piping has been replaced.
Electrical › Electric Supply System (service) › Cable
Issued 11 October 2011
Resolved
Remove all dead end wiring in engine room.
Action required: 705 - Other - as specified
Resolved 27 January 2012
Resolution: Dead end wires were removed.
Deck/Cargo › Ballast › Pumps
Issued 11 October 2011
Resolved
Ballast pump in port engine room not mounted on support bracket (2 inch gap) pump supported only through above piping - fix support bracket
Action required: 705 - Other - as specified
Resolved 27 January 2012
Resolution: Pump has been mounted correctly.
Engineering › Fuel Oil Storage/Transfer System › Hose
Issued 11 October 2011
Resolved
Fuel lines on port generator not SAE J-1492 approved lines. Replace with appropriate fuel lines
Action required: 705 - Other - as specified
Resolved 27 January 2012
Resolution: Fuel lines were replaced with SAE 1942.
Construction/Loadline › Hull › Keel
Issued 11 October 2011
Resolved
Port shaft in rudder compartment - RED HAND . Crop and renew as original.
Action required: 705 - Other - as specified
Resolved 6 February 2012
Resolution: C/R with an insert.
Construction/Loadline › Hull › Stiffener
Issued 11 October 2011
Resolved
Port rudder post supports wasted / crop and renew as original
Action required: 705 - Other - as specified
Resolved 27 January 2012
Resolution: Rudder post supports were C/R.
Construction/Loadline › Penetrations › Pipe Flange
Issued 11 October 2011
Resolved
Port rudder compartment piping soft patch - crop and renew. 90% of all piping in port rudder compartment wasted.
Action required: 705 - Other - as specified
Resolved 27 January 2012
Resolution: Piping was C/R.
Lifesaving › Launching Appliances › Lines
Issued 22 September 2011
Resolved
Rescue boat lifting device was made from three strand white synthetic line. Vessel to provide correct lifting harness that has been weight tested IAW D8 rescue boat policy letter.
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Resolved 27 January 2012
Resolution: Synthetic lifting device was replaced with a wire rope lifting device.
Construction/Loadline › Structures › Superstructure
Issued 22 September 2011
Resolved
Aft leg approx 20 feet from the top has sustained damage resulting in area that causes excessive backlash between gear box pinion and leg rack. Crop and renew area.
Condition: Damaged By Earlier Event
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Aft leg was repaired.
Construction/Loadline › Hull › Hull Plating
Issued 22 September 2011
Resolved
Galley deck near port door has an illegal doubler installed. Renew with proper insert.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Proper insert was installed.
Navigation › Collision/Grounding Avoidance › Navigation Lights
Issued 16 September 2011
Resolved
Fwd masthead light was inop.
Condition: Damaged By Earlier Event
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Repaired.
Accommodation/Occupational Safety › Occupational Safety › Tripping/Falling Hazard
Issued 16 September 2011
Resolved
Washer and Dryer that were located on the pilothouse deck were not secured.
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Both were secured.
Accommodation/Occupational Safety › Occupational Safety › Tripping/Falling Hazard
Issued 16 September 2011
Resolved
Stbd pilothouse deck paint locker was not secured.
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Paint locker was placed on main deck and secured.
Construction/Loadline › Structures › Trunk
Issued 16 September 2011
Resolved
Engineroom port ventilation trunk had a wasted through hole.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Repaired.
Accommodation/Occupational Safety › Sleeping Accommodations › Berth
Issued 16 September 2011
Resolved
A main deck port and a fwd window in the crew accommodation space were broken.
Condition: Damaged By Earlier Event
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Replaced.
Electrical › Lighting (service) › Lighting Fixture
Issued 16 September 2011
Resolved
Port maindeck light explosion proof cover was cracked.
Condition: Damaged By Earlier Event
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Replaced.
Fire Fighting › Fire Hoses › Condition
Issued 16 September 2011
Resolved
Submersible fire pump discharge hose damaged. Hose near the pump was bent 90 degrees resulting in damage to the outer core and inner wire support.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 27 January 2012
Resolution: Hose renewed.
