RUTH E HUGHES

RUTH E HUGHES is a 1990 passenger vessel (inspected). The Coast Guard has recorded 94 inspections since 2016, most recently in February 2026, along with 46 deficiencies, 1 operational control and 7 casualty investigations between 2006 and 2019.

Records from 2006 to 2026. Most recent: inspection, 10 February 2026.

Built
1990
Last inspected
10 February 2026
Documentation
Valid · documentation file of 10 August 2026
Controls
None recorded without a removal date

Coast Guard record current through 23 August 2026, retrieved 5 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Passenger Ship class in Maury's sources begin in 2016.

Inspection record

Last inspected 10 February 2026
…with no type recorded57
Operational controls None recorded without a removal date
Years with a record 11 calendar years (2016–2026)
Every line above is a count of records the US Coast Guard wrote, or a date it recorded. A blank resolution means none was recorded in this data; it does not establish that a deficiency is outstanding. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Identity

WCY8367
347418
Flag
UNITED STATES
Maury page id
psix-347418

Documentation record

Registered dimensions (L × B × D)100.7 ft × 24.0 ft × 7.9 ft
Registered tonnagegross 97 / net 66
ITC dimensions (L × B × D)100.7 ft × 24.0 ft × 7.9 ft
ITC tonnagegross 247 / net 106
BuilderSTEINER SHIPYARD, INC. · BAYOU LA BATRE, AL, UNITED STATES · built 1990
Hull materialAluminum
PropulsionDiesel Reduction
Hull shapeUNSPECIFIED
Hull configurationUNSPECIFIED
Hailing portBOSTON, MA
Trade endorsementsCoastwise, unrestricted
DocumentationValid · issued 6 August 2025 · expires 30 September 2026
Service, as the file records itPassenger (Inspected)
Hull formpowered (Maury's inference from propulsion, hull shape, material and length, rule hf-1; not a recorded fact)
Tonnage as PSIX records it247 - Convention (Subpart B), Gross Ton
97 - Regulatory (Subpart C or D), Gross Ton
106 - Convention (Subpart B), Net Ton
66 - Regulatory (Subpart C or D), Net Ton
Every line above is a field of the National Vessel Documentation Center's file as served by NOAA Fisheries, dated 10 August 2026, matched to this hull on its Official Number. Registered and ITC measurements are two systems and are never combined. One snapshot is held so far; documentation history begins with the next.
Vessel history report
Every record for this hull, in one document — $299

Every recorded inspection, 2016 to 2026 for this class, in one chronology · every deficiency, with system, dates and resolution · operational controls imposed and removed · every name this hull has been recorded under · the vessels it was inspected alongside, and when · how its record compares with hulls of similar age and size, as a fact about the population and never a judgement about this vessel.

Read one first, in full: a forty-year chronology · a hull that changed operators four times · the sparse case, shown as an example, not for sale.

This report is in development and is not for sale yet. There is no date, and nothing is charged. Leave an email and we will tell you when it exists, once.

