ANDINO ALPHA

ANDINO ALPHA is a 2002 tank ship. The Coast Guard has recorded 30 inspections since 2022, most recently in September 2025, along with 53 deficiencies and 10 operational controls, 1 with no removal date recorded.

Records from 2022 to 2025. Most recent: operational control imposed, 26 September 2025.

Built
2002
Last inspected
15 September 2025
Documentation
Not in the documentation file of 10 August 2026
Controls
1 with no removal date recorded

Coast Guard record current through 23 August 2026, retrieved 5 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Tank Ship class in Maury's sources begin in 2016.

Inspection record

Last inspected 15 September 2025
…with no type recorded7
Operational controls 1 with no removal date recorded
Years with a record 4 calendar years (2022–2025)
Every line above is a count of records the US Coast Guard wrote, or a date it recorded. A blank resolution means none was recorded in this data; it does not establish that a deficiency is outstanding. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Identity

9254202
563133
Flag
CYPRUS
Maury page id
psix-563133

Documentation record

Tonnage as PSIX records it14045 - Dead Weight, Ton
18453 - Displacement, Ton
8253 - Convention (Subpart B), Gross Ton
4735 - Convention (Subpart B), Net Ton
This hull's Official Number is not in the NVDC file dated 10 August 2026 as served by NOAA Fisheries, so no documentation record is shown. Absence from that file is a fact about the file, not about the hull.
Vessel history report
Every record for this hull, in one document — $299

Every recorded inspection, 2016 to 2026 for this class, in one chronology · every deficiency, with system, dates and resolution · operational controls imposed and removed · every name this hull has been recorded under · the vessels it was inspected alongside, and when · how its record compares with hulls of similar age and size, as a fact about the population and never a judgement about this vessel.

Read one first, in full: a forty-year chronology · a hull that changed operators four times · the sparse case, shown as an example, not for sale.

This report is in development and is not for sale yet. There is no date, and nothing is charged. Leave an email and we will tell you when it exists, once.

Inspection history · 30

15 September 2025 Bulk Liquid Transfer Monitor
Physical examination · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 8234810
10 September 2025 In-Service Inspection · Deficiency Check · PSC A · Administrative Inspection
Physical examination · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 8230847
9 September 2025 Type not recorded
No type recorded · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 8230675
6 August 2025 Administrative Inspection
Administrative · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 8204073
8 July 2025 PSC A
Physical examination · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 8178934
8 July 2025 Bulk Liquid Transfer Monitor
Physical examination · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 8179548
4 July 2025 Deficiency Check
Physical examination · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 8175020
16 May 2025 Deficiency Check · PSC A
Physical examination · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 8137673
7 May 2025 Administrative Inspection
Administrative · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 8130145
20 March 2025 Deficiency Check · PSC B
Physical examination · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 8096728
7 March 2025 Administrative Inspection
Administrative · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 8089851
28 January 2025 PSC B · COC-CHEM & TVE Annual · Deficiency Check
Physical examination · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 8071726
21 August 2024 Administrative Inspection · PSC B
Physical examination · Marine Safety Unit Lake Charles · USCG Heartland District (CGD-H) · Activity 7983817
16 June 2024 Deficiency Check
Physical examination · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 7935760
25 March 2024 PSC B
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 7879553
26 January 2024 PSC A · Deficiency Check · Administrative Inspection · COC-CHEM & TVE Renew
Physical examination · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 7856075
1 November 2023 Type not recorded
No type recorded · Sector Corpus Christi · USCG Heartland District (CGD-H) · Activity 7818712
26 October 2023 Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 7815061
9 March 2023 Type not recorded
No type recorded · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 7648449
9 March 2023 COE-Offshore
Physical examination · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 7648460
19 January 2023 Type not recorded
No type recorded · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 7624100
19 January 2023 COE-Offshore
Physical examination · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 7624103
18 December 2022 PSC B · COC-CHEM & TVE Annual
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 7610618
25 September 2022 Type not recorded
No type recorded · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 7565801
25 September 2022 COE-Offshore
Physical examination · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 7565803
21 August 2022 Type not recorded
No type recorded · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 7539835
21 August 2022 COE-Offshore
Physical examination · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 7539855
17 August 2022 Type not recorded
No type recorded · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 7537183
18 March 2022 COE-Administrative
Administrative · Resident Inspection Office St. Croix · USCG Southeast District (CGD-SE) · Activity 7414065
26 January 2022 COC-CHEM & TVE Renew · PSC B
Physical examination · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 7380452