Fire Fighting › Portable Dry Chemical Fire Extinguisher › Mounting Bracket
Issued 16 September 2011
Resolved
Port E/R extinguisher was installed with a hook style mounting bracket. Incorrect for marine type use.
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Proper bracket installed.
Engineering › Diesel Engine (propulsion-reduction gear) › Block
Issued 16 September 2011
Resolved
Port main diesel engine was leaking excessively. Noted several oil absorbent rags placed in areas of engine to collect oil. identify and repair leaks.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Leaks were corrected.
Engineering › Lubricating Oil Service System › Hose
Issued 16 September 2011
Resolved
Port E/R flex hose had a hydraulic leak that was wrapped in rags.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Replaced.
Electrical › Electrical Distribution System (service) › Switchboard
Issued 16 September 2011
Resolved
Electrical matting was missing for both switchboards.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Provided.
Engineering › Lubricating Oil Service System › Hose
Issued 16 September 2011
Resolved
Port E/R hydraulic manifold contained a melted flexible hose exposing the inner metal braid.
Condition: Damaged By Earlier Event
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Replaced.
Accommodation/Occupational Safety › Potable Water System › General
Issued 16 September 2011
Resolved
Hot water tank had a relief valve that relieved at eye level. Required valve to be piped to bilge.
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Relief valve piped to bilge.
Fire Fighting › Ventilation Systems › Duct Hatches
Issued 16 September 2011
Resolved
Engine room vent closures were not labeled "Close incase of fire".
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Labeled.
Fire Fighting › Remote Fuel Shutoff › General
Issued 16 September 2011
Resolved
Port and Stbd remote fuel cut off valves were not labeled on main deck.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Labeled.
Lifesaving › Lifebuoys › Markings (ship name/port)
Issued 16 September 2011
Resolved
Life ring stenciling was worn
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Stenciling renewed.
Navigation › Piloting/Steering › Coast Guard Light List
Issued 16 September 2011
Resolved
Vessel's coast pilot and light list were 2010 edition. Required 2011.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: 2011 editions were onboard.
Documentation › Certificates/Documents › Certificate of Documentation (CG-1270)
Issued 16 September 2011
Resolved
[withheld — contains personal information; the deficiency system, dates, and resolution status are shown above]
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Valid COD provided.
Documentation › Manuals/Policy Documentation › Stability Instructions
Issued 16 September 2011
Resolved
Vessel's operation manual was not updated by new owners. Required vessel to update.
Condition: Invalid
Action required: 17 - Rectify deficiencies prior to departure
Resolved 25 September 2012
Deck/Cargo › Cargo Transfer (solid) › General
Issued 16 September 2011
Resolved
Vessel's annual crane inspection report did not contain a year. Document had only month and day. Provide annual report.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Report was from current year.
Electrical › Electrical Distribution System (service) › Panelboard
Issued 16 September 2011
Resolved
Breaker box panel under pilothouse console did not have a cover. Install cover.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 27 January 2012
Resolution: Cover installed.
Documentation › Markings/Placards › Lifejacket Placard
Issued 16 September 2011
Resolved
Vessel had two different types of lifejackets onboard but only one set of donning instructions.
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: All lifejackets were one style and instructions were provided.
Lifesaving › Lifefloat › Float Free
Issued 16 September 2011
Resolved
Found billy pugh basket on top of lifefloat preventing it from floating free.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Lifefloat placed in float free condition.
Navigation › Collision/Grounding Avoidance › Navigation Lights
Issued 16 September 2011
Resolved
Nav light screens had white overspray. Required screens to be painted.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Re painted.
Accommodation/Occupational Safety › Occupational Safety › Tripping/Falling Hazard
Issued 16 September 2011
Resolved
Bottom ladder step to pilothouse was wasted and bent.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Replaced.
Lifesaving › Rescue Boat › Markings
Issued 16 September 2011
Resolved
Boat did not have vessel or max POB stenciled.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Stenciled.
Engineering › Lubricating Oil Service System › Piping
Issued 16 September 2011
Resolved
Port leg tower hydraulic system piping contained a temp patch.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Piping was replaced.
Engineering › Lubricating Oil Service System › Hose
Issued 16 September 2011
Resolved
Numerous jacking system hoses were either wasted or damaged on all leg towers. Vessel to replace those as indicated by MI.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Jacking system hoses were replaced.
