07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 9 December 2025
No resolution recorded
Controls [for fixed CO2 systems] shall be installed in an accessible location outside the space protected.
Pressure switches were installed inside the protected engine room space. System modification to be addressed IAW decision from Marine Safety Center (MSC) and prior
2026 hull credit. 46 CFR 181.20-10(b)(3)
Action required: 705 - Other - as specified
Due 9 December 2025 — due date passed with no resolution recorded
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 9 December 2025
Resolved
The general construction of the vessel shall be such as to minimize fire hazards insofar as reasonable and practicable. Vessels contracted for on or after July 1, 1961, which carry more than 150 passengers shall meet the requirements of subpart 72.05 of Subchapter H. Doors in bulkheads required to be Class A-60, A-30, or A-15 shall be of hollow steel in equivalent metal construction solidly filled with approved structural insulation capable of meeting the requirements for a class A-15 bulkhead. Engine room door could not be confirmed to meet A-15 fire boundary. Replace door to satisfaction of attending marine inspector and prior to 2026 hull credit. 46 CFR 177.10-5, 46 CFR 72.05-25.
Action required: 705 - Other - as specified
Due 9 December 2025
Resolved 6 March 2026
Resolution: Inspected engine room fire door and found consistent construction with fire doors in other boundaries. Domestic fire doors do not require type approval. Door appears to be two 1.5mm steel panels with insulation between and are original to the construction
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 25 November 2025
Resolved
At each initial and subsequent inspection for certifications and reinspection the firefighting equipment of all vessels shall be inspected and all deficiencies found shall be corrected. Complete and simple instructions must be located in a conspicuous place at or near all pull boxes, stop valve controls and in the CO2 cylinder storage room. On systems in which the CO2 cylinders are not within the protected space, these instructions must also include a schematic diagram of the system and instructions detailing alternate methods of discharging the system should the manual release or stop valve controls fail to operate. Marine Inspector observed failed pressure switches indicated on inspection report from Fire Equipment Inc dated 29Oct2025. Comments on the report stated pressure switches did not shut down main engines. Owner/operator to conduct additional servicing/testing of the system to verify pressure switches shut down vessel’s main diesel engines to the satisfaction of attending Marine Inspector. Provide system drawings and schematics for on board system. 46 CFR 176.25-25(Old T),
46 CFR 181.20-15(Old T)
Action required: 701 - Prior to carriage of passengers/cargo
Due 25 November 2025
Resolved 9 December 2025
Resolution: Fire technician performed necessary tests. Pressure switches operating satisfactory. Instuctions and schematics posted in proper locations.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 25 November 2025
Resolved
The construction and arrangement of a vessel must allow the safe operation of the vessel in accordance with the terms of its COI giving consideration to provisions for a seaworthy hull. Several areas of localized pitting was found in the #2 void port side forward. O/O to submit a temporary repair proposal to cognizant [name withheld] temp repair within 14 days. Permanent repairs are to then be made prior to next credit hull exam.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 9 December 2025
Resolved 8 April 2026
Resolution: Coating accepted to arrest further corrosion. Continued monitoring at annual ISEs.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 25 November 2025
Resolved
The construction and arrangement of a vessel must allow the safe operation of the vessel in accordance with the terms of its COI giving consideration to provisions for a seaworthy hull. Areas of corrosion and wastage were found in the way of the starboard blackwater watertight bulkhead penetration. O/O to submit repair proposal to cognizant [name withheld] repairs are to then be made prior to next credit hull exam. 46 CFR 182.40-1
Action required: 705 - Other - as specified
Due 25 November 2025
Resolved 30 March 2026
Resolution: Two inserts installed and inspected satisafactorily.
02 - Structural Conditions › N/A - No Subsystem › Steering gear
Issued 25 November 2025
Resolved
All vessels shall be provided with a suitable steering apparatus. Vessel’s starboard rudder hydraulic actuator leaking hydraulic fluid. O/O to repair/replace hydraulic actuator prior to receiving next credit hull exam. 46 CFR 182.30-1.