Deficiency record · 53

06 - Cargo Operations Including Equipment › N/A - No Subsystem › Other (cargo)
Issued 15 September 2025 Resolved
A transfer is considered to begin when the person in charge...(i) each transfer hose has no unrepaired loose covers, kinds, bulges, soft spots, or any other defect which would permit the discharge of oil or hazardous material through the hose material. PSCO observed soft spot and/or temporary repair on cargo hose connected between #1 Starboard and #6 Port manifold. 33CFR156.120
Action required: 17 - Rectify deficiencies prior to departure
Resolved 16 September 2025
Resolution: Received class report stating cargo hose removed from manifold and will be discarded at next available port.
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Other (cargo)
Issued 15 September 2025 Resolved
The conditions of the ship and it's equipment shall be maintained to conform with the provisions of the code to ensure that the ship will remain fit to proceed to sea without danger to the ship or persons on board or without presenting an unreasonable threat of harm to the marine environment. PSCO observed cargo dripping from the 8P Manifold flange at a rate of 12 drips per minute. 74SOLAS(20)VII/10.1 IBC Code 1.5.3.1
Action required: 17 - Rectify deficiencies prior to departure
Resolved 15 September 2025
Resolution: Vessel crew tightened down flange and stopped dripping.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 10 September 2025 Resolved
"A" CLASS DIVISIONS ARE THOSE DIVISIONS FORMED BY BULKHEADS AND DECKS WHICH COMPLY WITH THE FOLLOWING: THEY SHALL BE CONSTRUCTED AS TO BE CAPABLE OF PREVENTING THE PASSAGE OF SMOKE AND FLAME. PSCO OBSERVED THREE DOORS THAT WERE NOT GAS TIGHT-THE CO2 ROOM DOOR AND TWO DOORS LEADING INTO THE ENGINE ROOM. AIRFLOW WAS DETECTED AROUND THE PERIMETER OF THE DOORS WHILE IN THE CLOSED POSITIONS.
Condition: Design Flaw
Action required: 30 - Ship detained
Resolved 15 September 2025
Resolution: Vessel changed gaskets and adjusted doors. Received class report stating the same.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 10 September 2025 Resolved
ALL ELECTRICAL APPARATUS SHALL BE SO CONSTRUCTED AND SO INSTALLED AS NOT TO CAUSE INJURY WHEN HANDLED OR TOUCHED IN THE NORMAL MANNER. PSCO OBSERVED A MODIFIED SWITCH IN THE AIR CONDITIONING FLAT WITH EXPOSED ELECTRICAL WIRING.
Condition: Improper/Lack of Maintenance
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 15 September 2025
Resolution: Vessel crew rectified electrical wiring. Class report received stating the same.
15 - Safety Management Systems (ISM) › N/A - No Subsystem › Maintenance of the ship and equipment
Issued 10 September 2025 Resolved
IN MEETING THESE REQUIREMENTS, THE COMPANY SHOULD ENSURE THAT: INSPECTIONS ARE HELD AT APPROPRIATE INTERVALS; ANY NON-CONFORMITY IS REPORTED, WITH ITS POSSIBLE CAUSE, IF KNOWN; APPROPRIATE CORRECTIVE ACTION IS TAKEN; AND RECORDS OF THESE ACTIVITIES ARE MAINTAINED. THE TECHNICAL AND/OR OPERATIONAL NATURE OF DEFICIENCIES 02-06 PROVIDE OBJECTIVE EVIDENCE OF A SERIOUS FAILURE OF THE ISM CODE IMPLEMENTATION. AN EXTERNAL AUDIT REPORT SATISFACTORY TO THE OCMI MUST BE SUBMITTED PRIOR TO CLEARANCE OF THIS DEFICIENCY AND RELEASE FROM DETENTION. 74 SOLAS (20)IX/3.1, ISM 10.2
Condition: Improper/Lack of Maintenance
Action required: 30 - Ship detained
Resolved 26 September 2025
Resolution: Class society (Lloyd's Register) provided external audit results satisfying Sector H-G's requirements to clear the deficiency. Audit results uploaded to deficiency documents.
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Other (cargo)
Issued 10 September 2025 Resolved
SHIPS CARRYING TOXIC OR FLAMMABLE PRODUCTS OR BOTH SHALL BE EQUIPPED WITH AT LEAST TWO INSTRUMENTS DESIGNED AND CALIBRATED FOR TESTING THE SPECIFIC VAPOURS IN QUESTION. PSCO OBSERVED THAT THE VESSEL DID NOT CARRY ANY INSTRUMENTS TO MEASURE TOXIC VAPORS OF VINYL ACETATE, A CARGO CURRENTLY LOADED ON-BOARD. 74 SOLAS (01)VII/10.1, IBC 13.2.2
Condition: Improper/Lack of Maintenance
Action required: 30 - Ship detained
Resolved 15 September 2025
Resolution: Vessel received vacuum tubes for vinyl acetate.
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Other (cargo)
Issued 10 September 2025 Resolved
THE CONDITION OF THE SHIP AND ITS EQUIPMENT SHALL BE MAINTAINED TO CONFORM WITH THE PROVISIONS OF THE PRESENT REGULATIONS TO ENSURE THAT THE SHIP IN ALL RESPECTS WILL REMAIN FIT TO PROCEED TO SEA WITHOUT DANGER TO THE SHIP OR PERSONS ON BOARD. PSCO OBSERVED TEMPORARY REPAIRS AND PIPE CLAMPS IN 09 LOCATIONS ALONG THE VAPOR COLLECTION SYSTEM "C" LINE. 74 SOLAS (20)I/II(a),IBC 1.5.3.1