Inspection history · 94

10 February 2026 Internal Structural Exam · Vessel Attendance · Hull Examination
Physical examination · Sector Southeastern New England · USCG Northeast District (CGD-NE) · Activity 8308963
8 January 2026 Damage Survey
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 8294624
8 December 2025 Vessel Attendance · Damage Survey
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 8278960
19 November 2025 Internal Structural Exam · Annual Inspection · MTSA Verification
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 8265201
1 July 2025 In-Service Inspection · Deficiency Check
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 8172175
2 April 2025 Administrative Inspection
Administrative · Sector Boston · USCG Northeast District (CGD-NE) · Activity 8104304
10 December 2024 Annual Inspection · Deficiency Check · Internal Structural Exam
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 8042492
16 October 2024 Deficiency Check · In-Service Inspection
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 8019995
5 June 2024 In-Service Inspection · Administrative Inspection
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 7929220
25 January 2024 Examination of Repairs · Internal Structural Exam · Hull Examination · Administrative Inspection
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 7851075
25 October 2023 Deficiency Check
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 7814458
10 October 2023 Internal Structural Exam · Deficiency Check · COI Inspection
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 7799406
13 September 2023 Examination of Repairs · Damage Survey
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 7789594
27 April 2023 In-Service Inspection
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 7676764
18 January 2023 Administrative Inspection
Administrative · Sector Boston · USCG Northeast District (CGD-NE) · Activity 7598291
30 November 2022 Internal Structural Exam · Annual Inspection
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 7590512
24 March 2022 Administrative Inspection · Deficiency Check
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 7417887
21 January 2022 Hull Examination · Deficiency Check · Internal Structural Exam
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 7382542
17 November 2021 Annual Inspection
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 7344131
9 September 2021 In-Service Inspection
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 7308060
8 January 2021 Annual Inspection · Deficiency Check
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 7121673
7 January 2021 Deficiency Check · Administrative Inspection
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 7120967
13 March 2020 Damage Survey · Deficiency Check
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6927592
13 March 2020 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6928935
24 February 2020 Deficiency Check
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6914533
11 February 2020 Drydock Exam · Deficiency Check
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6906238
28 January 2020 Drydock Extension
Administrative · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6897836
8 January 2020 MTSA Verification · Deficiency Check · Annual Inspection
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6884527
10 December 2019 Administrative Inspection
Administrative · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6870965
14 November 2019 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6856393
25 October 2019 Administrative Inspection
Administrative · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6841790
16 January 2018 Plan Review (Other than "T") · COI Inspection · Construction Oversight · Administrative Inspection · DAPI Audit · MTSA Verification · Inclining Experiment
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6340481
11 October 2017 Hull Examination · Construction Oversight
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6286046
19 August 2017 Deficiency Check · Damage Survey
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6247106
19 August 2017 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6247275
3 July 2017 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6196398
3 July 2017 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6196403
22 June 2017 Type not recorded
No type recorded · Base Support Unit Boston · Activity 6183517
22 June 2017 Type not recorded
No type recorded · Base Support Unit Boston · Activity 6183589
23 May 2017 Deficiency Check · MTSA Verification · COI Inspection
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6152466
17 April 2017 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6126828
17 April 2017 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6126831
17 April 2017 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6126836
17 April 2017 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6126841
17 April 2017 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6126844
17 April 2017 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6126848
20 January 2017 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6074010
20 January 2017 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6074085
20 January 2017 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6074234
20 January 2017 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6074279
25 November 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6047404
25 November 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6047411
16 November 2016 Deficiency Check · Administrative Inspection
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6042120
3 November 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6035100
3 November 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6035104
3 November 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6035118
3 November 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6035122
1 September 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5989580
1 September 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5989592
13 July 2016 MTSA Verification · Annual Inspection
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5939483
16 June 2016 Examination of Repairs
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5910026
2 June 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5894967
2 June 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5894977
18 April 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5857248
18 April 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5857251
18 April 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5857252
18 April 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5857253
15 April 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5855318
15 April 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5855320
15 April 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5855321
15 April 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5855322
15 April 2016 Administrative Inspection · Deficiency Check
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5858311
16 February 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5816348
16 February 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5816356
16 February 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5816358
16 February 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5816361
11 February 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5813871
11 February 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5813880
11 February 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5813887
11 February 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5813889
9 February 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5813197
9 February 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5813198
9 February 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5813199
9 February 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5813200
3 February 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5808643
3 February 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5808651
3 February 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5809332
3 February 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5809333
3 February 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5809334
3 February 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5809335
2 February 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5808490
2 February 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5808492
2 February 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5808496
2 February 2016 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 5808497