Fire Fighting › Remote Fuel Shutoff › General
Issued 16 September 2011
Resolved
Stbd E/R fuel remote cut off reach rod was cracked in half.
Condition: Damaged By Earlier Event
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Repaired.
Engineering › Lubricating Oil Service System › Hose
Issued 16 September 2011
Resolved
A 78 inch flex hose was installed in the overhead of the stbd Engineroom. Hose serviced obsolete wire line equipment. Hose was leaking onto several absorbent rags on the deck. Required vessel to replace hose.
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: replaced.
Electrical › Electric Supply System (service) › Battery Installation
Issued 16 September 2011
Resolved
Stbd E/R battery box did not have a cover.
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Provided.
Engineering › Diesel Engine (auxiliary) › Block
Issued 16 September 2011
Resolved
Stbd E/R generator leaked oil excessively. Oil had pooled up in engine's fuel filter flame shield and engine radiator was saturated with oil. Identify and correct leaks.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Leaks were corrected.
Electrical › Lighting (emergency) › Battery Operated Lantern
Issued 16 September 2011
Resolved
Port and Stbd emergency lighting was inop. [name withheld] stated light batteries were exhausted from vessel power being secured overnight. Another emergency light check revealed galley light operating normally.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 27 January 2012
Resolution: All emergency lighting was operable.
Engineering › Lubricating Oil Service System › Hose
Issued 16 September 2011
Resolved
Stbd E/R hydraulic system flex hose above manifold had a blister leaking fluid. Replace.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Replaced.
Engineering › Steering Gear System › Hydraulic Hose
Issued 16 September 2011
Resolved
Stbd E/R steering flex hose cover was deteriorated to the point that the inner braid was exposed. Hose requires replacement.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Hoses were replaced.
Operations/Management › Casualty Reporting/Post-Casualty Actions › Notice of Marine Casualty
Issued 16 September 2011
Resolved
Shipyard superintendant notified local CG office of jacking system casualty. Vessel has not submitted CG-2692.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 16 September 2011
Resolution: 2692 was submitted on 15Sept2011.
Construction/Loadline › Hull › Stiffener
Issued 16 September 2011
Resolved
Middle support on port leg tower contained an illegal lap patch near top of tower. Required vessel to replace support.
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Support was replaced and UT report provided.
Engineering › Lubricating Oil Service System › Hose
Issued 16 September 2011
Resolved
Material condition of vessel's hydraulic jacking system was in substandard condition. Required vessel to provide 3rd party report identifying all system components as fail safe IAW NVIC 8-91, D8 policy letter 07-02, and 46 CFR 58.30.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 28 December 2011
Resolution: Received 3rd party report indicating system is fail safe. Scanned document into MISLE.
Communications › Audible Communications › Horn/Whistle
Issued 16 September 2011
Resolved
Horn was inop.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Repaired.
Construction/Loadline › Structures › Superstructure
Issued 16 September 2011
Resolved
Pilothouse bulkhead was wasted through on the port bulkhead in two places, under port side window, and stbd forward corner. Vessel to repair.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Bulkhead was repaired.
Accommodation/Occupational Safety › Occupational Safety › Deck Rail
Issued 16 September 2011
Resolved
Numerous handrails on main deck and 02 deck were wasted near the deck.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 November 2011
Resolution: Handrails were repired.
Communications › Radio Communications › EPIRB
Issued 16 September 2011
Resolved
EPIRB registration had expired in 1/2011. Renew registration.
Condition: Invalid
Action required: 17 - Rectify deficiencies prior to departure
Resolved 29 November 2011
Resolution: Vessel prvided documenation of valid EPIRB regristation.
Navigation › Piloting/Steering › Marine Charts
Issued 16 September 2011
Resolved
Charts onboard were from 2007 and were not updated. Notice to mariners was also not onboard.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 29 November 2011
Resolution: New charts purchased (dtd Sept 2011) NTM on board and Captain will verify charts updated to current date.
Engineering › Freshwater Generation System › Piping
Issued 16 September 2011
Resolved
Stbd water tank contains wasted pipes.