Condition: Improper/Lack of Maintenance
Action required: 30 - Ship detained
Resolved 15 September 2025
Resolution: Cargo is prohibited by vessel in the U.S. COC revoked. Class provided report stating "C" line is isolated and repairs will be made at next port.
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Other (cargo)
Issued 10 September 2025 Resolved
A TRANSFER IS CONSIDERED TO BEGIN WHEN THE PERSON IN CHARGE...NO PERSON SHALL CONDUCT AN OIL OR HAZARDOUS MATERIAL TRANSFER OPERATION UNLESS: (f) THE END OF EACH HOSE AND LOADING ARM THAT IS NOT CONNECTED FOR THE TRANSFER OF OIL OR HAZARDOUS MATERIAL IS BLANKED OFF. PSCO OBSERVED 02 HOSES NOT IN USE AND NOT BLANKED OFF ON DECK. 33 CFR 156.120
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 10 September 2025
Resolution: Crew blanked off 02 hoses.
09 - Working and Living Conditions › 092 - Working Conditions › Stowage of cargo
Issued 10 September 2025 Resolved
PROVISION SHALL BE MADE TO ENSURE THAT THE LIQUID HEAD IN ANY TANK DOES NOT EXCEED THE DESIGN HEAD OF THE TANK. PSCO OBSERVED CARGO TANKS 9 STARBOARD, 10 PORT, AND 10 STARBOARD ABOVE 98%, WITH 10 STARBOARD AT 99.8%, VISUALLY OBSERVED FROM CARGO CONTROL ROOM. OBSERVATION MADE POST OVERFLOW CASUALTY RESULTING IN CARGO RELEASE ONTO THE DECK VIA THE VAPOR LINE. 74SOLAS(01)VII/10.1,IBC 8.2.2
Condition: Improper/Lack of Maintenance
Action required: 30 - Ship detained
Resolved 15 September 2025
Resolution: Vessel transferred cargo into 5P. Class report received.
04 - Emergency Systems › N/A - No Subsystem › Emergency, lighting, batteries and switches
Issued 16 May 2025 Resolved
ELECTRICAL INSTALLATIONS SHALL BE SUCH THAT: ELECTRICAL SERVICES ESSENTIAL FOR SAFETY WILL BE ENSURED UNDER VARIOUS EMERGENCY CONDITIONS. PSCO WITNESSED ALL BUT ONE EMERGENCY LIGHT NOT ILLUMINATED ON ACCOMODATION EXTERIOR DURING TEST. 74 SOLAS (04) II-1/40.1.2
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 4 June 2025
Resolution: Observed operable emergency lighting during def check.
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Other (cargo)
Issued 16 May 2025 Resolved
THE CONDITION OF THE SHIP AND ITS EQUIPMENT SHALL BE MAINTAINED TO CONFORM WITH THE PROVISIONS OF THE PRESENT REGULATIONS TO ENSURE THAT THE SHIP WILL REMAIN FIT TO PROCEED TO SEA. PSCO OBSERVED FRAMO PUMPS ON 12P, 13P, 13S, 11P, AND 9P LEAKING HYDRAULIC OIL. ADDITIONALLY, PSCO OBSERVED SIGNIFICANT HYDRAULIC OIL ACCUMULATION UNDER FRAMO POWER PACKS. ALSO, FRAMO CONTROL UNIT IN CCR SHOWS WITH "PROTECTION PRESSURE" ALARM DUE TO FAULTY SENSOR. 74 SOLAS (20) I/11A
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 4 June 2025
Resolution: Observed operable framo pump system during def check.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 16 May 2025 Resolved
LIFEBUOYS COMPLYING WITH THE REQUIREMENTS OF PARAGRAPH 2.1.1 OF THE CODE SHALL BE: SO DISTRIBUTED AS TO BE READILY AVAILABLE ON BOTH SIDES OF THE SHIP. PSCO OBSERVED LIFEBUOY ON PORT MANIFOLD MISSING. VERIFIED ITS LOCATION ON GENERAL ARRANGEMENT. 74 SOLAS (20) III/7.1.1
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Resolved 4 June 2025
Resolution: Lifebouy observed in place during def check.
07 - Fire Safety › N/A - No Subsystem › Division - decks, bulkheads and penetrations
Issued 16 May 2025 Resolved
[withheld — contains personal information; the deficiency system, dates, and resolution status are shown above]
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 4 June 2025
Resolved 4 June 2025
Resolution: Observed repaired penetration during def check.
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Other (cargo)
Issued 16 May 2025 Resolved
EACH TANKSHIP WITH A VAPOR COLLECTION SYSTEM MUST BE FITTED WITH A PRESSURE SENSING DEVICE. 46CFR39, 2013 PSCO OBSERVED PRESSURE SENSORS ON VAPOR LINES “A” AND “D” INOPERABLE. VAPOR LINE “A” WAS CURRENTLY ALLIGNED FORVAPOR CONNECTION ON 11P, 9P, 14P, 12P, 10P, 13S, AND 11S
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Due 6 June 2025
Resolved 4 June 2025
Resolution: Observed operable pressure sensors on vapor lines during def check.
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Other (cargo)
Issued 16 May 2025 Resolved
EACH VESSEL VAPOR CONNECTION FLANGE MUST HAVE A PERMANENT STUD. 46CFR39, 2001(j) PSCO OBSERVED VAPOR LINE “D” ON STARBOARD MANIFOLD, WITHOUT STUD.
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Due 4 June 2025
Resolved 4 June 2025
Resolution: Observed vapor line stud on starboard manifold during def check.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 16 May 2025 Resolved