Action required: 705 - Other - as specified
Due 25 November 2025
Resolved 8 April 2026
Resolution: Hydraulic actuator renewed and tested.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 25 November 2025
Resolved
All vessels shall be provided with a satisfactory arrangement for draining any watertight compartment. Vessel’s bilge pick up pipe right after strainer in #6 void and bilge line coupling in #3 void near forward bulkhead was heavily wasted. O/O to repair/replace bilge pick up lines to satisfaction of attending marine inspector prior to receiving credit hull exam. 46 CFR 182.25-1
Action required: 705 - Other - as specified
Due 25 November 2025
Resolved 8 April 2026
Resolution: Descaled bilge pipe and tested. Current condition accepted.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Other (load lines)
Issued 25 November 2025
Resolved
Penetrations of required watertight decks and bulkheads are prohibited except when each penetration is accomplished using an acceptable metal fitting, welded or otherwise attached to bulkhead by accepted methods, and an acceptable metallic shutoff valve is installed adjacent to the through hull fittings. Blackwater lines penetrating watertight bulkhead between void #6 and lazarette to be fitted with metallic shutoff valves. O/O to submit repair proposal to cognizant OCMI detailing inclusion of metallic shut off valves to the piping system, prior to receiving next credit hull exam.
46 CFR 182.40-1
Action required: 705 - Other - as specified
Due 25 November 2025
Resolved 8 April 2026
Resolution: Piping renewed and metalic shutoff valve installed at MTWB.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 25 November 2025
Resolved
The owner, managing operator, or a qualified servicing facility as applicable must conduct the following inspections and tests: Monthly inspections required by NFPA 10 may be conducted by the owner, operator, person-in-charge, or a designated member of the crew. Monthly checks on portable fire extinguishers were not completed.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 25 November 2025
Resolved 31 December 2025
Resolution: O/O provided objective evidence showing monthly fire extinguisher inspections were completed.
07 - Fire Safety › N/A - No Subsystem › Fire pumps and its pipes
Issued 16 October 2024
Resolved
At each initial and subsequent inspection for certification, the owner or managing operator shall be prepared to conduct tests and have the vessel ready for inspection of its fire protection equipment, including the following: Operation of the fire main system and checking of the pressure at the most remote and highest outlets. When fire main was energized, the pipe burst while under pressure in the #3 void. Apply permanent repairs to fire main to the satisfaction of the attending marine inspector.
Action required: 701 - Prior to carriage of passengers/cargo
Due 30 October 2024
Resolved 4 November 2024
Resolution: Vessel made appropriate repairs.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Gauges, thermometers, etc
Issued 16 October 2024
Resolved
Gauges to indicate engine revolutions per minute (RPM), jacket water discharge temperature, and lubricating oil pressure must be provided for all propulsion engines installed in the vessel. The gauges must be readily visible at the operating station. Port forward engine oil pressure gauge at operating station was reading improper pressure level.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 30 October 2024
Resolved 4 November 2024
Resolution: Pressure gauge was repaired.
07 - Fire Safety › N/A - No Subsystem › Fire control plan
Issued 16 October 2024
Resolved
A fire control plan must be posted on the vessel in a location that is accessible and visible to all passengers. The plan must show escape routes, areas of refuge, embarkation stations, the location of fire protection/emergency equipment, compartment titles and hazard classification of accommodation and service spaces, and structural fire protection boundaries. Vessel's fire control plan is missing all required information except for fire protection/emergency equipment. Update plan to reflect required information/equipment that pertains to vessel.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 15 November 2024
Resolved 14 January 2025
Resolution: Revised fire control plan approved and onboard vessel.
02 - Structural Conditions › N/A - No Subsystem › Decks - corrosion
Issued 10 January 2024
Resolved
The construction and arrangement of a vessel must allow the safe operation of a vessel in accordance with the terms of the Certificate of Inspection giving consideration to provisions for a seaworthy hull.