Action required: 705 - Other - as specified
Resolved 27 January 2012
Resolution: Wasted pipe C/R.
Construction/Loadline › Hull › Stiffener
Issued 16 September 2011
Resolved
Stbd rudder stop weld is cracked. Gouge and reweld.
Condition: Damaged By Earlier Event
Action required: 705 - Other - as specified
Resolved 27 January 2012
Resolution: Weld was gouged and re-welded.
Stability › Watertight Integrity › General
Issued 16 September 2011
Resolved
Stbd rudder room centerline bulkhead has 1/8" diameter holes throughout bulkhead.
Action required: 705 - Other - as specified
Resolved 27 January 2012
Resolution: Wasted areas of the bulkhead was C/R.
Accommodation/Occupational Safety › Occupational Safety › Tripping/Falling Hazard
Issued 16 September 2011
Resolved
Port and stbd sponson ladders have wasted steps. Steps need to be renewed.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 27 January 2012
Resolution: Steps were C/R.
Stability › Watertight Integrity › General
Issued 16 September 2011
Resolved
Repair wasted holes in forward bulkhead and sideshell channels in Stbd ballast tank.
Action required: 705 - Other - as specified
Resolved 27 January 2012
Resolution: Holes were C/R in STBD ballast tank.
Stability › Watertight Integrity › General
Issued 16 September 2011
Resolved
Repair wasted centerline bulkhead in between port and stbd ballast tanks.
Action required: 705 - Other - as specified
Resolved 25 January 2012
Resolution: Wasted section of bulkhead was C/R.
Construction/Loadline › Hull › Hull Plating
Issued 16 September 2011
Resolved
Repair port bow rake inset.
Condition: Damaged By Earlier Event
Action required: 705 - Other - as specified
Resolved 27 January 2012
Resolution: During the Hull inspection, did not come across any inset in the bow rake.
Engineering › Bilge Water Management System › Strainer
Issued 16 September 2011
Resolved
Replace missing or wasted bilge suction strainers.
Action required: 705 - Other - as specified
Resolved 27 January 2012
Resolution: All bilge suction strainers replaced.
Lifesaving › Rescue Boat › Carriage Requirement
Issued 16 September 2011
Resolved
Rescue boat did not run. Demonstrate operation to attending MI.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 29 November 2011
Resolution: Vessel operated fwd and backward. Captain reported bad gas caused prior failure.
Operations/Management › Bilge/Bilge System Management › Control of Excess Water
Issued 16 September 2011
Resolved
Stbd engineroom bilge alarm was inop.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 29 November 2011
Resolution: tested bilge alarm - sat
Construction/Loadline › Hull › Keel
Issued 16 September 2011
Resolved
Provide to local OCMI a 3rd party UT report of a 2 ft by 2 ft grid of the entire hull (keel, sideshell, deck and all internal bulkheads)
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 December 2011
Resolved 7 December 2011
Resolution: UT shots were provided by Qualitech Services INC.
Documentation › Logs/Records › Logbook (official)
Issued 22 December 2010
Resolved
No Abandon Ship Drills Logged
Action required: 705 - Other - as specified
Due 23 December 2011
Resolved 6 February 2012
Resolution: Drills are being logged in Ships rough log.
Documentation › Logs/Records › Logbook/Record (unofficial)
Issued 22 December 2009
Resolved
Properly log all fire fighting/ life saving drills
Action required: 705 - Other - as specified
Resolved 23 December 2010
Resolution: Fire fighting drills logged.
Documentation › Logs/Records › Logbook/Record (unofficial)
Issued 22 December 2009
Resolved
Provide log for predeparture check-offs.