Deficiency record · 46

13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 8 January 2026 Resolved
All machinery shall be installed and maintained in such a manner as to afford adequate protection against fire, explosion, machinery failure and personnel injury. At the time of inspection, the vessel was found to have exhaust leaks on each of the vessel's four Main Diesel Engines. Operator to rectify within 30 days to the satisfaction of the attending Marine Inspector. 46CFR182.01-5
Action required: 50 - Rectify deficiencies w/in 30 days
Due 8 February 2026
Resolved 21 January 2026
Resolution: Received satisfactory video from operator of vessel's main diesel engines running with the new exhaust elbow pieces installed. No discernable exhaust leaks were observed. Deficiency cleared.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 8 December 2025 Resolved
Rudder angle indicator has not functioned in several months. Repair rudder angle indicator or provide an equivalent level of safety prior to the carriage of passengers.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 12 December 2025
Resolution: Rudder angle indicator tested satisfactorily.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 8 December 2025 Resolved
The steering pump indicator lights on the bridge have been covered with electrical tape impeding the visibility of the lights. Remove tape (if lights are too bright, replace with less intensity bulbs or cover with a darker lens) prior to the carriage of passengers.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 12 December 2025
Resolution: Steering pump indicator lights tested for both pumps and observed uncovered.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 19 November 2025 Resolved
Portable fuel systems, including portable tanks and related fuel lines and accessories, are prohibited except where used for portable dewatering pumps or outboard motor installations. Portable red gasoline tank filled with diesel observed stored in crew storage closet in lower-deck passenger accommodation, and not intended for portable dewatering pumps or outboard motors. 46 CFR 119.458
Action required: 10 - Deficiency Rectified
Resolved 19 November 2025
Resolution: Portable fuel tank removed and stored shoreside.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 10 December 2024 Resolved
All vessels shall be provided with a satisfactory arrangement for draining any watertight compartment other than small buoyancy compartments, under all practical conditions. The bilge pick-up pipe in the forepeak has a hole in it. Repair pipe to the satisfaction of the attending marine inspector.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 24 December 2024
Resolved 13 December 2024
Resolution: Operator replaced wasted pipe.
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 10 December 2024 Resolved
Every vessel subject to Part III of Title III of the Communications Act must have a detailed inspection of the radio installation by an FCC-licensed technician in accordance with § 80.59 once every five years. The vessel is equipped with an EPIRB, but the vessel's Safety Radiotelephony Certificate does not have the EPIRB box checked. Have a FCC licensed technician re-issued certificate.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 24 December 2024
Resolved 13 January 2025
Resolution: Vessel received updated certificate
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 16 October 2024 Resolved
For semiportable and fixed gas fire extinguishing systems, the inspections and tests required by Table 115.810(b). The owner or managing operator shall provide satisfactory evidence of the required servicing to the marine inspector. While witnessing the annual servicing of the vessel's fixed gas fire extinguishing system (FFS) by a certified technician, the main stop valve failed twice to operate both through the time delay and manually, preventing the testing agent (carbon dioxide) to flow into it's designated space (engine room). The system must be repaired, re-tested, and documents provided showing that the repair were conducted IAW manufacturers manual. Vessel is authorized to conduct a 01 time transit from Long Wharf gate 4 to Cashman Yard in Quincy to conduct/enact repairs. 46 CFR 115.810(b)(2)
Action required: 705 - Other - as specified
Due 1 June 2025
Resolved 1 July 2025
Resolution: New installation of CO2 FFS inspected by attending marine inspector. Halon system no longer on board.
07 - Fire Safety › N/A - No Subsystem › Ready availability of fire fighting equipment
Issued 16 October 2024 Resolved
System components must be listed and labeled by an independent laboratory. A component from a different system, even if from the same manufacturer, must not be used unless included in the approval of the installed system. During annual servicing of FFS, it was observed that the system charged indicator did not operator for 02 tests. Indicator must be addressed & re-tested. 46 CFR 118.410(a)(2)
Action required: 705 - Other - as specified
Due 1 May 2025
Resolved 1 July 2025
Resolution: New installation of CO2 FFS inspected by attending marine inspector. Halon system no longer on board.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 25 October 2023 Resolved