Pitting was found on the over head of the vessel's number 2 void, including approximately 10 small holes through the deck where the forward part of the superstructure meets the weather deck. Provide repair proposal and make effective repairs to the satisfaction of the attending Marine Inspector. 46 CFR 116.100(a)
Action required: 701 - Prior to carriage of passengers/cargo
Due 10 January 2024
Resolved 1 March 2024
Resolution: 3" circular inserts accepted, visually inspected satisfactorily inside weathertight superstructure.
02 - Structural Conditions › N/A - No Subsystem › Decks - corrosion
Issued 10 January 2024
Resolved
he construction and arrangement of a vessel must allow the safe operation of a vessel in accordance with the terms of the Certificate of Inspection giving consideration to provisions for a seaworthy hull.
Goose-neck for aft ballast tank vent on the starboard side of the aft weather-deck, found with pinhole wastage where the standpipe meets the deck. Repair to the satisfaction of the attending Marine Inspector. 46 CFR 116.100(a)
Action required: 701 - Prior to carriage of passengers/cargo
Due 10 January 2024
Resolved 1 March 2024
Resolution: No crack inspected in weld after paint was removed. O/O to weld support bracket to prevent vibration and damage. All sat.
02 - Structural Conditions › N/A - No Subsystem › Hull - corrosion
Issued 19 January 2023
Resolved
The owner or managing operator of a vessel shall ensure that the vessel complies with the laws and regulations applicable to the vessel and that the vessel is otherwise satisfactory for the intended service. Excessive pitting was observed in the #6 void, port #4 bulkhead stiffener from centerline. Two substantial pits were observed with a depth of .270 and .210. Vessel representative shall make a final determination through visual inspection of the hull or by other NDT methods to determine plate thickness.
Action required: 705 - Other - as specified
Due 19 January 2023
Resolved 10 January 2024
Resolution: Verified area fitted with 1/2" + 3/8" plate with primer and corrosion arrested internally. No corossion identified, NDT not required at this time.
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 29 October 2020
Resolved
All escape hatches shall be marked on both sides using at least 1" letters "Emergency Exit, Keep Clear". Engine room emergency escape hatch was not marked on either side. Crew mounted placards during the inspection.
46 CFR 185.30-15
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 29 October 2020
Resolved 29 October 2020
Resolution: Placards mounted on both sides of hatch during inspection.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 29 October 2020
Resolved
All electrical equipment must be clearly marked and identified. The port and starboard steering motor breakers were marked with the wrong amperage. (see pictures)
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 12 November 2020
Resolved 11 November 2020
Resolution: Vessel rep provided steering pump breaker proper labled placards.
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 26 November 2019
Resolved
The general construction of the vessel shall be such as to minimize fire hazards insofar as reasonable and practicable. Vessels contracted for on or after July 1, 1961, which carry more than 150 passengers shall meet the requirements of subpart 72.05 of Subchapter H (Passenger Vessels) of this chapter. The application of these requirements to specific vessels shall be as determined by the Officer in Charge, Marine Inspection.
Vessel's machinery space on the main deck and on the second deck do not meet the fire control boundary requirements of A-60 boundaries. Submit plans to OCMI for modifications to the spaces to meet structural fire protection requirements IAW: SUBCHAPTER H & NVIC 9-97.
46 CFR 177.10-5
Action required: 16 - Rectify deficiencies w/in 14 days
Due 10 December 2019
Resolved 21 May 2020
Resolution: New SFP completed satisfactory
09 - Working and Living Conditions › 092 - Working Conditions › Machinery
Issued 29 October 2019
Resolved
Exhaust piping shall be led to the point of escape with
a minimum number of bends or elbows. It shall be
gastight throughout its length and shall be properly
supported by non-combustible hangers or blocks.
Marine inspector noted evidence of exhaust leak in
void #6 via visual condition of lagging and through
smell while machinery was online. Locate source or
exhaust leak and make repairs as nessecary to
resolve issue.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 November 2019
Resolved 5 February 2020
Resolution: Witnessed a satisfactory welding around the exhaust.
09 - Working and Living Conditions › 092 - Working Conditions › Machinery
Issued 29 October 2019
Resolved
Provide mitigation plan to prevent personnel exposure
to exhaust hazard in #6 void space to remain in effect
until deficiency #1 is corrected.