Action required: 705 - Other - as specified
Resolved 23 December 2010
Resolution: Pre-departure check offs logged
Communications › Public Address System › Loudspeaker
Issued 22 December 2009
Resolved
Demonstrate proper operation of public address on emergency power
Action required: 705 - Other - as specified
Resolved 5 March 2010
Communications › Radio Communications › VHF Radiotelephone
Issued 22 December 2009
Resolved
Demonstrate proper operation of VHF radio on emergency power
Action required: 705 - Other - as specified
Resolved 5 March 2010
Engineering › Generator (propulsion-electric) › Overcurrent Devices Circuitry
Issued 22 December 2009
Resolved
Demonstrate proper operation of overspeed on both generators
Action required: 705 - Other - as specified
Resolved 5 March 2010
Navigation › Piloting/Steering › Marine Charts
Issued 22 December 2009
Resolved
Properly correct/mark navigation charts
Action required: 705 - Other - as specified
Resolved 23 December 2010
Resolution: New charts on board
Deck/Cargo › Cargo Transfer (solid) › General
Issued 22 December 2009
Resolved
Provide crane signals/ label throttles
Action required: 705 - Other - as specified
Resolved 5 March 2010
Fire Fighting › Fire Pumps › Pressure
Issued 22 December 2009
Resolved
Demonstrate proper operation and adequate pressure for fire pump
Action required: 705 - Other - as specified
Resolved 5 March 2010
Lifesaving › Lifefloat › Netting
Issued 22 December 2009
Resolved
Remove paint on lifefloat and repair damaged reflective tape.
Action required: 705 - Other - as specified
Resolved 5 March 2010
Engineering › Generator (propulsion-electric) › Generator Voltage Regulator Circuitry
Issued 2 February 2009
Resolved
Demonstrate proper operation of both service generators.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 3 February 2009
Resolution: Both generators operating properly.
Navigation › Piloting/Steering › Tide/Tidal Current Tables
Issued 2 February 2009
Resolved
No current Tide/Tidal Current Tables on board
Action required: 17 - Rectify deficiencies prior to departure
Resolved 3 February 2009
Resolution: Current Tide/Tidal Current Tables provided.
Documentation › Markings/Placards › Garbage Placard
Issued 2 February 2009
Resolved
Renew Garbage Placards and Oil placards
Action required: 17 - Rectify deficiencies prior to departure
Resolved 3 February 2009
Resolution: New placards placed on board
Communications › Alarms/Indicators › Bilge Alarm
Issued 2 February 2009
Resolved
Demonstrate proper operation of vsl's bilge alarms
Action required: 17 - Rectify deficiencies prior to departure
Resolved 3 February 2009
Resolution: Bilge alarms operating properly
Navigation › Collision/Grounding Avoidance › Day Shapes
Issued 2 February 2009
Resolved
Provide proper day shapes
Action required: 17 - Rectify deficiencies prior to departure
Resolved 3 February 2009
Resolution: Proper day shapes placed on board.
Navigation › Collision/Grounding Avoidance › Day Shapes
Issued 2 February 2009
Resolved
Provide proper day shapes
Action required: 17 - Rectify deficiencies prior to departure
Resolved 3 February 2009
Resolution: Proper day shapes placed on board.
Lifesaving › Lifefloat › Float-free Link
Issued 2 February 2009
Resolved
Improper size Float-free link attached to lifefloat
Action required: 17 - Rectify deficiencies prior to departure
Resolved 3 February 2009
Resolution: Proper size Float-free link installed.
Engineering › Generator (propulsion-electric) › Battery
Issued 2 February 2009
Resolved
Battery box had no cover
Action required: 17 - Rectify deficiencies prior to departure
Resolved 3 February 2009
Resolution: Battery box cover installed
Fire Fighting › Means of Escape › Escape Route Signs
Issued 2 February 2009
Resolved
Emergency Exits not stenciled
Action required: 17 - Rectify deficiencies prior to departure
Resolved 3 February 2009
Resolution: Emergency exits stenciled properly
Fire Fighting › Means of Escape › Escape Route Signs
Issued 2 February 2009
Resolved
Emergency Exits not stenciled
Action required: 17 - Rectify deficiencies prior to departure
Resolved 3 February 2009
Resolution: Emergency exits stenciled properly
Lifesaving › Lifejacket/PFD (General) › Marking
Issued 2 February 2009
Resolved
Lifejackets on board not stenciled with Vessel name
Action required: 17 - Rectify deficiencies prior to departure
Resolved 3 February 2009
Resolution: Lifejackets stenciled properly
Documentation › Certificates/Documents › FCC SSL
Issued 2 February 2009
Resolved
Master had no FCC Operator Permit
Due 4 March 2009
Resolved 5 March 2010
Navigation › Collision/Grounding Avoidance › Day Shapes
Issued 18 September 2007
Resolved
Provide adequate amount of day shapes for vessel.