Electrical installations shall be such as to minimize the risk of fire and explosion from flammable products. PSCO observed tank radars on 7S, 9S, 11S, 13P, 14P, with exposed wiring. Additionally, PSCO observed H/L sensor on 11S with exposed wiring. 74Solas (20) VII/10.1 IBC 10.1.2.1
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 4 June 2025
Resolution: Observed proper wiring on tank radars during def check.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 16 May 2025 Resolved
The fire resistance of doors shall be equivalent to that of the division in which it is fitted.. doors required to be self closing shall not be fitted with hold back hooks. PSCO observed inoperable self closing doors in ladder well down from CCR, ECR, and galley. Additionally class “b” fire door into CCR was unable to be closed. PSCO observed fresh water hose run through class “a” door leading to steering preventing closure. 74Solas (01) II-2/ 47
Condition: Placed in Improper Service
Action required: 30 - Ship detained
Resolved 4 June 2025
Resolution: Observed operable self closing doors during def check.
15 - Safety Management Systems (ISM) › N/A - No Subsystem › Maintenance of the ship and equipment
Issued 16 May 2025 Resolved
The company and the ship shall comply with the requirement of the ISM code. The company should establish procedures to ensure that the ship is maintained in conformity with the provisions of the relevant rules and regulations. The technical and operational nature of the deficiencies 02-13 provide objective evidence of a serious failure, or lack of effectiveness, of the implementation of the ISM Code. A safety management audit carried out by the administration, or RO, with a corresponding report of findings satisfactory to the OCMI must be submitted prior to clearance of the deficiency and release from detention. 74 SOLAS (20) IX/3.1 ISM Code 10.1
Condition: Improper/Lack of Maintenance
Action required: 30 - Ship detained
Resolved 4 June 2025
Resolution: Recieved satisfactory ISM audit report from LR.
07 - Fire Safety › N/A - No Subsystem › Ready availability of fire fighting equipment
Issued 16 May 2025 Resolved
The total suction head and net positive suction head of the pump shall be such that the requirements of paragraphs 3.3.2, 3.3.2.1, 3.3.2.2, and 4.2 of these regulations shall be obtained under all conditions of trim, list, roll, and pitch likely to be encountered in service. PSCO observed emergency fire pump unable to obtain suction. Ships crew stated that that the pump does not work when in ballast condition. 74 SOLAS (01) II-2/4.3.3.2.5
Condition: Improper Installation
Action required: 30 - Ship detained
Resolved 4 June 2025
Resolution: Observed operable emergency fire pump during def check.
11 - Life Saving Appliances › N/A - No Subsystem › Rescue boats
Issued 16 May 2025 Resolved
Rescue boats shall be stowed in a state of continuous readiness for launching in not more than 5 minutes. PSCO observed rescue boat fail to start and run within 5 minutes. 74 SOLAS (20) III/14
Condition: Design Flaw
Action required: 30 - Ship detained
Resolved 4 June 2025
Resolution: Observed operable rescue boat during def check.
04 - Emergency Systems › N/A - No Subsystem › Fire drills
Issued 16 May 2025 Resolved
Performance of crew members assigned fire-fighting duties shall be periodically evaluated by conducting on-board training and drills to identify area in need of improvement, to ensure competency in fire-fighting skills is maintained, and to ensure the operational readiness of fire-fighting organization. PSCO observed 2 failed fire drills at midship stores. Observed crew unfamiliarity with fire-fighting equipment leading to unsafe conditions for fire team. A satisfactory fire drill is required prior to clearing this deficiency in the presence of a Coast Guard PSCO. 74 SOLAS (20) II-2/16.2.2.3
Condition: Improper/Lack of Maintenance
Action required: 30 - Ship detained
Resolved 4 June 2025
Resolution: Observed satisfactory fire drill during def check.
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Loading instrument
Issued 16 May 2025 Resolved
Alternatively, pressure sensors may be fitted on each deck with a monitoring system in the ships cargo control room. PSCO observed audible and visual alarm systems turned off, due to constant alarms. 74 SOLAS (01) II-2/59.1.2.3
Condition: Improper Installation
Action required: 30 - Ship detained
Resolved 4 June 2025
Resolution: Observed operable alarms in CCR during def check.
15 - Safety Management Systems (ISM) › N/A - No Subsystem › Shipboard operations
Issued 13 February 2025 Resolved