Condition: Damaged By Earlier Event
Action required: 10 - Deficiency Rectified
Due 29 October 2019
Resolved 29 October 2019
Resolution: Mitigation plan provided. Added to documents.
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 29 October 2019
Resolved
All escape hatches and other emergency exits shall be
marked on both sides using at least 1-inch letters:
"Emergency Exit, Keep Clear", unless such markings
are deemed unnecessary by the Officer in Charge,
Marine Inspection. Fwd engine room escape hatch is
not properly marked on engine room side. Mark hatch
as required.
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 29 October 2019
Resolved 29 October 2019
Resolution: Emergency escape properly labeled.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 29 October 2019
Resolved
All vessels except non-self-propelled vessels shall be
provided with suitable steering apparatus. Upper
rudder post plate on starboard steering arm is wasted
and visually bent due to weakened metal. Replace
stbd upper rudder post plate.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 November 2019
Resolved 4 February 2020
Resolution: Rudder post plate was replaced.
07 - Fire Safety › N/A - No Subsystem › Division - decks, bulkheads and penetrations
Issued 29 October 2019
Resolved
Class A bulkheads shall be so insulated with approved
structural insulation, bulkhead panels, or deck
covering that the average temperatures on the
unexposed side would not rise more than 250 °F.
Insulation not properly installed in aft stbd corner of
engine room. Install missing insulation.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 12 November 2019
Resolved 12 November 2019
Resolution: Missing insulation replaced.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Gauges, thermometers, etc
Issued 29 October 2019
Resolved
A battery charger intended for connection to a
commercial supply voltage shall have an ammeter that
is readily visible shall be included in the battery
charger circuit. Battery charger on fwd stbd bulkhead
in engine room has a non operational ammeter that is
not properly mounted to the charger housing. Provide
operational ammeter as required.
Condition: Damaged By Earlier Event
Action required: 16 - Rectify deficiencies w/in 14 days
Due 12 November 2019
Resolved 12 November 2019
Resolution: Battery charger meter replaced.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Covers (hatchway-, portable-, tarpaulins, etc.)
Issued 18 December 2018
Resolved
Each hatch cover must have a securing device. Lazarette hatch cover missing securing device.
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Resolved 18 December 2018
Resolution: Securing device installed.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 18 December 2018
Resolved
Engine exhaust piping shall be gastight throughout its length. Stbd forward exhaust was found with excessive pitting at the point where it meets the side shell. Make gastight. 46CFR182.20-20
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 1 January 2019
Resolved 2 January 2019
Resolution: Pitting cleaned out and re-welded, all sat.
02 - Structural Conditions › N/A - No Subsystem › Hull - cracking
Issued 18 December 2018
Resolved
At each vessel inspection, all observed hazardous situations must be corrected. In lazarette, stbd quarter has significant inset, above which is a crack in the side shell showing daylight. Make side shell watertight. On port quarter, one cracked weld marked for repair. 46CFR115.830
Condition: Damaged By Earlier Event
Action required: 16 - Rectify deficiencies w/in 14 days
Due 1 January 2019
Resolved 8 January 2019
Resolution: Crack welded, all sat.
04 - Emergency Systems › N/A - No Subsystem › Man Overboard Drill (MOB)
Issued 18 December 2018
Resolved
At each inspection, the marine inspector may require that man overboard/fire drill be held under simulated emergency conditions. Unable to conduct drills due to strong winds.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 1 January 2019
Resolved 8 January 2019
Resolution: Satisfactory man overboard and fire drills conducted.
10 - Safety of Navigation › N/A - No Subsystem › Automatic Identification System (AIS)
Issued 10 September 2018
Resolved
Vsl is broadcasting no IMO #, not broadcasting a Call Sign, smaller than expected vessel length and no static draft information.