Due 18 October 2007
Resolved 20 September 2007
Resolution: Adequate amount of day shapes provided.
Navigation › Piloting/Steering › US Coast Pilot
Issued 18 September 2007
Resolved
Provide US Coast Pilot, and Light List.
Due 18 October 2007
Resolved 20 September 2007
Resolution: Purchased required Navigation Publications.
Documentation › Logs/Records › Logbook/Record (unofficial)
Issued 18 September 2007
Resolved
Provide Lifesaving maintenance record.
Due 18 October 2007
Resolved 20 September 2007
Resolution: Provided Life Saving Maintenance Record.
Fire Fighting › Fire Main › Pressure
Issued 18 September 2007
Resolved
Demonstrate proper operation of fire pump, with sufficient pressure.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 20 September 2007
Resolution: Demonstrated proper operation of fire pump, 62 psi.
Lifesaving › Lifefloat › Painter
Issued 18 September 2007
Resolved
Arrange lifefloat as per 46 CFR's require.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 20 September 2007
Resolution: Lifefloat arranged properly.
Fire Fighting › Portable CO2 Fire Extinguisher › Location
Issued 18 September 2007
Resolved
Provide adequate amount of fire extinguishers as per COI., and install properly.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 20 September 2007
Resolution: Provided adequate amount of fire extinguishers.
Navigation › Collision/Grounding Avoidance › Navigation Lights
Issued 25 January 2007
Resolved
Remove all paint overspray from navigation lights. Install proper vertical filament bulbs as required by COLREGS.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 26 January 2007
Navigation › Collision/Grounding Avoidance › Navigation Lights
Issued 25 January 2007
Resolved
Renew starboard (green) running light.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 26 January 2007
Fire Fighting › Means of Escape › Escape Route Signs
Issued 25 January 2007
Resolved
Label all emergency escape scuttles on deck with "Emergency Escape - Do Not Block" with brightly colored background. Label interior ladders for emergency escapes "Emergency Escape - Do Not Block" .
Action required: 17 - Rectify deficiencies prior to departure
Resolved 26 January 2007
Accommodation/Occupational Safety › Potable Water System › General
Issued 25 January 2007
Resolved
Properly secure hot water heater and plumb pressure/temperature relief valve to bilge.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 26 January 2007
Engineering › Diesel Engine (propulsion-reduction gear) › Spark Arrestor (exhaust)
Issued 25 January 2007
Resolved
Correct/renew as necessary exhaust insulation as needed on all engines.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 26 January 2007
Engineering › Diesel Engine (propulsion-reduction gear) › Silencer (exhaust)
Issued 25 January 2007
Resolved
Correct all exhaust leaks on all engines.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 26 January 2007
Engineering › Fuel Oil Service System › Filter
Issued 25 January 2007
Resolved
Remove all petcock style valves from fuel system.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 26 January 2007
Electrical › Electrical Distribution System (service) › Non-conducting Deck Covering
Issued 25 January 2007
Resolved
Provide non-conductive matting for deck in front of switchboard.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 26 January 2007
Engineering › Fuel Oil Service System › Piping
Issued 25 January 2007
Resolved
Correct fuel leaks on starboard propulsion engine.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 26 January 2007
Accommodation/Occupational Safety › Occupational Safety › Portable Electric Equipment/Appliances
Issued 25 January 2007
Resolved
Secure televisions, microwave ovens and refrigerators on vessel.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 26 January 2007
Electrical › Electrical Distribution System (service) › Panelboard
Issued 25 January 2007
Resolved
Install breaker blank on main deck breaker panel.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 26 January 2007
Fire Fighting › Remote Fuel Shutoff › General
Issued 25 January 2007
Resolved
Label all remote fuel shutoffs with bright contrasting color background and direction of operation.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 26 January 2007
Electrical › Lighting (emergency) › Lighting Fixture
Issued 25 January 2007
Resolved
Provide emergency lighting at all emergency exits.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 26 January 2007
Engineering › Steering Gear System › Piping
Issued 25 January 2007
Resolved