The company should identify equipment and techincal systems the sudden operational failure of which may result in hazardous situations. PSCO observed numerious failures of cargo monitoring deficiencies from the exam on 31Jan2025: #1, #2, #3; the exam on 02Feb2025: #1, #2, #3; and the exam on 13Feb2025: #10, #11, #12. Provide objective evidence of a failure of the implementation of the ISM Code with regard to cargo handling and monitoring systems. An internal audit report satisfactory to the OCMI must be submitted within 90 days prior to the clearance of this deficiency. 74 SOLAS (20) IX/3.1 ISM Code 10.3
Condition: Invalid
Action required: 705 - Other - as specified
Due 13 May 2025
Resolved 4 June 2025
Resolution: Cleared during Def Check on 04Jun25
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Loading instrument
Issued 13 February 2025 Resolved
Alternatively, pressure sensors may be fitted in each tank protected by the arrangements required in 1.2.2. PSCO observed inoperable tank pressure senors on 2p, 7s, % 9s. Vessel relies on pressure senors as alternative means under 74 SOLAS II-2/59.12. PSCO observed additional pressure senor on 5s/p defective. due 01Mar2025 IAW flag letter: RCS 13979-01-2025. 74 SOLAS (01) II-2/59.1.2.3.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 March 2025
Resolved 4 July 2025
Resolution: SUPPORTING DOCUMENTS ATTACHED TO MISLE.
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Other (cargo)
Issued 13 February 2025 Resolved
Each cargo tank of a tankship must be equipped with intrinsically safe high-level alarm and a tank overfill alarm. PSCO observed inoperable overfill alarm on 5p and high level and overfill alarm on 7p out on deck. Repair due in accordance with flag dispensation RCS 13979-01-277-2025. 46 CFR 39.2007(a)
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 March 2025
Resolved 4 June 2025
Resolution: Cleared on def check on 04Jun25
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 13 February 2025 Resolved
Electrical installations shall be such as to minimize the risk of fire and explosion from flammable product. PSCO observed high level/overfill sensor for cargo tank 11p with defective packing gland. 74 SOLAS (20) XII/10.1 IBC 10.1.2.1
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 13 February 2025
Resolved 13 February 2025
07 - Fire Safety › N/A - No Subsystem › Fire pumps and its pipes
Issued 31 January 2025 Resolved
THE ARRANGEMENT FOR PROVIDING FOAM SHALL BE CAPABLE OF DELIVERING FOAM TO THE ENTIRE CARGO TANK DECKS AREA. PSCO OBSERVED LEAK FROM FOAM LINE OF APPROX. 2 GALLONS/MINUTE UNDER MANIFOLD, LINE WAS FITTED WITH TEMPORARY REPAIR WHICH WAS NOT HOLDING. 74SOLAS(01) II-2/61.1
Condition: Damaged By Earlier Event
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 2 February 2025
15 - Safety Management Systems (ISM) › N/A - No Subsystem › Resources and personnel
Issued 31 January 2025 Resolved
Suitable instructions and component spares for testing and mainanence shall be provided. PSCO observed ships crew open heat detectors with heat gun. The authorized heat detector testing mechanisom requires a power supply not available on the vessel.
Condition: Improper Installation
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 2 February 2025
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 29 January 2025 Resolved
ELETRICAL EQUIPMENT, CABLES, AND WIRING SHALL NOT BE INSTALLED IN THE HAZARDOUS LOCATIONS UNLESS IT CONFORMS WITH THE STANDARDS NOT INFERIOR TO THOSE ACCEPTABLE TO THE ORGANIZATION. PSCO OBSERVED EXPOSED WIRING ON MULTIPLE TANK GAUGING SYSTEMS ON THE CARGO DECK, AND EXPOSED WIRING AT CABLE PENETRATION IN FRAMO POWER PACK ROOM. 74SOLAS(20)VII/10.1 IBC 10.1.4
Condition: Improper/Lack of Maintenance
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 2 February 2025
07 - Fire Safety › N/A - No Subsystem › Division - decks, bulkheads and penetrations
Issued 29 January 2025 Resolved
Where "A" class divisions are penetrated for the passage of electric cables, pipes, trunks, ducts, etc., or for girders, beams or other structural members, arrangements shall be made to ensure that the fire resistance is not impaired. PSCO observed multiple electrical cable penetrations through "A" class boundaries with missing or cracked insulation in the bridge electrical locker, the passage above the wheel house door, the cable trunk on the "C" deck, and the penetration leading into the wheelhouse from the port bridge wing. 74SOLAS(2001) II-2 18.1.1
Condition: Improper Installation
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 2 February 2025
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Loading instrument