Condition: Invalid
Action required: 705 - Other - as specified
Resolved 1 November 2018
Resolution: While running a query in VIVS, all information had been updated and AIS was broadcasting the proper information.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 20 August 2018
Resolved
Remove & replace the wasted pipe on the forward generator raw water intake line. Prove proper operation of both generators while operating underway. Conduct sea trials to prove all components are in working order.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 20 August 2018
Resolved 21 August 2018
Resolution: Removed & replaced the wasted pipe on the forward generator raw water intake line. Proved proper operation of both generators while operating underway. Conducted sea trials to prove all components were in working order.
Engineering › Freshwater Generation System › Piping
Issued 21 March 2018
Resolved
Several wasted pipes discovered in exhaust compartment (void #6). Issued requirement to make permanent repairs.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 23 April 2018
Resolved 13 April 2018
Resolution: Made permanent repairs on the wasted pipes.
Construction/Loadline › Hull › Hull Plating
Issued 21 March 2018
Resolved
Significant inset was discovered on the port side of the lazerette, issued requirement to make permanent repairs.
Action required: 705 - Other - as specified
Due 9 April 2019
Resolved 18 December 2018
Resolution: Permanent repair made, all sat.
Operations/Management › Vessel Activity › Underway
Issued 21 March 2018
Resolved
Vessel replaced the port outboard shaft and realigned to gear, issued requirement to conduct underway sea trials.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 13 April 2018
Resolution: Conducted underway sea trials with satisfactory results.
Engineering › Feedwater/Condensate Water System › Piping
Issued 21 March 2018
Resolved
Repair cracked weld on starboard inboard raw water pipe intake for the engine at the forward bulkhead in void #6. Conduct additional rounds every 30 minutes to ensure condition does not worsen.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 18 April 2018
Resolved 17 April 2018
Resolution: Weld was repaired and air lance/soap tested. All sat.
Engineering › Engine Controls (Electric/Electronic) › Software
Issued 9 November 2017
Resolved
Troubleshoot and repair stbd inboard MDE over speed alarm.
Condition: Invalid
Action required: 705 - Other - as specified
Due 23 November 2017
Resolved 21 November 2017
Resolution: Repaired sensor in alarm. All sat.
Electrical › Electric Supply System (service) › Battery Charger
Issued 9 November 2017
Resolved
Repair or renew battery charger in pilothouse.
Condition: Invalid
Action required: 705 - Other - as specified
Due 23 November 2017
Resolved 30 November 2017
Resolution: Battery charger was replaced with new unit.
Electrical › Electrical Distribution System (service) › Panelboard
Issued 9 November 2017
Resolved
Provide cover for distribution panel in pilothouse.
Condition: Invalid
Action required: 705 - Other - as specified
Due 23 November 2017
Resolved 21 November 2017
Resolution: Replaced distribution panel cover.
Operations/Management › Drills/Instruction › Man Overboard Recovery
Issued 9 November 2017
Resolved
Provide platform on MOB ladder.
Condition: Invalid
Action required: 705 - Other - as specified
Due 23 November 2017
Resolved 30 November 2017
Resolution: Platform on MOB ladder was added.
Construction/Loadline › Structures › Transverse Bulkhead
Issued 9 November 2016
Resolved
Crop and renew wasted bulkhead IWO sewage tank.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 28 November 2016
Resolution: Approx area of 20" X 30" aluminum plate was croppped out and renewed.
Engineering › Sea-water System (primary cooling) › Piping
Issued 9 November 2016
Resolved
Repair or replace wasted salt water overboard piping for generators.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 28 November 2016
Resolution: Salt water piping was replaced in kind.
Engineering › Freshwater Generation System › Piping
Issued 9 November 2016
Resolved
Repair or replace wasted fresh water piping in exhaust void.
Action required: 705 - Other - as specified
Due 28 November 2016
Resolved 28 November 2016
Resolution: Fresh water piping was replaced in kind.
Operations/Management › Drills/Instruction › Man Overboard Recovery
Issued 26 October 2016
Resolved
During MOB drill rescue platform was inadequate. Vessel to provide satisfactory arrangements to the satisfaction of the attending marine inspector.
Condition: Invalid
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 27 October 2016
Resolution: Received photograph from vessel rep showing adequate modifications made to the rescue platform.