For semiportable and fixed gas fire extinguishing systems, the inspections and tests required by Table 115.810(b). Halon-1301, recharge or replace with if weight loss exceeds 5 percent. Fire technician stated the system had lost more than 5 percent of cylinder weight and did not contain enough agent to extinguish an engine room fire. Refill tank or replace with an approved system to the satisfaction of the attending marine inspector. If refilled the following conditions must be met: 1. Provide latest servicing report from 25Oct23. 2. Provide information on company providing the agent and refilling the bottle. 3. Replace tank fittings and pressure gauge. 4. System service must be conducted after initial refill to ensure no leaks and serviceable condition by a qualified technician in the presence of marine inspector. 5. After initial refill, system must be serviced once every three months by a qualified technician in the presence of a marine inspector or until system is replaced.
Action required: 701 - Prior to carriage of passengers/cargo
Due 25 October 2023
Resolved 21 November 2023
Resolution: Vessel operator submitted fire technician report stating halon system is serviceable.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 13 September 2023 Resolved
The construction and arrangement of a vessel must allow the safe operation of the vessel in accordance with the terms of its Certificate of Inspection. Outboard skin of port rudder was peeled back due to weld failure. Renew plate and test weld.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 30 September 2023
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 8 January 2021 Resolved
Each floating water light must have a lanyard of at least 3' but not more than 6' securing the waterlight around the body of the ring life buoy. Water light is not properly attached.
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 22 January 2021
Resolved 12 January 2021
Resolution: Recieved email picture of ring buoy light installation, cleared deficiency on the ring buoy light.
02 - Structural Conditions › N/A - No Subsystem › Stability/strength/loading information and instruments
Issued 8 January 2021 Resolved
Vessel must have permanently marked draft marks at each end of the vessel. Vessel has no visible draft marks. 46 CFR 185.30-3(b) Due NLT next DD. 31JAN2022.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 22 January 2021
Resolved 21 January 2022
Resolution: Draft marks were welded and painted onto vessel's hull.
02 - Structural Conditions › N/A - No Subsystem › Bulkhead -corrosion
Issued 8 January 2021 Resolved
Machinery spaces shall be separated from other spaces by a watertight bulkhead. Small hole on aft watertight bulkhead of engine room. Temp repair approved. permanent repair NLT next DD 31JAN2022.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 22 January 2021
Resolved 21 January 2022
Resolution: Penetration in bulkhead has been repaired.
07 - Fire Safety › N/A - No Subsystem › Fire pumps and its pipes
Issued 8 January 2020 Resolved
All piping, valves, and fittings shall be in accordance with good marine practice and suitable for the purpose intended. In the #2 void, the fire main leading to the forward fire station has a severe leak at the coupling at the deck penetration. Make permanent repairs to the fire main.
Condition: Damaged By Earlier Event
Action required: 30 - Ship detained
Resolved 10 January 2020
Resolution: Replaced fire main section going through deck to forward fire station.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 8 January 2020 Resolved
Each length of hose must have a nozzle that has a ½” solid stream orifice or a combination nozzle approved by the Commandant in accordance with 46 CFR 162.027-6. The fire hose nozzle at the aft station does not have the ability to spray a straight stream, and is in poor condition.
Condition: Damaged By Earlier Event
Action required: 30 - Ship detained
Resolved 13 January 2020
Resolution: Verified nozzle could adjust stream from fog to jet.
07 - Fire Safety › N/A - No Subsystem › Fire-dampers
Issued 8 January 2020 Resolved
In all ventilation systems, manually operated dampers shall be provided in accessible locations, outside the spaces served by the system for shutting off the passage of air in the event of fire. The port and starboard aft dampers would not close using the manual pull.
Condition: Damaged By Earlier Event
Action required: 30 - Ship detained
Resolved 10 January 2020
Resolution: Bolted on new hinge to starboard fire damper, tested both aft dampers and operated correctly
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 8 January 2020 Resolved
Recharge or replace if weight loss exceeds 5% of the weight of the charge or if cylinder has a pressure gauge, recharge cylinder if pressure loss exceeds 10%, adjusted for temperature. The gauge on the halon cylinder is below 10% and does not match what is recorded on the last servicing certificate from November 2019.
Condition: Damaged By Earlier Event
Action required: 30 - Ship detained
Resolved 14 January 2020
Resolution: Halon Cylinder weighed with calibrated scale at 217.5 lbs total gross weight, within the 5% loss of agent weight.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 8 January 2020 Resolved
Complete but simple instructions for the operation of a fixed gas fire extinguishing system must be located in a conspicuous place in the space where the extinguishing agent cylinders are stored. The instructions posted at the halon station are insufficient as the valves are not numbered or identified.
Condition: Damaged By Earlier Event