Issued 29 January 2025 Resolved
Alternatively pressure sensors may be fitted in each tank with a monitoring system in the ship's cargo control room. PSCO observed inoperable tak pressure sensirs on 2P, 7S, & 9S. VSL relies on pressure sensors as alternative means under 74 SOLAS (01) II-2 / 59.1
Condition: Improper/Lack of Maintenance
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 2 February 2025
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Loading instrument
Issued 28 January 2025 Resolved
ALTERNATIVELY, PRESSURE SENSORS MAY BE FITTED IN EACH TANK WITH A MONITORING SYSTEM IN THE SHIPS CARGO CONTROL ROOM. PSCO OBSERVED ERRORS ON COT 10P, 11P 14P DISPLAY IN CCR ADDITIONALLY, AUDIBLE ALARMS TO THE SYSTEM HAVE BEEN SECURED LOCALLY DUE TO CONSTANT ALARMS. 74SOLAS(01)II-2/59.1.2.3
Condition: Improper/Lack of Maintenance
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 13 February 2025
Resolution: PSO witnessed the rectification of pressure alarms on COT 10p, 11p, & 14p in CCR.
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Other (cargo)
Issued 28 January 2025 Resolved
EACH CARGO TANK OF A TANKSHIP MUST BE EQUIPPED WITH AN INTRINSICALLY SAFE HIGH-LEVEL ALARM AND A TANK OVERFILL ALARM. PSCO OBSERVED INOPERABLE VISUAL HIGH-LEVEL ALARM AND TANK OVERFILL ALARM OUT ON DECK. 46CFR39.2007(a)
Condition: Invalid
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 13 February 2025
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Other (cargo)
Issued 28 January 2025 Resolved
SUITABLY MARKED DECONTAMINATION SHOWERS AND EYEWASH SHALL BE AVAILABLE ON DECK IN CONVENIENT LOCATIONS. THE SHOWERS AND EYEWASH SHALL BE OPERABLE IN ALL AMBIENT CONDITIONS. PSCO OBSERVED INADEQUATE PRESSURE OF THE SHOWER AND EYEWASH STATIONS. 74SOLAS(20)VII/10.1
Condition: Improper/Lack of Maintenance
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 13 February 2025
Resolution: PSCO observed adequate water pressure on all on deck shower and eyewash stations.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Other (load lines)
Issued 21 August 2024 Resolved
The ring, lines and letters shall be painted in white or yellow on a dark ground or in black on a light ground. They shall be permanently marked on the sides of the ships. PSCO observed starboard side plimsoll line was not painted. ICLLC REG. 8
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 23 August 2024
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Gauges, thermometers, etc
Issued 21 August 2024 Resolved
Measures shall be taken to the satisfaction of the Administration to ensure that the equipment is functioning in a reliable manner and that satisfactory arrangements are made for regular inspections and routine tests to ensure continuous reliable operations. PSCO observed inoperable engine gauge cluster on the starboard side main generator. 74 SOLAS(CONS. 2009)II-1/46.2
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 30 September 2024
Resolved 2 February 2025
11 - Life Saving Appliances › N/A - No Subsystem › Inflatable liferafts
Issued 21 August 2024 Resolved
Provisions shall be made for marking each liferaft with the name and port of registry of the ship to which is is to be fitted, in such a form that the ship identification can be changed at any time without opening the container. PSCO observed starboard liferaft did not display the name and port of registry of the vessel. 74 SOLAS(CONS. 2020)III/31.1.2.2, LSA Code 4.2.7.2
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 23 August 2024
11 - Life Saving Appliances › N/A - No Subsystem › On board training and instructions
Issued 21 August 2024 Resolved
On-board training in the use of the ship's life-saving appliances shall be given as soon as possible. PSCO observed Oiler was not familiar with use of anti-exposure suit. 74 SOLAS(CONS. 2020)III/19.4.1
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 23 August 2024
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 21 August 2024 Resolved
Each lifebuoy shall be marked in block capitals of the Roman alphabet with the name and port of registry of the ship on which it is carried. PSCO observed portside lifebuoy did not contain name and port of registry of the vessel and had inadequate retro-reflective material. 74 SOLAS(CONS. 2020)III/7.1.4
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 23 August 2024
15 - Safety Management Systems (ISM) › N/A - No Subsystem › Company responsibility and authority
Issued 21 August 2024 Resolved