Plug or cap drain valve on starboard hydraulic fluid tank.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 26 January 2007
Operations/Management › Casualty Reporting/Post-Casualty Actions › Determination of Alcohol/Drug Use
Issued 25 January 2007
Resolved
Provide alcohol test kit as required for post-casualty alcohol testing.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 26 January 2007
Engineering › Steering Gear System › Piping
Issued 25 January 2007
Resolved
Provide appropriate flame screen for hydraulic steering reservoir vent.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 26 January 2007
Pollution Prevention/Response › Prevention Equipment › Sewage System Piping
Issued 25 January 2007
Resolved
Provide means to secure sewage overboard connection as per 33 CFR 159.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 26 January 2007
Operations/Management › Drills/Instruction › Not Conducted
Issued 25 January 2007
Resolved
Conduct and log drills as required by 46 CFR 185.420
Action required: 17 - Rectify deficiencies prior to departure
Resolved 26 January 2007
Operations/Management › Drills/Instruction › Making Voice Radio Distress Call
Issued 25 January 2007
Resolved
Provide proper emergency broadcast placard.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 26 January 2007
Lifesaving › Lifejacket/PFD (General) › Marking
Issued 25 January 2007
Resolved
Stencil proper vessel name on all lifesaving equipment.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 26 January 2007
Operations/Management › Drills/Instruction › Safety Orientation
Issued 25 January 2007
Resolved
Label all switches and controllers in main deck lounge.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 26 January 2007
Electrical › Electrical Distribution System (service)
Issued 2 March 2004
Resolved
Label all breakers in wire line room breaker panel. LEGACY COMPONENT DESC: Panel board
Action required: 17 - Rectify deficiencies prior to departure
Resolved 5 March 2004
Resolution: Breakers labled.
Electrical › Electrical Distribution System (service)
Issued 2 March 2004
Resolved
Provide rubber mat at each switchboard. LEGACY COMPONENT DESC: Non-conducting Deck Covering
Action required: 17 - Rectify deficiencies prior to departure
Resolved 5 March 2004
Resolution: Mats provided.
Stability › Watertight Integrity
Issued 2 March 2004
Resolved
Lubricate and adjust engine room hatches.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 5 March 2004
Resolution: Hatches lubricated and adjusted.
Stability › Watertight Integrity
Issued 2 March 2004
Resolved
Clean, adjust, lubricate and replace issuing parts on P & S engine room escape hatches.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 5 March 2004
Resolution: Repairs completed.
Stability › Watertight Integrity
Issued 2 March 2004
Resolved
Provide dogging wrenches for watertight doors
Action required: 17 - Rectify deficiencies prior to departure
Resolved 5 March 2004
Resolution: Provided.
Electrical › Lighting (emergency) › Battery Operated Lantern
Issued 2 March 2004
Resolved
Replace dead and missing E light batteries.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 5 March 2004
Resolution: Batteries replaced.
Accommodation/Occupational Safety › Medical/First Aid
Issued 2 March 2004
Resolved
Provide new USCG Approved first aid kit LEGACY COMPONENT DESC: Medicine Chest
Action required: 17 - Rectify deficiencies prior to departure
Resolved 5 March 2004
Resolution: First aid kit provided.
Communications › Visual Communication
Issued 2 March 2004
Resolved
Provide complete set of distress fares.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 5 March 2004
Resolution: Flares provided.
Navigation › Piloting/Steering › Coast Guard Light List
Issued 2 March 2004
Resolved
Provide current publications: Nav Rules, Light List, Coast Pilot, and 46 CFR 166-199.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 12 March 2004
Resolution: Provided.
Engineering › Fuel Oil Service System › Filter
Issued 2 March 2004
Resolved
Replace missing flame bowls.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 5 March 2004
Resolution: Replaced missing flame bowls.
Operations/Management › Pollution
Issued 2 March 2004
Resolved
Service Type II MSD
Action required: 17 - Rectify deficiencies prior to departure
Resolved 5 March 2004
Resolution: Serviced by authorized repair facility
Stability › Watertight Integrity
Issued 15 October 2002
Resolved
Repair or replace port engine room escape hatch.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 17 October 2002
Resolution: Hatch repaired.