Action required: 30 - Ship detained
Resolved 13 January 2020
Resolution: Verified correct manual fixed fire system instruction posted.
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 8 January 2020 Resolved
All escape hatches and other emergency exits used as means of escape must be marked on both sides. The emergency escape from the engine room was not marked.
Condition: Damaged By Earlier Event
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 10 January 2020
Resolution: New emergency escape label placed on bulkhead directly below the emergency escape.
05 - Radio Communications › N/A - No Subsystem › Distress messages: obligations and procedures
Issued 8 January 2020 Resolved
A durable placard must be posted next to all radio telephone installations with the emergency broadcast instructions and information. Vessel did not have placard posted.
Condition: Damaged By Earlier Event
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 13 January 2020
Resolution: Raidio broadcast instructions posted
01 - Certificates & Documentation › 013 - Documents › Stability Information Booklet
Issued 8 January 2020 Resolved
The stability letter must be posted under glass or other suitable transparent material at the operating station. The current stability letter was not posted.
Condition: Damaged By Earlier Event
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 13 January 2020
Resolution: Verified current stability letter posted near the operating station
05 - Radio Communications › N/A - No Subsystem › Operation/maintenance
Issued 8 January 2020 Resolved
Each EPIRB must be tested monthly and shall be logged or otherwise documented. EPIRB testing was not logged.
Condition: Damaged By Earlier Event
Action required: 10 - Deficiency Rectified
Resolved 8 January 2020
Resolution: Instructed captain to start logging EPIRB test.
01 - Certificates & Documentation › 012 - Crew Certificates › Manning specified by the minimum safe manning doc
Issued 8 January 2020 Resolved
The movement of a vessel shall be under the direction and control of the master or a licensed mate at all times. The vessel’s COI allows for a licensed mate to be substituted by a senior deckhand that is designed in writing. The senior deckhand was not designated in writing upon start of inspection.
Condition: Damaged By Earlier Event
Action required: 10 - Deficiency Rectified
Resolved 8 January 2020
Resolution: BHC produced a new senior deck hand letter
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 8 January 2020 Resolved
All vessels must be provided with bilge pumps in accordance with Table 182.25-10(a). The primary bilge pump was inoperable, but was repaired during the inspection.
Condition: Damaged By Earlier Event
Action required: 10 - Deficiency Rectified
Resolved 8 January 2020
Resolution: BHC Electrician rewired breaker panel
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 11 October 2018 Resolved
Engine room means of escape needs to be labeled IAW CRF. Label means of escape from engine room.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 25 October 2018
Resolved 25 October 2018
Resolution: Installed sign as requiered
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 11 October 2018 Resolved
Engine room means of escape needs to have emergency light IAW CRF. Provide emergency light for means of escape from engine room.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 25 October 2018
Resolved 25 October 2018
Resolution: Emergency lighting IWO emergency escape from engine room installed and tested sat.
01 - Certificates & Documentation › 013 - Documents › Signs, indications
Issued 11 October 2018 Resolved
Upper deck max pax should be labeled at all access points. No sign indicating max pax on upper deck aft access.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 25 October 2018
Resolved 25 October 2018
Resolution: Upper deck aft max pax capacity labeled
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 11 October 2018 Resolved
Fixed fire ext. system must be hydrostaticly tested as required. No date of last hydro available.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 25 October 2018
Resolved 25 October 2018
Resolution: Met requirements for testing HALON system as per NFPA.
02 - Structural Conditions › N/A - No Subsystem › Stability/strength/loading information and instruments
Issued 11 October 2018 Resolved
Vessel required to have draft marks. No draft marks are permanently affixed on vessel. Permanently mark draft marks as required NLT next DD 31JAN2020
Action required: 705 - Other - as specified
Due 31 January 2020
Resolved 14 February 2020
Resolution: Verified that draft marks were properly installed.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 11 October 2018 Resolved
DC12 panel in PH breaker to VHF, Flux, radio and GPS do not match the approved drawing. make correction and get approval from MSC
Action required: 50 - Rectify deficiencies w/in 30 days
Due 8 November 2018
Resolved 25 October 2018
Resolution: Corrected installation to match approved drawing.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 11 October 2018 Resolved
120VAC panel in ER has breaker to sub panel in PH new installation that does not match the approved drawing. Make corrections and get approval from MSC
Action required: 50 - Rectify deficiencies w/in 30 days
Due 8 November 2018
Resolved 25 October 2018
Resolution: Corrected drawing and got approval from MSC