In meeting these requirements, the company should ensure that... .2 any non-conformity is reported, with its possible cause, if known; .3 appropriate corrective action is taken. 02, 04, 05, 06, 07, 08, 09 deficiencies below provide objective evidence of a serious failure of the implementation of the ISM Code. An external audit report is recommended. 74 SOLAS(CONS. 2020)IX/3.1, ISM CODE 10
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 23 August 2024
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Operation of machinery
Issued 21 August 2024 Resolved
The electrical power available shall be sufficient to supply all thos services that are essential for safety in an emergency. PSOO observed #2 Start Air compressor was removed. According to ships diagrams was wired to emergency switch board. 74 SOLAS(Cons. 2004) II-1/43.2
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Resolved 23 August 2024
09 - Working and Living Conditions › 092 - Working Conditions › Ventilation (Working spaces)
Issued 21 August 2024 Resolved
Machinery Spaces of category A shall be adequately ventilated so as to ensure that when machinery or boilers therein are operating at full power in all weather condtions...During inspection of engine room, there was temporary ventilation to the BWTS. Class shall verify proper operation of BWTS without portable ventilation. 74 SOLAS(Cons. 2004)II-1/35
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 23 August 2024
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 21 August 2024 Resolved
For the purpose of adequately controlling cargo, cargo transfer systems shall be provided with...one stop valve capable of being manually operated on each tank filling and discharge line, located near tank penetration...PSCO observed during deck walk, a hydraulic oil leak near the #10 STBD FRAMO pump. Crew stated it was from the gauge area of the FRAMO. 74 SOLAS(Cons. 2020)II-2/4.1.1
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 23 August 2024
07 - Fire Safety › N/A - No Subsystem › Maintenance of Fire protection systems
Issued 21 August 2024 Resolved
Maintenance, testing and inspections shall be carried out based on the guidelines developed by the organization. PSCO observed a portable fire extinguisher near annex II locker had not been inspected since July but marked on SMS procedures as completed by crew. 74 SOLAS(CONS. 2020)II-2/2.2.1
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 23 August 2024
11 - Life Saving Appliances › N/A - No Subsystem › Stowage of rescue boats
Issued 25 March 2024 Resolved
The rescue baot embarkation and launching arrangements shall be such that the rescue boat can be boarded and launched in the shortest time possible. PSCO observed inoperable rescue boat davit. See Panama Flag Dispensation SEG-067568. 74SOLAS(01) III/17.1 40AC
Condition: Improper/Lack of Maintenance
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 16 June 2024
Resolution: Rescue boat davit installation was fixed and load tested to the satisfaction of the attending surveyor.
07 - Fire Safety › N/A - No Subsystem › Fire pumps and its pipes
Issued 25 March 2024 Resolved
Fire fighting systems appliances shall be kept in working order and readily availible for immediate use. PSCO observed pin hole leak on fire main supply pipe to fire hydrant on port bridge wing. 74SOLAS(14)II-2/14.2.1.2 40ac
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 16 June 2024
Resolution: Section of fire line approx 3 m has been replace3d with a new one and fire pump tested with no anomolies.
09 - Working and Living Conditions › 092 - Working Conditions › Safe means of access Deck - hold/tank, etc.
Issued 25 March 2024 Resolved
Every tanker shall be provided with the means to enable the crew to gain safe access to the bow even in severe weather conditions. PSCO observed excessivly wasted deck grating near midship deck crane. 74SOLAS(01) II-1/3-3.2 40ac
Condition: Improper/Lack of Maintenance
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 16 June 2024
Resolution: Wasted deck gratings on the walk way have been replaced with new gratings and found generally in order per class surveyor.
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Cargo operation
Issued 29 January 2024 Resolved
The venting arrangements shall be so designed and operated as to ensure that neither pressure nor vacuum in cargo tanks shall exceed design parameters and be such as to provide for: alternatively, pressure sensors may be fitted in each tank protected by the arrangement required in 1.2.2, with a monitoring system in the ship's cargo control room or the position from which cargo operations are normally carried out. PSCO observed non-operational audible alarm for cargo tank pressure sensors.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 29 January 2024