Electrical › Lighting (emergency) › Battery Operated Lantern
Issued 15 October 2002
Resolved
Replace burnt bulbs on all "E" lights as necessary.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 17 October 2002
Resolution: Lights repaired.
Engineering › Diesel Engine (propulsion-reduction gear)
Issued 15 October 2002
Resolved
Replace flame guards on Racor filters as necessary.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 17 October 2002
Resolution: Flame guards replaced
Communications › Alarms/Indicators › Bilge Alarm
Issued 15 October 2002
Resolved
Repair port bilge alarm to ring in wheel house.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 17 October 2002
Resolution: Alarm repaired.
Lifesaving › Lifebuoys › Self-igniting Lights
Issued 15 October 2002
Resolved
Replace brokenn water light.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 17 October 2002
Resolution: Light replaced
Lifesaving › Buoyant Apparatus
Issued 15 October 2002
Resolved
Replace sea painter
Action required: 17 - Rectify deficiencies prior to departure
Resolved 17 October 2002
Resolution: Sea painter replaced
Communications › Radio Communications
Issued 15 October 2002
Resolved
Update EPIRB registration and replace hydrostatic release. LEGACY COMPONENT DESC: EPIRB
Action required: 17 - Rectify deficiencies prior to departure
Resolved 24 October 2002
Resolution: Registration updated / hydrostat replaced.
Lifesaving › Lifebuoys
Issued 15 October 2002
Resolved
Replaced cracked life rings.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 17 October 2002
Resolution: life rings replaced.
Electrical › Electrical Distribution System (service) › Circuit Breaker
Issued 15 October 2002
Resolved
Lable breakers in wire line room.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 17 October 2002
Resolution: Breakers labled.
Navigation › Collision/Grounding Avoidance › Navigation Lights
Issued 15 October 2002
Resolved
Replace starboard nav light.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 17 October 2002
Resolution: Light replaced.
Accommodation/Occupational Safety › Medical/First Aid › Medicine Chest
Issued 15 October 2002
Resolved
Restock first aid kit
Action required: 17 - Rectify deficiencies prior to departure
Resolved 17 October 2002
Resolution: first aid kit replaced.
Lifesaving
Issued 16 December 1999
Resolved
DEMONSTRATE COMPLIANCE WITH THE EIGHTH COAST GUARD DISTRICT'S POLICY LETTER"RESCUE BOATS ON OFFSHORE SUPPLY BOATS" TO THE SATISFACTION OF THE ATTENDING COAST GUARD MARINE INSPECTOR.
Condition: Unknown
Due 16 December 1999
Resolved 16 December 1999
Documentation
Issued 19 October 1994
Resolved
OBTAIN INDIVIDUAL VESSEL FCC STATION LICENSE AND CALL SIGN.
Condition: Unknown
Due 19 October 1994
Resolved 19 October 1994
Documentation
Issued 4 March 1991
Resolved
PROVIDE ON BOARD VALID CERTIFICATE OF DOCUMENTATION.
Condition: Unknown
Due 4 March 1991
Resolved 4 March 1991
Documentation
Issued 3 November 1989
Resolved
PROVIDE ON BOARD A COAST GUARD ISSUED STABILITY LETTER AND FREEBOARD MARKINGS IN ACCORDANCE WITH STABILITY REQUIREMENTS.
Condition: Unknown
Due 3 November 1989
Resolved 3 November 1989
Documentation
Issued 3 November 1989
Resolved
SUBMIT AN OPERATING MANUAL MEETING THE APPLICABLE SECTIONS OF 46 CFR 109.121 TO [name withheld] FOR APPROVAL.
Condition: Unknown
Due 3 November 1989
Resolved 3 November 1989
Documentation
Issued 3 November 1989
Resolved
SUBMIT PLANS SHOWING GENERAL ARRANGEMENT, INBOARD AND OUTBOARD PROFILE, ANDA STRUCTURAL ANALYSIS OF ALL LEGS AND LEG TOWER SUPPORTS TO [name withheld] FOR APPROVAL.
Condition: Unknown
Due 3 November 1989
Resolved 3 November 1989