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 11 October 2018 Resolved
Spec sheets for new instalation of equipment for propulsion control need final approval from MSC. submit and get approval from MSC
Action required: 50 - Rectify deficiencies w/in 30 days
Due 8 November 2018
Resolved 25 October 2018
Resolution: Provided specification sheets for all new installed gear and recieved approval from MSC. Verified installation matched submision documents.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 11 October 2018 Resolved
DRW 320-03 Rev C needs revision to show installation of disconect switch prior to 10A fuse to MDE stops. Make corrections and get approval from MSC
Action required: 50 - Rectify deficiencies w/in 30 days
Due 8 November 2018
Resolved 25 October 2018
Resolution: Provided reviced, approved drawing.
11 - Life Saving Appliances › N/A - No Subsystem › Inflatable liferafts
Issued 16 January 2018 Resolved
Each vessel inspected and certificated under the provisions of Subchapter K must be in full compliance with the terms of the certificate. Vessel has removed its IBA for servicing and is limited to a route 1nm from shore until the raft is onboard and properly installed.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 13 September 2018
Resolved 11 October 2018
Resolution: Verified proper installation of authorized IBA
Construction/Loadline › Hull › Hull Plating
Issued 19 August 2017 Resolved
Crop and renew hull in way of puntured area, void #3, port side.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 21 August 2017
Resolution: New plate approx 20" x 20" was welded to existing hull plating.
Engineering › Bilge Water Management System › Piping
Issued 23 May 2017 Resolved
#4 bilge piping failed to pump water from compartment. Prove proper operation of bilge system.
Action required: 701 - Prior to carriage of passengers/cargo
Due 24 May 2017
Resolved 24 May 2017
Resolution: Vessel removed clog from piping and renewed the check valve and adjacent piping. #4 void bilge system sucessfully pumped water overbaord.
Pollution Prevention/Response › Prevention Equipment › Sewage System Piping
Issued 23 May 2017 Resolved
Discovered wasted piping on supply water and discharge line for the starboard head. Repair holed piping.
Action required: 705 - Other - as specified
Due 16 June 2017
Resolved 15 June 2017
Resolution: Vessel rep repaired piping.
Fire Fighting › Miscellaneous Items › Insulation (Penetration of Oil/Oil Vapors)
Issued 23 May 2017 Resolved
Numerous failures of structural fire protection insulation throughout the engine room. Make repairs with approved materials.
Action required: 705 - Other - as specified
Due 16 June 2017
Resolved 15 June 2017
Resolution: SFP was repaired.
Operations/Management › Drills/Instruction › Fire
Issued 23 May 2017 Resolved
Halon discharge instructions were damaged and unreadable. Provide Halon discharge instructions.
Action required: 705 - Other - as specified
Due 6 June 2017
Resolved 24 May 2017
Resolution: Vessel provided new instructions and posted them.
Engineering › Compressed Air System (control) › Compressor
Issued 23 May 2017 Resolved
Cracked welds were found on the air receiver where the compressor mounts. Make repairs and re-weld.
Action required: 705 - Other - as specified
Due 16 June 2017
Resolved 15 June 2017
Resolution: Mounts were repaired.
Fire Fighting › Portable Dry Chemical Fire Extinguisher › Service
Issued 23 May 2017 Resolved
Extinguisher was found un-serviced. conduct annual servicing.
Action required: 705 - Other - as specified
Due 16 June 2017
Resolved 15 June 2017
Resolution: Extingusher was serviced.
Construction/Loadline › Penetrations › Gasket
Issued 23 May 2017 Resolved
Steering compartment hatch was found without a gasket installed. Intall gasket and make hatch water tight. 46 CFR 116.1160
Action required: 705 - Other - as specified
Due 16 June 2017
Resolved 15 June 2017
Resolution: Gasket was replaced.
Engineering › Lubricating Oil Service System › Gauge
Issued 23 May 2017 Resolved
Bridge STBD Aft propulsion engine's lube oil pressure gauge was inoperable. Prove proper opeeration of guage. 46 CFR 182.20-5
Action required: 705 - Other - as specified
Due 16 June 2017
Resolved 15 June 2017
Resolution: Gauge was working properly.
Lifesaving › Inflatable Buoyant Apparatus › Servicing
Issued 16 November 2016 Resolved
The vessel's 100-person IBA has been removed for annual servicing. The vessel is limited to operations not more than one nautical mile from shore until the IBA has been re-installed to the satisfaction of an attending marine inspector.
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 16 December 2016
Resolved 13 December 2016
Resolution: Inspected re-installation of IBA - sat.
Engineering › Compressed Air System (control) › Receiver/Bottle
Issued 13 July 2016 Resolved
Make pressure vessel available for internal inspection.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 12 August 2016
Resolved 10 August 2016
Resolution: Pressure vessel internal inspection complete. All sat.
Operations/Management › Equipment Service/Testing › EPIRB
Issued 15 April 2016 Resolved
Vessel is restricted to three miles from shore until EPIRB is returned from servicing.
Action required: 705 - Other - as specified
Due 29 April 2016
Resolved 22 April 2016
Resolution: Returned EPIRB after being properly serviced.Vessel no linger resitricted to 3 miles.