Resolution: After hours of trouble shooting, crew was able to satisfactorily demonstrate to PSCOs audible alarms for Cargo pressures in CCR.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 29 January 2024 Resolved
Unless expressly provided otherwise or unless, in the opinion of the Administration having regard to theparticular voyages on which the ship is constantly engaged, other requirements are appropriate, all life-savingappliances prescribed in this part shall: early marked with approval information including the Administration which approved it, andany operational restrictions; PSCO observed lifejackets missing approval markings.
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Resolved 8 February 2024
Resolution: Received survey report and verified CG and SOLAS approval for 31 lifejackets and lights.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 29 January 2024 Resolved
The condition of the ship and its equipment shall be maintained to conform with the provisions of the present regulations to ensure that the ship in all respects will remain fit to proceed to sea without danger to the ship or persons on board. PSCO's observed significant wastage and leaks on the following systems: hydraulic return line above tanks 12 & 13, cargo steam line above tank 6, main cargo common line at port manifold.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 8 February 2024
Resolution: Received survey report and verified satisfactory repairs. Observed NDT report.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Railing, gangway, walkway and means for safe passage
Issued 29 January 2024 Resolved
Satisfactory means (in the form of guard rails, life lines, gangways, or underdeck passages,) shall be provided for the protections of the crew in getting to and from their quarters, the machinery space and all other parts used in the necessary work of the ship. PSCO observed the STBD aft P/V bank deck grating severely corroded.
Condition: Improper/Lack of Maintenance
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 8 February 2024
Resolution: Received survey report and verified corroded deck plating replaced.
09 - Working and Living Conditions › 091 - Living Conditions › Sickbay
Issued 29 January 2024 Resolved
The Secretary may order any vessel, in a port or place subject to the jurisdiction of the United States or in the navigable waters of the United States, to operate or anchor in a manner the Secretary directs if - (1) the Secretary has reasonable cause to believe such vessel does not comply with any regulation issued under section 70034 or any other applicable law or treaty; (2) the Secretary determines such vessel does not satisfy the conditions for port entry set forth in section 70021 or 70022 of this title; or (3) by reason of weather, visibility, sea conditions, port congestion, other hazardous circumstances, or the condition of such vessel, the Secretary is satisfied such direction is justified in the interest of safety. PSCO observed insufficient hot water supply to the hospital space. (Approximately 1 gallon per mintue). A very slow pour from faucet and one small nozzle of the shower was passing water. The superintendant was storing his luggage in the hospital space as well.
Condition: Improper/Lack of Maintenance
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 29 January 2024
Resolution: PSCO Observed the the correction of the hospital hot water by the ship crew. Verified the operation and flow of hot water. Witnessed the removal of stowed luggage.
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 18 December 2022 Resolved
The purpose of this regulation is to prevent the ignition of combustible materials or flammable liquids. For this purpose, the following functional requirements shall be met: means shall be provided to control leaks of flammable liquids. PSCO observed three high pressure fuel pumps on the main diesel engine leaking fuel oil, also the #3 high pressure fuel line, as well as a substantial accumulation of MGO on the main engine. 74SOLAS(01)II-2/15.4
Action required: 10 - Deficiency Rectified
Resolved 18 December 2022
Resolution: Class society (RINA) verified and attested to the fuel leaks on the main diesel were repaired.

Ownership record

The Coast Guard's documentation record for this hull -- the Abstract of Title, with its owners and liens as filed -- is not in PSIX. Ask, and Maury buys it from the National Vessel Documentation Center, files it here with its date, and every reader of this page gets it.