Construction/Loadline › Structures › Door
Issued 26 October 2016
Resolved
Engine room door does not latch.
Condition: Invalid
Action required: 705 - Other - as specified
Due 9 November 2016
Resolved 9 November 2016
Resolution: Engine door handle assembly was replaced with new.
Construction/Loadline › Structures › Door
Issued 26 October 2016
Resolved
Stair tower doors have carpet installed on the threshold and doors do not self close.
Condition: Invalid
Action required: 705 - Other - as specified
Due 9 November 2016
Resolved 9 November 2016
Resolution: Stair tower carpet was removed from both door thresholds and properly close.
Documentation › Manifests/Lists › Muster List/Emergency Instructions
Issued 26 October 2016
Resolved
Provide instructions for fixed firefighting arrangements.
Condition: Invalid
Action required: 705 - Other - as specified
Due 9 November 2016
Resolved 9 November 2016
Resolution: Instruction were provided for fixed fire fighting system.
Engineering › Compressed Air System (control) › Receiver/Bottle
Issued 26 October 2016
Resolved
Make pressure vessel available for inspection and replace relief valve.
Condition: Invalid
Action required: 705 - Other - as specified
Due 9 November 2016
Resolved 9 November 2016
Resolution: Pressure vessel was made available for inspection, conducted satisfactory internal visual inspection. Tested new safety relief, test sat.
Construction/Loadline › Penetrations › Pipe Flange
Issued 26 October 2016
Resolved
Make permanent repairs to A/C raw water line in fuel void. A/C not to be used until repaired.
Condition: Invalid
Action required: 705 - Other - as specified
Due 9 November 2016
Resolved 9 November 2016
Resolution: A/C piping and bulkhead coupling was replaced in kind and satisfactorily tested.
Navigation › Piloting/Steering › Magnetic Compass
Issued 26 October 2016
Resolved
Compass light inoperable. Vessel restricted to daylight operations.
Condition: Invalid
Action required: 705 - Other - as specified
Due 9 November 2016
Resolved 9 November 2016
Resolution: Compass light was inspected and found to be operational.
Documentation › Certificates/Documents › Stability Letter
Issued 26 October 2016
Resolved
Provide current stability letter.
Condition: Invalid
Action required: 705 - Other - as specified
Due 9 November 2016
Resolved 9 November 2016
Resolution: Current stability letter was provided.
Engineering › Diesel Engine (propulsion-direct drive) › Piping (exhaust)
Issued 26 October 2016
Resolved
Make exhaust space safe and available for inspection. High levels of CO2 were found indicating an exhaust leak. Repair exhaust leak.
Condition: Invalid
Action required: 705 - Other - as specified
Due 9 November 2016
Resolved 9 November 2016
Resolution: Exhaust void was made available for inspection.
Engineering › Compressed Air System (control) › Valve
Issued 13 August 2016
Resolved
Vessels propulsion controls (pnuematic) inop for outboard starboard engine (locked in forward). Repair and test to the satisfaction of MI.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 18 August 2016
Resolution: New valve has been installed and tested by attending [name withheld].
Accommodation/Occupational Safety › Other Accommodation Spaces › Recreation Space
Issued 13 August 2016
Resolved
02 Windows damaged due to collision. Replace to the satisfaction of attending MI.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 18 August 2016
Resolution: Windowns have been replaced and inspected. SAT.
Engineering › Diesel Engine (propulsion-reduction gear) › Piping (exhaust)
Issued 20 January 2016
Resolved
Crack was found in port fwd engine exhaust in void #6. Repair. 46CFR182.15-20(d)
Action required: 705 - Other - as specified
Due 3 February 2016
Resolved 21 January 2016
Resolution: Exhaust pipe repaired.
Electrical › Electrical Distribution System (service) › Non-conducting Deck Covering
Issued 20 January 2016
Resolved
Have non-conductive mat in front of switchboard. (Corrected on the spot)
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 5 February 2016
Resolved 20 January 2016
Resolution: corrected on the spot.