Casualty record · 7

12 June 2006Major Marine Casualty · role: Transiting Vicinity of Primary Subject · serious marine incident, as classified · activity 2678071
10 July 2007Routine · role: Involved in a Marine Casualty · serious marine incident, as classified · activity 2990497
27 February 2013Routine · role: Involved in a Marine Casualty · activity 4540461
5 August 2013Routine · role: Transiting Vicinity of Primary Subject · 1 injured · activity 4705733
31 March 2015Routine · role: Involved in a Marine Casualty · activity 5095457
19 August 2017Routine · role: Involved in a Marine Casualty · activity 6247275
14 November 2019Routine · role: Involved in a Marine Casualty · serious marine incident, as classified · 1 injured · activity 6856393
Each line is an incident investigation the Coast Guard recorded with this hull among the vessels involved, with the date and the classification the Coast Guard gave it. Involvement is not fault. The investigation narrative is not published. Source: IIR, through 2026.

Recorded names · 1

LAURA (2006–2007). Names as the Coast Guard recorded them in incident records, with the years they appear; some are renames and some are spelling variants.

Ownership record

The Coast Guard's documentation record for this hull -- the Abstract of Title, with its owners and liens as filed -- is not in PSIX. Ask, and Maury buys it from the National Vessel Documentation Center, files it here with its date, and every reader of this page gets it.